Fire Department Connections

Rev 1 · Updated Jun 13, 2026 · View history

1 Scope

NOTE This standard covers fire department connections (FDCs): the listed assemblies that allow fire department pumper apparatus to inject supplemental water into a building's automatic sprinkler, standpipe, or combination fire protection system. (1.1)
NOTE The covered assembly includes the FDC body, inlets (2½ in. National Standard Thread, Storz large-diameter, or combination), swing clappers, the integral or in-riser check valve, the automatic ball drip drain, the pipe connection to the system riser, protective inlet caps, and the required identification signage. (1.2)
NOTE FDC configurations covered are wall-mounted exposed (Siamese), wall-mounted recessed (flush box), freestanding post-type, and sidewalk box assemblies on commercial, institutional, industrial, and multi-family residential buildings of all sizes. (1.3)
NOTE This standard applies to new construction and to additions or retrofits of existing fire protection systems where a new or relocated FDC is required by code or by AHJ directive. (1.4)
NOTE The fire department connection is the supply interface to the protected system, not the system itself. (1.5)
NOTE The system piping, risers, control valves, and hydraulic design that the FDC feeds are governed by the system standards: Wet Pipe Fire Sprinkler Systems, Dry Pipe Fire Sprinkler Systems, Pre Action And Deluge Sprinkler Systems, and Standpipe Systems. This standard ends at the listed check valve that separates the FDC from the system riser. (1.6)
NOTE The following are excluded from this standard and are governed elsewhere. (1.7)

2 Referenced Standards

2.1Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
NOTE Where the AHJ adopts a different edition or imposes a local amendment, the AHJ-adopted requirement shall govern. (2.3)
Standard Title
NFPA 13 (2022) Standard for the Installation of Sprinkler Systems (Section 8.17, fire department connections)
NFPA 13R (2022) Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies
NFPA 14 (2019) Standard for the Installation of Standpipe and Hose Systems (Section 7.12, fire department connections)
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
NFPA 291 (2022) Recommended Practice for Fire Flow Testing and Marking of Hydrants
NFPA 1 (2021) Fire Code
IFC 2021 International Fire Code, Section 912 (Fire Department Connections)
IBC 2021 International Building Code, Section 905 (Standpipe Systems)
UL 405 Standard for Fire Department Connections
ASME B1.20.7 Hose Coupling Screw Threads (National Standard Thread, NST/NH)

3 Submittals

3.1 Action Submittals

3.1.1The Contractor shall submit the following action submittals for review and approval before fabrication or ordering:
  • Product data for the FDC body, inlets, clappers, check valve, automatic ball drip, caps, and identification plate, with UL 405 listing markings shown.
  • Manufacturer's certification of the inlet thread type and confirmation that it matches the AHJ-specified fire department thread standard.
  • Shop drawings showing FDC type, inlet count and size, body material and finish, pipe connection size and type, ball drip orientation, and mounting height referenced to finished grade.
  • Layout drawing showing FDC location, the 3 ft access clearance radius, distance to the nearest hydrant, and coordination with civil, landscape, and architectural elevations.
  • Signage submittal showing the engraved or cast legend, letter height, and the system type identified.
Action Submittalscheckbox
Product data (body, inlets, clappers, check valve, ball drip, caps, plate)
Inlet thread certification matching AHJ standard
Shop drawings (type, inlet count/size, material, finish, connection)
Location layout with access clearance and hydrant distance
Signage legend and letter-height submittal

3.2 Closeout Submittals

3.2.1The Contractor shall submit the following closeout submittals before Substantial Completion:
  • Field acceptance test report documenting cap removal, inlet inspection, and manual clapper operation.
  • Hydrostatic test record for the FDC piping where tested with the connected system.
  • Operation and maintenance data, including NFPA 25 inspection frequency for the installed FDC.
  • AHJ acceptance documentation for FDC location, thread type, and any locking-cap arrangement.
Closeout Submittalscheckbox
Field acceptance test report
Hydrostatic test record
O&M data with NFPA 25 inspection frequency
AHJ acceptance documentation

3.3 Informational Submittals

3.3.1The Contractor shall submit the following informational submittals:
  • Written confirmation from the AHJ or fire department of the required inlet thread standard.
  • Pre-construction meeting record documenting the fire marshal's approval of the FDC location.
  • Manufacturer's UL 405 listing certificate and pressure rating documentation.
Informational Submittalscheckbox
AHJ written thread-standard confirmation
Fire marshal location-approval record
UL 405 listing and pressure rating documentation

4 Quality Assurance

4.1Each FDC assembly shall be listed to UL 405 in the as-installed configuration.
4.2The Contractor shall coordinate the FDC location with the AHJ before completing the fire protection design.
4.3.1The FDC location shall be confirmed in writing with the AHJ at or before the fire marshal's pre-construction meeting.
4.3.2The inlet thread type shall be confirmed in writing with the serving fire department before the FDC is ordered.
4.4The installing contractor shall be a fire protection contractor licensed in the jurisdiction of the work.
4.5Replacement parts (clappers, caps, drip) shall be from the FDC manufacturer or a UL 405-listed equivalent.

5 Environmental and Service Conditions

5.1The FDC body and trim material shall be selected for the corrosion exposure at the installed location.
NOTE Standard rough or polished brass is appropriate for ordinary atmospheric exposure. In coastal, marine, or chemically aggressive industrial environments, chloride and airborne contaminants pit and dezincify brass, seizing caps and clappers; a stainless steel body is specified for those exposures. The exposure assessment is made for the specific site, not assumed from the building type. (5.2)
5.2.1A stainless steel FDC body shall be specified where the FDC is exposed to coastal salt air, marine spray, or a corrosive industrial atmosphere.
5.3An automatic ball drip shall be provided where any portion of the FDC piping is subject to freezing.
NOTE Water trapped between the system check valve and the inlet caps has no path to drain on its own. In a freeze-prone location it freezes, expands, and can crack the FDC body or unseat the clappers. NFPA 13 Section 8.17.2.6 requires an automatic drip valve for exposed or minimally heated FDCs. The drip discharges this trapped water continuously to a safe point. (5.4)
5.4.1The automatic ball drip shall discharge to a location where the discharge will not create an ice hazard on walking surfaces or apparatus approaches.
5.4.2The automatic ball drip shall be installed in the orientation (horizontal, vertical, or either) for which the device is listed.
Corrosion Environment / Body Materialradio
Ordinary atmospheric - brass
Ordinary atmospheric - chrome-plated brass
Coastal / marine / corrosive industrial - stainless steel
Automatic Ball Drip Required (Freeze Exposure)radio
Yes - FDC piping subject to freezing
No - FDC piping in continuously heated space
Automatic Ball Drip Listed Orientationradio
Horizontal
Vertical
Either (universal)

6 FDC Type and Mounting

6.1The FDC type shall be selected to suit the building wall condition, site access, and AHJ direction.
NOTE The four common types serve different site conditions. The wall-mounted exposed Siamese is the default and the easiest to operate. The recessed flush type hides the body in a wall box for architectural integration and is required by some AHJs and architects. The freestanding post-type is used when no suitable wall location exists or when the AHJ wants the connection remote from the building. The sidewalk box is used where the FDC must sit at or below a paved surface. (6.2)
FDC Typeradio
Wall-mounted exposed (Siamese)
Wall-mounted recessed (flush box)
Freestanding post-type
Sidewalk box
6.3The FDC shall be located in an approved, visible position accessible to fire department apparatus.
NOTE IFC Section 912.2.1 requires the FDC to be in a visible, identifiable location that responding apparatus can reach. Section 912.2.2 governs height, and Section 912.3 governs the unobstructed clearance around the connection. These are mandatory dimensional requirements, not preferences. (6.4)
6.4.1The FDC shall be located on the street side of the building or as otherwise directed in writing by the AHJ.
6.4.2Inlet centerlines shall be installed not less than 24 in. and not more than 60 in. above the adjacent finished grade.
6.4.3A minimum 3 ft (914 mm) unobstructed clearance shall be maintained on all sides of each FDC inlet.
6.4.4The FDC location shall be coordinated across the civil, landscape, and architectural drawings before those drawings are issued for construction.
6.4.5No wall, fence, sign, or planting shall be placed within the required 3 ft clearance of any FDC inlet.
NOTE FDC mounting height frequently generates RFIs when finished grade changes late in design. (6.5)
NOTE The 24 in. to 60 in. window is measured to finished grade, not to the slab or to the pipe penetration. When site grading is revised after the FDC elevation is set, the as-built inlet height can fall outside the code window. Setting the inlet centerline against the final grading plan, and rechecking it when grading changes, prevents the rework. (6.6)
Inlet Centerline Height Above Finished Graderange
in
2460
Default: 36 in
6.7The FDC shall be located within 100 ft of the nearest fire hydrant unless the AHJ approves a greater distance in writing.
Maximum FDC-to-Hydrant Distancerange
ft
40100
Default: 100 ft

7 Inlets and Sizing

7.1The number and size of FDC inlets shall be determined by the served system type and its demand, not by a fixed default.
NOTE Defaulting to "two 2½-inch inlets" regardless of demand is one of the most common FDC errors. The inlet count is a hydraulic requirement. For sprinkler systems, NFPA 13 sets the minimum on the basis of riser size. For standpipe and combination systems, NFPA 14 Section 7.12.3 requires one 2½-inch inlet for each 250 gpm of system demand, so a 1,000 gpm standpipe system requires four inlets, not two. (7.2)
7.2.1Sprinkler-system FDCs serving a riser larger than 3 in. shall be provided with not fewer than two 2½-inch inlets.
7.2.2A single 2½-inch inlet may be used for a sprinkler system whose riser is 3 in. or smaller.
7.2.3An NFPA 13R low-rise residential system shall be provided with a single 1½-inch inlet where a full NFPA 13 connection is not required.
7.2.4Standpipe and combination-system FDCs shall be provided with one 2½-inch inlet for each 250 gpm of system demand.
Served System Typeradio
Sprinkler (NFPA 13)
Sprinkler - low-rise residential (NFPA 13R)
Standpipe (NFPA 14)
Combination sprinkler and standpipe
Inlet Configurationradio
Twin 2½-inch NST
Single 2½-inch NST
Single 1½-inch (NFPA 13R)
Single Storz 4 in. (500 gpm)
Single Storz 5 in. (750 gpm)
Combination - twin 2½-inch plus Storz
Number of 2½-inch Inletsrange
inlets
16
Default: 2 inlets
7.3The inlet thread type shall match the standard used by the serving fire department.
NOTE National Standard Thread (NST/NH) per ASME B1.20.7 is the common default, but it is not universal. Several major cities - Chicago, Pittsburgh, New York, and others - use proprietary local thread forms, and a number of departments are standardizing on Storz large-diameter connections. Specifying NST without written confirmation from the AHJ is among the most common and most expensive FDC errors, because a mismatched FDC body must be replaced after the wall is built. Always obtain the thread standard in writing before ordering. (7.4)
7.4.1The inlet thread shall be the National Standard Thread (NST/NH) per ASME B1.20.7 unless the AHJ specifies a different local thread standard in writing.
Inlet Thread Standardradio
National Standard Thread (NST/NH) per ASME B1.20.7
Local fire department thread standard (per AHJ confirmation)
NOTE Storz large-diameter inlets are increasingly required where the department runs large-diameter hose. (7.5)
NOTE A single Storz inlet replaces the twin 2½-inch arrangement for departments equipped with large-diameter hose (LDH). The 2023 NFPA guidance rates a 4 in. Storz inlet at 500 gpm and a 5 in. Storz inlet at 750 gpm. A Storz inlet is genderless and connects faster than threaded inlets, which is why adoption is growing. Where the existing FDC is threaded, a listed thread-to-Storz swivel adapter can be added, but a purpose-built Storz body is preferred on new work. (7.6)
Storz Inlet Rating (where used)radio
4 in. Storz - 500 gpm
5 in. Storz - 750 gpm
Not used

8 Body, Clappers, and Check Valve

8.1The FDC body, inlets, and clappers shall be of the listed assembly construction and pressure rating.
NOTE The body is the cast structure that carries the inlets and joins them to the system pipe connection. Each inlet contains a swing clapper that opens under pumper pressure and closes to retain system water when the inlet is not in use. UL 405 listing covers the construction, the clapper action, and the pressure rating of the complete assembly. (8.2)
8.2.1The FDC assembly shall be rated for not less than 175 psi working pressure.
8.2.2Each inlet shall be provided with a swing clapper that seats against backpressure from the system side.
Body Material and Finishradio
Rough brass
Polished brass
Chrome-plated brass
Stainless steel
Assembly Working Pressure Ratingradio
175 psi (minimum)
300 psi (standard brass)
600 psi (stainless steel)
Clapper Arrangementradio
Independent swing clapper per inlet
Single common clapper
8.3A listed check valve shall be provided in the FDC connection to the system riser.
NOTE The check valve prevents system water - and any contaminant the system may have picked up - from flowing back into the FDC and out to the street supply. NFPA 13 requires it, and it is sometimes omitted on simple systems, which is a code violation and a cross-connection hazard. The check valve may be built into the FDC body as a clapper assembly or provided as a separate listed check valve in the riser; either arrangement satisfies the requirement when listed for the service. (8.4)
8.4.1A listed check valve shall be installed between the FDC and the connection to the system riser to prevent backflow into the water supply.
Check Valve Arrangementradio
Swing clapper integral to FDC body
Separate listed check valve in riser connection

9 Pipe Connection

9.1The FDC pipe connection size shall match the served system demand.
NOTE NFPA 13 sets a 4 in. pipe connection from the FDC to the riser as the default for most sprinkler systems. High-demand combination systems require a larger connection sized by the hydraulic calculation. The connection is most commonly a female NPT threaded inlet on the FDC body; a flanged connection is used on larger or higher-pressure work. (9.2)
9.2.1The FDC shall connect to the system riser with a 4 in. connection for ordinary NFPA 13 sprinkler systems.
9.2.2The connection shall be increased above 4 in. where the hydraulic calculation for a high-demand combination system requires a larger pipe.
FDC-to-Riser Connection Sizeradio
4 in. (NFPA 13 default)
6 in.
8 in.
Connection Typeradio
Female NPT threaded
Flanged

10 Caps and Security

10.1Each inlet shall be fitted with a protective cap to keep debris out of the body.
NOTE Brass caps with chains are the traditional choice and resist vandalism better than plastic. Plastic break-away caps are inexpensive and visibly indicate tampering. Locking security caps deter theft of the brass body and prevent debris insertion in vandalism-prone areas, but they require a key carried by the responding department. (10.2)
Inlet Cap Typeradio
Brass cap with chain
Plastic break-away cap
Locking security cap (keyed)
10.3Locking caps shall be coordinated with the serving fire department before they are specified.
NOTE A locking cap that the responding company cannot open quickly is an operational hazard - it can delay a supplemental supply at the moment it is needed. Locking caps are only acceptable where the fire department carries the matching key or where a standardized regional key system is in use. The arrangement is confirmed with the department, not assumed. (10.4)
10.4.1Locking inlet caps shall be provided only where the serving fire department approves the locking system and carries the matching key.

11 Signage and Identification

11.1A permanent identification sign shall be provided at each FDC stating the system it serves.
NOTE NFPA 13 requires a sign with raised or engraved letters not less than 1 in. tall identifying the served system. Adhesive labels are not compliant and are routinely rejected by the AHJ. The legend names the system type so that the responding company connects to the correct supply, which matters where a site has more than one FDC. (11.2)
11.2.1The FDC sign shall use raised or engraved letters not less than 1 in. in height.
11.2.2The sign legend shall read SPRINKLER, STANDPIPE, or STANDPIPE AND SPRINKLER to match the served system.
11.2.3An adhesive or printed label shall not be used in place of the raised or engraved sign.
FDC Signage Legendradio
SPRINKLER
STANDPIPE
STANDPIPE AND SPRINKLER
Sign Letter Heightrange
in
13
Default: 1 in
11.3A pressure demand note shall be added to the FDC sign where the system demand at the FDC exceeds 150 psi.
NOTE Where the system requires more than 150 psi at the FDC to meet demand, the responding pump operator must know the target pressure to charge the connection correctly. The pressure demand is added to the identification sign as a note so the information is at the connection rather than buried in the record drawings. (11.4)
Pressure Demand Note Required (> 150 psi)radio
No - system demand at FDC is 150 psi or less
Yes - add pressure demand note
11.5A single FDC that serves more than one building or zone shall be marked to identify every location served.
NOTE NFPA 14 requires an additional sign on a combination or shared FDC that lists all of the buildings or zones the connection feeds. Without it, a responding company cannot tell from the FDC which areas will be supplied, and a connection meant for one zone can be misapplied to another. (11.6)
11.6.1A combination or shared FDC shall carry an additional sign identifying each building or zone it serves.

12 Testing

12.1Each FDC assembly shall be factory tested before shipment.
NOTE UL 405 requires a hydrostatic proof test of the assembly and verification of clapper operation. This is a production test of the listed product, distinct from the field acceptance test. (12.2)
12.2.1Each FDC body shall be factory hydrostatically tested at 300 psi for 1 minute with clapper operation verified.
12.3The installed FDC shall be field tested as part of system acceptance.
NOTE Field acceptance confirms the as-installed connection is sound and operable. Caps are removed, the inlets and clappers are inspected, and each clapper is operated by hand to confirm it swings freely and reseats. The FDC piping is included in the hydrostatic test of the connected system. NFPA 25 governs the inspection and test frequency for the life of the installation; the FDC is inspected at least annually thereafter. (12.4)
12.4.1Each inlet cap shall be removed and the inlet and clapper inspected at field acceptance.
12.4.2Each clapper shall be operated by hand to confirm free movement and proper reseating.
12.4.3The FDC piping shall be hydrostatically tested with the connected system at the system test pressure.
Field Acceptance Testcheckbox
Caps removed and inlets inspected
Clappers operated and reseating verified
Automatic ball drip operation verified
FDC piping hydrostatically tested with system
Ongoing Inspection Frequency (NFPA 25)radio
Quarterly
Annual

13 Installation

13.1The FDC shall be installed at the approved location and orientation shown on the drawings.
NOTE The mounting position, the pipe routing to the riser, and the discharge point of the ball drip are spatial decisions that cannot be reduced to a datasheet field; they are coordinated on the drawings. (13.2)
13.2.1The FDC shall be installed at the location shown FDC plan location.
13.2.2The FDC piping shall be routed to the system riser as shown FDC riser connection.
13.2.3The automatic ball drip discharge shall terminate at the point shown ball drip discharge.
13.3The FDC shall be installed plumb and rigidly supported so that connecting hose loads are not transferred to the system piping.
13.3.1A freestanding or post-type FDC shall be set on a foundation sized for the apparatus connection loads and frost depth at the site.
13.3.2The inlet face shall be set flush with or proud of the finished wall surface so that caps and couplings can be operated without obstruction.
13.3.3Backfill and finished grade around a sidewalk or freestanding FDC shall be set so that the inlet centerline meets the required height above final grade.
13.4The FDC piping shall be protected against freezing consistent with the ball drip provision.
13.4.1FDC piping in a freeze-prone location shall be arranged so that no water is trapped on the system side of the ball drip.

14 Delivery, Storage, and Handling

14.1FDC assemblies shall be delivered, stored, and handled so that machined faces and threads are not damaged.
NOTE The inlet threads and clapper seats are the working surfaces of the connection; a nicked thread or a dented seat can prevent a tight hose coupling or a proper clapper reseat. Protective caps and plugs stay in place until installation, and the assemblies are kept off the ground and dry. (14.2)
14.2.1Inlet caps and shipping plugs shall remain installed until the FDC is connected and tested.
14.2.2FDC assemblies shall be stored off the ground, under cover, and protected from construction dust and debris.
14.2.3Damaged threads, seats, or clappers shall be cause for rejection of the assembly.

15 Warranty

15.1The FDC assembly shall be warranted against defects in material and workmanship.
15.1.1The Contractor shall provide the manufacturer's standard written warranty for the FDC assembly, not less than one year from Substantial Completion.
Warranty Periodradio
1 year (standard)
2 years
5 years

16 Spare Parts

16.1Spare consumable components shall be furnished so that field-damaged or stolen parts can be replaced without ordering delay.
NOTE Caps and chains are the parts most often lost to theft or vandalism, and clapper rubbers wear over time. A small spare stock keeps the connection serviceable. (16.2)
16.2.1The Contractor shall furnish spare inlet caps and chains matching each installed inlet size and thread type.
Spare Parts to Furnishcheckbox
Spare inlet caps and chains (per inlet size/thread)
Spare clapper rubbers
Spare automatic ball drip
Spare identification sign

Edit this page