Grounding and Bonding for Electrical Systems

Revision 4 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 11, 2026 +2 −2

Migrate datasheet deferrals to drawing_ref + default: deferred
Showing changes from Rev 3 to Rev 4 in Grounding and Bonding for Electrical Systems.
Tag changes −Electrical−Grounding−Low Voltage
---
title: Grounding and Bonding for Electrical Systems
367 unchanged lines
- "250 kcmil"
- "350 kcmil"
default: "Per NEC Table 250.66 — see drawings"
+default: deferred
```
42 unchanged lines
label: Equipment Grounding Conductor Type
type: radio
+drawing_ref: true
options:
- "Insulated or covered copper conductor in every raceway and cable"
- "Metallic raceway serving as the equipment grounding conductor"
- "Combination per circuit (see drawings)"
default: "Insulated or covered copper conductor in every raceway and cable"
```
564 unchanged lines
## Where the achieved ground resistance is marginal relative to the acceptance criterion, the Engineer may require a re-test during the warranty period to confirm that seasonal soil changes have not raised the resistance above the acceptance value.

View current revision