Hydronic Piping

Revision 6 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 18, 2026 +1 −1

Adoption-parse fixes (YAML quoting, valid types, range defaults/min-max)
Showing changes from Rev 5 to Rev 6 in Hydronic Piping.
---
title: Hydronic Piping
286 unchanged lines
label: Glycol Concentration (percent by volume, where glycol is used)
type: range
unit: % (by volume)
+unit: '% (by volume)'
options:
min: 20
1296 unchanged lines
### Every CHW fitting, flange, and valve shall be insulated with fitting covers or mitered sections sealed with manufacturer's vapor-retarder adhesive before final inspection, because chilled water insulation vapor retarder breaches at supports, valve bodies, and fitting insulation seams cause condensation drips on ceilings and floors.