SynC · SynC Standards

Low Voltage Switchgear

Rev5
IssuedJun 22, 2026

Revision history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

NOTE This specification covers metal-enclosed, low voltage power circuit breaker switchgear assemblies rated 600V and below. (1.1)
NOTE Switchgear covered by this standard utilizes individually mounted drawout power circuit breakers as the primary switching and protective devices. (1.2)
NOTE For applications using molded case or insulated case breakers in a non-drawout configuration, see Low Voltage Switchboards. (1.3)
NOTE For medium voltage switchgear rated above 600V, see Medium Voltage Switchgear. (1.4)
NOTE Grounding and bonding per Grounding And Bonding. (1.5)
1.6 Equipment shall comply with UL 1558 and IEEE C37.20.1 and shall be listed and labeled by a Nationally Recognized Testing Laboratory (NRTL).

2 Referenced Standards

2.1 Equipment and installation shall comply with the latest edition of the following.
Standard Title
UL 1558 Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear
IEEE C37.20.1 Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear
IEEE C37.13 Low-Voltage AC Power Circuit Breakers Used in Enclosures
IEEE C37.20.7 Arc-Resistance Testing of Metal-Enclosed Switchgear
IEEE C37.51 Conformance Testing of Metal-Enclosed LV AC Power Circuit Breaker Switchgear
IEEE C37.90 Relays and Relay Systems Associated with Electric Power Apparatus
IEEE C57.13 Requirements for Instrument Transformers
IEEE 1584 Guide for Performing Arc-Flash Hazard Calculations
NFPA 70 National Electrical Code
NEMA ICS 6 Industrial Control and Systems: Enclosures
NETA ATS Acceptance Testing Specifications for Electrical Power Equipment and Systems
ASCE 7 Minimum Design Loads and Associated Criteria for Buildings
ASHRAE 90.1 Energy Standard for Buildings (submetering requirements)
ANSI/NEMA SG 3 Low-Voltage Power Circuit Breakers
2.2 Equipment and installation shall comply with the latest edition of the standards listed above.
2.3 Where conflicts exist between referenced standards, the more stringent requirement shall govern unless otherwise directed by the Engineer of Record.

3 Submittals

3.1 Action Submittals

3.1.1 Contractor shall submit the following for review prior to fabrication:
  • Shop drawings showing front, side, and rear elevations with overall dimensions
  • Single line diagram indicating breaker frame sizes, trip ratings, and bus configuration
  • Bill of materials listing all major components
  • Breaker time-current coordination curves for all protective devices
  • Control schematic and wiring diagrams
  • Seismic certification documentation, where required
Submittal Documentationcheckbox
Shop drawings (front, side, rear elevations)
Single line diagram
Bill of materials
Time-current coordination curves
Control schematics and wiring diagrams
Seismic certification (IBC/ASCE 7)
Arc flash calculation input data
Catalog cut sheets for all protective devices
3.1.2 Contractor shall submit the action submittals listed above for review prior to fabrication.

3.2 Closeout Submittals

3.2.1 Contractor shall provide at substantial completion:
  • Operation and maintenance manuals, bound with table of contents
  • As-built shop drawings reflecting field modifications
  • Factory and field test reports
  • Warranty documentation
  • Spare parts inventory with reorder information
Closeout Submittalscheckbox
Operation and maintenance manuals, bound with table of contents
As-built shop drawings reflecting field modifications
Factory and field test reports
Warranty documentation
Spare parts inventory with reorder information
3.2.2 Contractor shall provide the closeout submittals listed above at substantial completion.

4 Quality Assurance

4.1 Manufacturer Qualifications

4.1.1 Switchgear shall be manufactured by a single company responsible for the assembly, bus, and all integral protective devices.
4.1.2 The manufacturer shall have a minimum of five years documented experience producing UL 1558 listed switchgear.
4.1.3 The manufacturer shall maintain an ISO 9001 certified quality management system.
4.1.4 The manufacturer shall maintain a 24/7 service organization with factory-trained field representatives available within 24 hours of notification.

4.2 Source Limitations

4.2.1 All switchgear sections, bus, circuit breakers, protective relays, and metering equipment shall be produced or furnished by the switchgear manufacturer as an integrated assembly.
4.2.2 Third-party components assembled by others are not acceptable.

4.3 Testing Personnel Qualifications

4.3.1 Acceptance testing shall be performed by a firm regularly engaged in testing electrical power equipment, employing technicians certified by NETA or equivalent.
4.3.2 Testing personnel shall have a minimum of three years experience testing low voltage switchgear assemblies.

5 Environmental and Service Conditions

5.1 Switchgear shall be suitable for continuous operation under the following ambient conditions.
NOTE Where site conditions exceed these parameters, notify the manufacturer and derate equipment accordingly. (5.2)
Ambient Temperature (Maximum)select
40°C (standard rating)
50°C (tropical rating)
55°C (desert/rooftop rating)
Installation Altitudeselect
Below 6,600 ft (2,000 m) - No derating
6,600 - 9,900 ft (2,000 - 3,000 m) - Derating required
Above 9,900 ft (3,000 m) - Consult manufacturer
Corrosion Severityselect
C2 - Low (indoor, climate-controlled)
C3 - Medium (indoor, unconditioned)
C4 - High (coastal, chemical exposure)
C5 - Very High (industrial, marine)
NOTE See Electrical Rooms for room environmental classification requirements. (5.3)
5.4 Switchgear shall be suitable for continuous operation under the specified ambient conditions.
5.5 Where site conditions exceed the specified parameters, the Contractor shall notify the manufacturer and derate equipment accordingly.
5.6 Equipment rated for standard conditions (40°C, below 6,600 ft) shall be derated per IEEE C37.20.1 when installed outside these parameters.
5.7 The Engineer shall document derating calculations on the contract drawings.
5.8 For installations classified C4 or C5, bus bars shall be copper (tin or silver-plated).
5.9 For installations classified C4 or C5, enclosure paint systems shall provide enhanced corrosion protection per IEEE C57.12.29.

5.10 Seismic Requirements

Seismic Certificationselect
Not required
IBC/ASCE 7 - Importance Factor 1.0
IBC/ASCE 7 - Importance Factor 1.5 (essential facility)
OSHPD pre-approval required (California healthcare)
5.10.1 Where required by the applicable building code, switchgear shall be seismically certified by shake-table testing per ICC ES AC156 or by analysis per ASCE 7.
5.10.2 Seismic certification shall be by an independent third-party testing laboratory.
5.10.3 Certification shall cover the complete assembly including all circuit breakers, bus, and ancillary components as installed.
5.10.4 Certification of individual components in isolation is not acceptable.

6 Electrical Requirements

6.1 System Ratings

Service Entrance Equipmentradio
Yes - Main Service Entrance
No - Downstream Distribution
System Voltageselect
120/208V 3-Phase 4-Wire
277/480V 3-Phase 4-Wire
480V 3-Phase 3-Wire
System Frequencyradio
60 Hz
50 Hz
6.1.1 Where switchgear serves as main service entrance equipment, it shall comply with NFPA 70 Article 230 including provisions for metering, service disconnect, and available fault current labeling.
6.1.2 The Contractor shall coordinate metering requirements with the serving utility prior to submittal.

6.2 Bus Rating

6.2.1 Main bus continuous current rating shall be as indicated in the datasheet.
Main Bus Continuous Currentrange
A
8005000
8001200160020002500300040005000
Default: 1600 A
Per drawings
6.2.2 Short-circuit current rating shall equal or exceed the available fault current at the switchgear terminals.
Short-Circuit Current Ratingselect
42 kAIC
65 kAIC
85 kAIC
100 kAIC
200 kAIC
6.2.3 Bus short-time withstand rating shall be coordinated with the downstream protective device settings required to maintain selective coordination.
Short-Time Withstand Ratingselect
30-cycle (0.5 seconds)
15-cycle (0.25 seconds)
6.2.4 Bus shall be braced for the available short-circuit current at the point of installation as determined by a short-circuit analysis per IEEE 551.
6.2.5 The Contractor shall verify available fault current with the utility provider and perform a short-circuit study per Short Circuit Study prior to equipment procurement.

6.3 Neutral and Ground Bus

Neutral Bus Ratingselect
Full rated (100% of main bus)
Reduced (50% of main bus)
Oversized (200% of main bus)
Not applicable (3-wire system)
Ground Busradio
Included - Full length of assembly
Not required
6.3.1 Oversized neutral bus is required where nonlinear loads exceed 30% of the total connected load to accommodate triplen harmonic currents.
6.3.2 The Engineer shall evaluate harmonic loading per IEEE 519 when selecting neutral bus sizing.
6.3.3 Ground bus shall be bare copper, minimum 1/4 in. x 2 in. cross-section, extending the full length of the switchgear assembly.
6.3.4 Ground bus shall be accessible without removing any covers or barriers required for safe operation.

7 Physical Construction

7.1 Enclosure

Enclosure Ratingselect
NEMA 1 - Indoor General Purpose
NEMA 3R - Outdoor Rainproof
NEMA 12 - Industrial (dust-tight)
Front Accessibilityradio
Front accessible only
Front and rear accessible
7.1.1 Switchgear overall dimensions and arrangement shall be as indicated on the contract documents.
7.1.2 Enclosure shall be fabricated from galvanized steel with a minimum thickness of 12 gauge (2.66 mm) for structural members and 14 gauge (1.90 mm) for covers and doors.
7.1.3 All joints shall be continuously welded or bolted with gaskets as required for the specified NEMA rating.
7.1.4 For outdoor installations (NEMA 3R), enclosure shall include sun shields, rain hoods over ventilation openings, and condensation heaters in each section.
7.1.5 For outdoor installations (NEMA 3R), heater sizing shall be a minimum of 250W per vertical section.
7.1.6 For outdoor installations (NEMA 3R), heaters shall be thermostat controlled and wired to remain energized whenever the switchgear is de-energized.
7.1.7 Rear-accessible configurations require minimum 36 in. working clearance at rear per NFPA 70 Article 110.26.
7.1.8 Rear compartments shall have individual hinged doors with padlockable latches.

7.2 Bus Bars

Bus Bar Materialradio
Copper
Copper (tin-plated)
Copper (silver-plated)
Bus Extension Provisionsradio
No future extension
Provision for future extension at one end
Provision for future extension at both ends
7.2.1 Bus bar joints shall be bolted with Belleville washers to maintain contact pressure under thermal cycling.
7.2.2 All joint contact surfaces shall be silver-plated.
7.2.3 Bus connections shall be designed to be accessible for re-torquing during maintenance without de-energizing adjacent sections.
7.2.4 Phase bus shall be fully insulated with flame-retardant material rated for the operating temperature of the bus.
7.2.5 Bus insulation shall be continuous through barriers and bus transitions between sections.

7.3 Barriers and Compartmentalization

7.3.1 Switchgear shall provide metal barriers between all functional units and between the bus compartment and cable compartment.
7.3.2 Barriers shall prevent propagation of an arc fault from one compartment to adjacent compartments.
7.3.3 Individual circuit breaker compartments shall allow insertion, withdrawal, and testing of any breaker without exposing personnel to energized components in adjacent compartments.
7.3.4 Interlocks shall prevent opening compartment doors while the breaker is in the connected position.

7.4 Arc Resistance

Arc-Resistant Constructionselect
Not required
Type 1 - Front only (accessible from front)
Type 2 - Front and rear
Type 2B - Front, rear, and sides
Type 2C - Front, rear, sides, and between units
NOTE See Arc Flash Study for arc flash study requirements and labeling. (7.4.1)
7.4.2 Where arc-resistant construction is specified, switchgear shall be tested per IEEE C37.20.7 at the specified short-circuit current rating and duration.
7.4.3 Arc-resistant design shall redirect arc gases through plenums or ducts to areas where personnel are not present.
7.4.4 Pressure relief flaps and reinforced enclosure construction shall contain the arc event.
NOTE Arc-resistant construction does not eliminate the need for arc flash hazard analysis per IEEE 1584. (7.4.5)

7.5 Infrared Scanning Provisions

7.5.1 Enclosure shall include removable infrared inspection windows or cover plates at each bus joint, main breaker connections, and feeder breaker connections.
7.5.2 Windows shall allow thermographic inspection of energized connections without removing covers or de-energizing equipment.

8 Circuit Breakers

8.1 Main Circuit Breaker

Main Breaker Configurationselect
Power circuit breaker (drawout)
Main lugs only (no main breaker)
Main Breaker Trip Unitselect
Electronic trip - LSI (Long-time, Short-time, Instantaneous)
Electronic trip - LSIG (Long-time, Short-time, Instantaneous, Ground Fault)
8.1.1 Main breaker frame size and trip rating shall be as indicated on the one-line diagram.
8.1.2 Circuit breakers shall comply with IEEE C37.13 and shall be drawout, stored-energy type with manual charging and electrical close/trip capability.
8.1.3 Each breaker shall have three distinct positions: connected, test, and disconnected.
8.1.4 It shall not be possible to move a breaker between positions with the door closed unless motor operators are provided.
8.1.6 Ground fault protection is required by NFPA 70 Article 230.95 for solidly grounded wye services of more than 150V to ground and 1000A or more.
NOTE Even where not code-required, ground fault protection significantly reduces equipment damage from arcing faults. (8.1.7)

8.2 Arc Flash Mitigation

NOTE NFPA 70 Article 240.87 requires that circuit breakers rated 1200A or more have one of the following arc energy reduction methods. (8.2.1)
NOTE Specify the method appropriate for the project's operating requirements. (8.2.2)
Arc Energy Reduction Method (1200A+ Breakers)select
Zone-selective interlocking (ZSI)
Energy reducing maintenance switch (ERMS)
Energy reducing active arc flash mitigation system
Approved equivalent method
8.2.3 Circuit breakers rated 1200A or more shall have one of the arc energy reduction methods listed above per NFPA 70 Article 240.87.
NOTE Zone-selective interlocking allows upstream breakers to delay tripping only when a downstream breaker detects the fault, reducing arc flash energy at the upstream equipment while maintaining coordination, and does not require any mode switching for maintenance activities. (8.2.4)

8.3 Feeder Circuit Breakers

NOTE Feeder breaker sizes, quantities, and trip ratings are as indicated on the one-line diagram and breaker schedules. (8.3.1)
Feeder Breaker Typeselect
Power circuit breaker (drawout)
Insulated case circuit breaker (drawout)
Feeder Breaker Trip Unitsselect
Electronic trip - LSI
Electronic trip - LSIG
Per drawings — breaker schedule
Breaker Accessories (All Breakers)checkbox
Auxiliary contacts (1a + 1b minimum)
Shunt trip
Undervoltage release
Mechanical interlock (paired breakers)
Kirk key interlock
Motor operator with remote close/trip
Breaker position indication (drawout connected/test/disconnected)
8.3.2 Auxiliary contacts shall be provided on every breaker regardless of other accessory selections.
8.3.3 Auxiliary contacts shall indicate breaker open/close status and shall be wired to terminal blocks accessible without removing the breaker from its compartment.

8.4 Breaker Drawout Mechanism

8.4.1 All breakers shall be fully drawout and interchangeable within a given frame size.
8.4.2 A manual racking mechanism shall allow movement between connected, test, and disconnected positions.
8.4.3 The racking mechanism shall include a mechanical position indicator visible from the front of the switchgear and a means to padlock the breaker in any of the three positions.
8.4.4 Self-aligning primary disconnects shall engage automatically when the breaker is racked to the connected position.
8.4.5 Secondary disconnects for control wiring shall engage at the test position.
8.4.6 It shall be possible to operate the breaker electrically in the test position for trip testing without energizing the primary circuit.

9 Protective Relaying

Protective Relay Functionscheckbox
Overcurrent (50/51)
Ground fault (50G/51G)
Bus differential (87B)
Under/overvoltage (27/59)
Under/overfrequency (81)
Breaker failure (50BF)
Reverse power (32)
NOTE Relay settings are as indicated on the relay setting schedule. (9.1)
9.2 Protective relays shall comply with IEEE C37.90 and shall be microprocessor-based with digital displays, self-diagnostics, and event recording.
9.3 Relays shall be tested per IEEE C37.90.1 for surge withstand capability.
9.4 Protection coordination study shall be performed per Protective Coordination Study.

10 Metering and Instrumentation

10.1 Instrument Transformers

10.1.1 Current transformers shall comply with IEEE C57.13.
10.1.2 Accuracy class shall be appropriate for the connected metering:
  • Revenue metering: Class 0.3 accuracy
  • Protective relaying: Class C200 or higher
  • General monitoring: Class 0.6 accuracy
10.1.3 Current transformers for metering and relaying shall be provided on separate cores.
10.1.4 CTs shall not be shared between metering and protection functions.

10.2 Power Monitoring

Metering Typeselect
No metering
Digital multifunction meter (main only)
Digital multifunction meter (main and feeders)
Revenue-grade metering per utility requirements
Meter Functionscheckbox
Voltage (L-L, L-N all phases)
Current (per phase and neutral)
Power factor (per phase and total)
kW / kVA / kVAR (demand and instantaneous)
kWh / kVARh energy accumulation
Harmonics (THD per phase, individual to 31st)
Min/max recording with time stamp
Waveform capture
Metering Communication Protocolselect
No communications
Modbus RTU (RS-485)
Modbus TCP/IP (Ethernet)
BACnet IP
DNP3
10.2.1 Where building energy code requires submetering (ASHRAE 90.1 Section 8.4.3 or local amendments), meter data shall be accessible via the selected communication protocol for integration with the building management system.
10.2.2 The Contractor shall coordinate communication wiring and protocols with Building Automation System.

11 Finish and Identification

Finish Colortext
ANSI 61 gray
11.1 Enclosure shall receive a minimum two-coat paint system: corrosion-resistant primer and manufacturer's standard polyester powder coat finish.
11.2 Minimum total dry film thickness shall be 3 mils (75 microns).
11.3 For outdoor installations or environments classified C3 or higher, an enhanced paint system with a minimum of 5 mils dry film thickness shall be applied.
11.4 All internal structural members shall receive the same corrosion treatment as exterior surfaces.

11.5 Labeling

11.5.1 Manufacturer shall provide engraved phenolic nameplates for the switchgear assembly and each individual device.
11.5.2 Nameplates shall identify:
  • Switchgear designation and one-line reference
  • Bus ratings (voltage, continuous current, short-circuit)
  • Individual breaker designation, frame size, and trip rating
  • Current transformer ratios and accuracy class
  • Arc flash warning labels per NFPA 70E and IEEE 1584
Nameplate Materialradio
Laminated phenolic (indoor)
Stainless steel (outdoor or corrosive)
Aluminum (anodized)
11.5.3 Mimic bus diagram shall be provided on the front of the switchgear showing the bus configuration, breaker positions, and instrument transformer locations.
11.5.4 Equipment labeling shall follow Equipment Labeling conventions.

12 Testing

12.1 Factory Tests

12.1.1 The manufacturer shall perform the following production tests on the completed switchgear assembly per IEEE C37.51:
  • 60 Hz dielectric withstand test on primary bus
  • Insulation resistance measurement on each phase and neutral bus
  • Mechanical operation of each circuit breaker (minimum 5 open/close cycles)
  • Electrical operation of each circuit breaker (trip and close)
  • Ground fault sensing system functional test
  • Control wiring continuity verification
  • Current transformer ratio and polarity test
  • Protective relay functional test (verify trip at set values)
  • Visual and dimensional inspection
Factory Acceptance Testradio
Witnessed by Owner's representative
Unwitnessed with certified test report
Not required beyond standard production tests
12.1.2 The manufacturer shall perform the production tests listed above on the completed switchgear assembly per IEEE C37.51.
12.1.3 Where witnessed factory testing is specified, the manufacturer shall provide a minimum of two weeks advance notice of test readiness.
12.1.4 Where witnessed factory testing is specified, test procedures shall be submitted for review prior to testing.

12.2 Field Acceptance Tests

12.2.1 Contractor shall engage a qualified independent testing firm to perform acceptance testing per NETA ATS.
12.2.2 Field acceptance tests shall include as a minimum:
  • Visual and mechanical inspection of all sections
  • Insulation resistance testing (phase-to-phase and phase-to-ground)
  • Contact resistance measurement on all bolted bus connections
  • Circuit breaker operational testing (mechanical and electrical)
  • Protective relay calibration verification
  • Primary current injection testing of all trip functions (long-time, short-time, instantaneous, ground fault pickup and time delay)
  • Current transformer ratio and polarity verification
  • Metering accuracy verification
  • Ground impedance measurement per IEEE 81
  • Functional testing of all control circuits, interlocks, and alarms
Field Testing Requirementsradio
NETA acceptance testing and manufacturer startup
NETA acceptance testing only
Manufacturer startup only
Infrared Thermographic Inspectionradio
Initial scan within 90 days of energization, follow-up at 11 months
Initial scan within 90 days of energization only
Not required
12.2.3 Acceptance testing shall occur after installation is complete and before the equipment is energized.
12.2.4 Field acceptance tests shall include as a minimum the inspections and tests listed above.
12.2.5 Infrared scanning shall be performed under normal operating load conditions (minimum 40% of rated load).
12.2.6 All connections exceeding 10°C rise above ambient shall be reported and corrected.
NOTE A follow-up scan at 11 months captures connections that may loosen during the initial thermal cycling period. (12.2.7)

13 Installation

13.1 Concrete Housekeeping Pad

NOTE See Concrete Pads for construction requirements. (13.1.1)
13.1.2 Switchgear shall be mounted on a reinforced concrete housekeeping pad extending a minimum of 3 in. beyond the base of the equipment on all sides.
13.1.3 Pad shall be a minimum of 4 in. above finished floor for indoor installations and 6 in. above finished grade for outdoor installations.
13.1.4 The Contractor shall coordinate pad dimensions, conduit penetrations, and anchor bolt locations with equipment shop drawings prior to concrete placement.

13.2 Equipment Setting

NOTE Before energizing, verify the following: (13.2.1)
  • All shipping restraints and temporary grounds removed
  • Bus joint torque verified per manufacturer's specifications using calibrated torque wrench
  • All circuit breakers rack and operate freely in all three positions
  • Conduit terminations sealed and cable connections torqued
  • Space heaters energized (outdoor or unconditioned installations)
  • Working clearances per NFPA 70 Article 110.26 are maintained
13.2.2 Contractor shall comply with manufacturer's installation instructions and applicable rigging requirements.
13.2.3 The Contractor shall remove all temporary shipping braces, blocking, and desiccants prior to final assembly.
13.2.4 The Contractor shall verify section alignment and bolt all sections together per manufacturer's torque specifications.
13.2.5 After assembly and before energizing, the Contractor shall verify the conditions listed above.

13.3 Working Clearance

13.3.1 Minimum working space shall be maintained per NFPA 70 Article 110.26 based on the nominal voltage and accessibility configuration:
Voltage Condition 1 (exposed on one side) Condition 2 (exposed on both sides)
0-150V 36 in. 36 in.
151-600V 36 in. 48 in.
13.3.2 Minimum working space shall be maintained per NFPA 70 Article 110.26 based on the nominal voltage and accessibility configuration shown in the table above.
13.3.3 Working space shall not be used for storage.
13.3.4 Dedicated electrical space above and below the equipment shall be maintained per NFPA 70 Article 110.26(E).

14 Delivery, Storage, and Handling

14.1 Switchgear shall be shipped in the largest factory-assembled sections that can be transported to and within the installation site.
14.2 The Contractor shall verify all pathway dimensions (doors, hallways, elevator shafts) between the delivery point and the final installation location prior to ordering.
14.3 Equipment shall be stored indoors in a clean, dry location.
14.4 Where indoor storage is not available, the manufacturer shall provide weatherproof packaging.
14.5 Condensation heaters shall be connected and energized during storage if the equipment will be stored for more than 30 days or if the storage environment is not climate-controlled.

15 Warranty

Warranty Periodselect
1 year from substantial completion
2 years from substantial completion
3 years from substantial completion
5 years from substantial completion
Extended Warranty Coveragecheckbox
Parts only
Parts and labor
Emergency response (24/7 with 4-hour commitment)
Scheduled preventive maintenance (annual)
15.1 Warranty shall cover defects in materials and workmanship under normal use and service conditions.
15.2 The manufacturer shall maintain a service organization capable of providing emergency replacement parts and field service within 24 hours during the warranty period.

16 Spare Parts

Spare Breakersradio
None
One spare of each frame size
10% of each frame size (minimum one)
16.1 Spare breakers shall be of the same type, rating, and configuration as the installed breakers and shall be fully interchangeable.
16.2 Spare breakers shall be stored in a manufacturer-provided storage cabinet or on a breaker storage truck, located in the electrical room.
16.3 Manufacturer shall provide the following additional spare parts: one set of replacement fuses for each fuse type and rating installed, one set of replacement indicating lights for each type installed, one set of racking handle, breaker test plugs, and portable closing tools, and one complete set of keys for all locks.

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Low Voltage Switchgear." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/low-voltage-switchgear — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.