Metal Lockers

Revision 2 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 4, 2026 +707 −615

Granular element model: citable clauses + {note} rationale
Showing changes from Rev 1 to Rev 2 in Metal Lockers.
---
title: Metal Lockers
category: Architectural / Specialties
toc_depth: 3
description: >
When to use: Factory-fabricated metal (steel) lockers for athletic and locker-room, employee and industrial, and school corridor applications, furnished as knocked-down (KD) standard-duty, heavy-duty, or fully welded assemblies. Covers steel sheet and component gauges, powder-coat finish over phosphatized steel, locker types and tiers (single, double, triple, box, Z-tier), ventilation (louvers, perforations, diamond), latching and locking (recessed handle, padlock hasp, built-in combination or key, electronic), trim and accessories (sloped tops, closed and Z bases, end and filler panels, number plates, benches), accessibility under the ADA Standards and ICC A117.1, and anchorage including seismic restraint.
Not intended for: Plastic, solid-polymer (HDPE), or phenolic lockers (see [[sync/plastic-lockers]]); wood and high-pressure-laminate casework and cubbies (see [[sync/wood-and-laminate-casework]]); wire-mesh storage partitions and tool cribs; bulk shelving and pallet rack; mailbox and parcel-delivery lockers; refrigerated or electronically managed asset-management lockers as a packaged building system; toilet compartments (see [[sync/toilet-compartments]]).
---
# Scope
This standard covers the furnishing and installation of factory-fabricated metal lockers and their trim, accessories, and anchorage. A metal locker is an assembly of formed steel sheet — a body (back, sides, top, and bottom), a door, and a door frame — joined either by mechanical fasteners (knocked-down, or KD, construction) or by welding, and finished with a baked powder-coat enamel. The scope includes the selection of construction grade to match the service duty, the steel gauges of each component, the ventilation type appropriate to the contents stored, the latching and locking method, the trim and accessories that finish a locker installation, the dimensional and operational requirements for accessible lockers, and the anchorage and seismic restraint of the installed run.
The locker layout — the number of lockers, the tier arrangement, the individual opening sizes, the bank lengths, and the location of accessible lockers — shall be [[drawing: as indicated on the locker plans and elevations]]. This standard establishes the material, construction, finish, hardware, accessibility, and installation requirements for the lockers shown on those drawings.
The single most consequential decision in this standard is matching the construction grade to the service duty. A standard-duty KD locker that performs adequately in a supervised employee coat room will be pried, dented, and racked out of service within a season in an unsupervised school corridor or a high-turnover athletic locker room. The narrative below ties each construction grade and gauge to the occupancy and abuse level in which it is the appropriate choice, so that the specifier selects the locker from the actual service environment rather than from first cost alone. Plastic, polymer, and phenolic lockers are an alternative to steel where moisture, corrosion, or hose-down cleaning rules steel out; those materials are addressed in [[sync/plastic-lockers]] and are noted here only as a selection branch.
Coordinate this work with [[sync/gypsum-board-assemblies]] and [[sync/unit-masonry]] for in-wall blocking and wall anchorage backing; with the flooring and base trades for the floor condition beneath closed and Z bases; with [[sync/toilet-compartments]] and [[sync/toilet-accessories]] where lockers adjoin a locker-room wet area; and with the electrical trade where electronic locks require power or network connection.
# Referenced Standards
Materials, fabrication, finish, and installation shall comply with the latest adopted edition of the referenced standards. Where the contract documents or the adopted building code impose more stringent requirements than a referenced standard, the more stringent requirement shall govern. The Contractor shall resolve conflicts in writing with the Architect before fabrication begins.
| Standard | Title |
|----------|-------|
| ASTM A1008/A1008M | Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy |
| ASTM A1011/A1011M | Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy |
| ASTM A653/A653M | Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process |
| ASTM D3359 | Standard Test Methods for Rating Adhesion by Tape Test |
| ASTM B117 | Standard Practice for Operating Salt Spray (Fog) Apparatus |
| ASTM D2794 | Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact) |
| ASTM D523 | Standard Test Method for Specular Gloss |
| ANSI/BHMA A156.5 | Cylinders and Input Devices for Locks (key and electronic locking, where applicable) |
| ICC A117.1-2017 | Accessible and Usable Buildings and Facilities |
| 2010 ADA Standards for Accessible Design | Americans with Disabilities Act Accessibility Standards (Sections 225 and 811, Storage) |
| ASCE/SEI 7 | Minimum Design Loads and Associated Criteria for Buildings and Other Structures (nonstructural component anchorage) |
| IBC Chapter 8 | International Building Code — Interior Finishes |
# Submittals
## Action Submittals
The following submittals shall be submitted for review and returned before fabrication begins.
**Product Data:** Manufacturer's product data for each locker type, construction grade, ventilation type, and lock, including the steel gauge of the body, door, and frame; the finish system; the available colors; and the lock function and keying or programming.
**Shop Drawings:** Plans and elevations of each locker location drawn to scale, showing every locker bank; tier arrangement and individual opening sizes; bank lengths and overall dimensions; the location and tier of each accessible locker; trim, sloped-top, base, end-panel, and filler-panel locations; number-plate sequence; bench locations; and the anchorage and seismic-restraint details with connection to the building structure. Shop drawings shall identify which lockers are accessible and shall show the reach-range compliance of the accessible lockers' operable parts.
**Samples:** Color and finish samples (manufacturer's full color line) and, where requested, a sample lock and recessed handle of each specified type.
**Finish Test Reports:** Reports demonstrating the powder-coat finish complies with the adhesion (ASTM D3359), corrosion-resistance (ASTM B117), impact (ASTM D2794), and gloss (ASTM D523) requirements specified under Materials below.
**Seismic Anchorage Calculations:** Where the project is in a seismic design category that requires anchorage of nonstructural components, signed and sealed anchorage calculations and details prepared in accordance with ASCE/SEI 7 for the locker height, weight, and base condition.
```datasheet
label: Action Submittals Required
type: checkbox
options:
- "Product data for locker type, construction grade, ventilation, and lock"
- "Dimensioned shop drawings (plans and elevations) with tier and opening sizes"
- "Color and finish samples (full color line)"
- "Sample lock and recessed handle of each type"
- "Finish test reports (D3359 adhesion, B117 salt spray, D2794 impact, D523 gloss)"
- "Accessible locker reach-range and operable-parts verification"
- "Seismic anchorage calculations and details (where required by SDC)"
default: "Dimensioned shop drawings (plans and elevations) with tier and opening sizes"
```
## Closeout Submittals
At substantial completion the Contractor shall provide the manufacturer's care and maintenance instructions, the manufacturer's written warranty, a master keying schedule or combination/programming record for the installed locks, and an inventory of attic-stock parts (number plates, locks, and touch-up paint) where specified. Lock control documentation shall be transmitted directly to the Owner's designated representative and shall not be left with the lockers.
```datasheet
label: Closeout Submittals Required
type: checkbox
options:
- "Care and maintenance instructions"
- "Manufacturer warranty documentation"
- "Master keying schedule / combination / programming record (to Owner)"
- "Attic-stock locks, number plates, and touch-up paint inventory"
default: "Care and maintenance instructions"
```
# Quality Assurance
## Manufacturer Qualifications
The manufacturer shall be a firm regularly engaged in the fabrication of metal lockers of the type, construction grade, and lock specified, with a minimum of five years of production experience and products in service in comparable applications. Lockers, trim, accessories, and locks within a single installation shall be the product of a single manufacturer to ensure dimensional fit and finish match.
## Single-Source Responsibility
```datasheet
label: Single-Source Responsibility
type: radio
options:
- "All lockers, trim, accessories, and locks from a single manufacturer"
- "Lockers and accessories furnished as a coordinated package by a single supplier"
default: "All lockers, trim, accessories, and locks from a single manufacturer"
```
Trim, fillers, sloped tops, and bases are fabricated to the manufacturer's locker module and frame profile; mixing trim from one manufacturer with lockers from another produces misaligned joints and exposed gaps. Locks are machined to the manufacturer's door and frame preparation. The locker body, door, frame, trim, and lock shall therefore be a matched system from one source.
## Field Measurements
The Contractor shall verify field dimensions at each locker location before fabrication. Bank lengths, recess depths, soffit heights, and the as-built location of walls and columns determine the number of lockers, the trim, and the filler panels required. Where field conditions differ from the contract drawings, the Contractor shall notify the Architect before fabrication so that openings, trim, and fillers can be adjusted.
# Materials
## Steel Sheet
Locker components shall be formed from prime, commercial-quality mild steel sheet, free of surface imperfections. Cold-rolled sheet shall conform to ASTM A1008/A1008M; where hot-rolled sheet is used for heavier structural members it shall conform to ASTM A1011/A1011M. Where lockers will be exposed to elevated humidity or intermittent moisture, zinc-coated (galvannealed) sheet conforming to ASTM A653/A653M shall be specified for the body and door so that the steel substrate resists corrosion at coating defects; in sustained-wet or hose-down environments, steel lockers shall not be used and a non-metallic locker per [[sync/plastic-lockers]] shall be selected instead.
```datasheet
label: Steel Substrate
type: radio
options:
- "Cold-rolled carbon steel sheet (ASTM A1008), standard dry interior"
- "Galvannealed steel sheet (ASTM A653), elevated humidity / intermittent moisture"
default: "Cold-rolled carbon steel sheet (ASTM A1008), standard dry interior"
```
## Component Gauges by Construction Grade
The steel gauge of each component is the physical measure of locker duty. Gauge is expressed as a sheet-metal gauge number, where a lower number is a thicker, heavier sheet. The body, door, and frame each carry a gauge appropriate to the construction grade; the door and the frame — the components that take direct abuse — are heavier than the body in every grade. The values below are the procurable standards across the major manufacturers for each grade.
### Standard-duty knocked-down construction
Standard-duty KD lockers ship as flat components fastened together in the field. They are the economical choice for supervised, low-abuse employee, office, and light-commercial applications. Standard-duty bodies are typically 24-gauge with 16-gauge door frames and 16-gauge doors. Standard-duty lockers shall not be specified for unsupervised school corridors, athletic rooms, or any high-abuse application.
### Heavy-duty knocked-down construction
Heavy-duty KD lockers use heavier body and door sheet and reinforced frames while retaining field-assembled KD construction. They are the appropriate selection for school corridors and general institutional use. Heavy-duty bodies are typically 16-gauge with 14- or 16-gauge door frames and 14- or 16-gauge doors.
### Welded construction
Welded (fully assembled) lockers arrive as rigid, factory-welded units with no field-fastened body seams to loosen, racking-resistant frames, and the highest abuse resistance. They are the appropriate selection for athletic and team locker rooms, public recreation, corrections, and any environment with heavy abuse or no supervision. Welded bodies are typically 16-gauge with 12- or 14-gauge frames and 14- or 16-gauge doors.
```datasheet
label: Construction Grade
type: select
options:
- "Standard-duty knocked-down (KD) — supervised, low-abuse employee/office"
- "Heavy-duty knocked-down (KD) — school corridor, general institutional"
- "Welded — athletic/team room, recreation, corrections, high-abuse"
default: "Heavy-duty knocked-down (KD) — school corridor, general institutional"
```
```datasheet
label: Locker Body Gauge
type: radio
options:
- "24 gauge (standard-duty)"
- "16 gauge (heavy-duty / welded)"
default: "16 gauge (heavy-duty / welded)"
```
```datasheet
label: Door Frame Gauge
type: radio
options:
- "16 gauge (standard / heavy-duty)"
- "14 gauge (heavy-duty)"
- "12 gauge (welded high-abuse)"
default: "16 gauge (standard / heavy-duty)"
```
```datasheet
label: Door Gauge
type: radio
options:
- "16 gauge (standard / heavy-duty)"
- "14 gauge (heavy-duty / welded)"
default: "16 gauge (standard / heavy-duty)"
```
#### Door frame vertical members shall form a continuous integral door strike the full height of the opening.
#### KD body seams shall be flanged to provide a double thickness of metal at joints and corners.
## Finish
Lockers shall be finished with a baked thermoset powder-coat enamel electrostatically applied over a cleaned, phosphatized steel substrate. The five-stage (or better) pretreatment — clean, rinse, iron- or zinc-phosphate conversion, rinse, seal — is essential: powder coat applied over unphosphatized steel loses adhesion and the finish fails at the first impact or scratch. The cured finish shall meet the performance requirements below.
#### Finish adhesion shall be not less than rating 4B when tested per ASTM D3359 (cross-cut tape test).
#### Finish corrosion resistance shall show no more than minimal undercutting at a scribe after 500 hours of salt-spray exposure per ASTM B117.
#### Finish impact resistance shall show no cracking or loss of adhesion at 80 in-lb direct impact per ASTM D2794.
```datasheet
label: Finish Gloss (ASTM D523, 60-degree)
type: select
options:
- "Low gloss / matte (hides scratches and fingerprints, athletic/corridor)"
- "Medium / satin gloss"
- "High gloss"
default: "Low gloss / matte (hides scratches and fingerprints, athletic/corridor)"
```
```datasheet
label: Salt-Spray Exposure (ASTM B117) Minimum
type: range
unit: h
options:
min: 250
max: 1000
setpoints: [250, 500, 750, 1000]
default: 500
```
```datasheet
label: Finish Color
type: select
drawing_ref: true
options:
- "Manufacturer's standard color (single, as selected)"
- "Two-tone (body one color, doors another)"
- "Custom color match (extended lead time)"
default: "Manufacturer's standard color (single, as selected)"
```
# Locker Types and Configuration
## Tier Arrangement
The tier arrangement is the number of separately locking openings stacked within one locker frame height. More tiers give more openings per floor area at the cost of opening height. Tier shall be selected for the contents and the user: full-height single tier for hanging garments and street clothes, and box or triple tier for compact personal-item storage and high user counts.
### Single tier (one-tier)
One full-height opening per frame, suited to hanging coats and street clothes. The standard for employee and corridor lockers where garments are stored.
### Double tier (two-tier)
Two openings stacked, each roughly half the frame height. A common school-corridor configuration, doubling locker count where full-height hanging space is not required.
### Triple tier (three-tier)
Three openings stacked. Used where user count is high and stored items are small (gym clothes, books, personal effects).
### Box tier (four-, five-, or six-tier)
Four or more compact openings per frame, for personal-item, valet, and day-use storage where many users share a small footprint.
### Z-tier
Two interlocking Z-shaped openings per width, each providing partial hanging height at roughly half the floor area of a single-tier locker — a space-efficient compromise that still allows short garments to hang.
```datasheet
label: Locker Tier
type: select
drawing_ref: true
options:
- "Single tier (one-tier) — full-height, hanging garments"
- "Double tier (two-tier)"
- "Triple tier (three-tier)"
- "Box tier (four/five/six-tier) — compact personal items"
- "Z-tier — interlocking, partial hanging height, space-efficient"
default: "Single tier (one-tier) — full-height, hanging garments"
```
## Opening Size
Individual opening width, depth, and frame height shall be [[drawing: as indicated on the locker elevations]]. The values below are the common procurable nominal sizes and serve as datasheet defaults where the drawings do not dictate otherwise.
```datasheet
label: Locker Opening Width (nominal)
type: range
unit: in
drawing_ref: true
options:
min: 9
max: 24
setpoints: [9, 12, 15, 18, 24]
default: 12
```
```datasheet
label: Locker Depth (nominal)
type: range
unit: in
drawing_ref: true
options:
min: 12
max: 24
setpoints: [12, 15, 18, 21, 24]
default: 15
```
```datasheet
label: Locker Frame Height (excluding base/legs)
type: range
unit: in
drawing_ref: true
options:
min: 60
max: 72
setpoints: [60, 66, 72]
default: 72
```
## Ventilation
Lockers that store damp athletic clothing, footwear, or wet-weather garments shall be ventilated so that moisture and odor are not trapped. The ventilation type shall be matched to the airflow needed: louvered doors for general athletic and gym use, full perforation or diamond perforation for maximum airflow in wet team rooms and pool environments. Non-ventilated solid doors are appropriate only for dry storage of non-perishable items.
```datasheet
label: Ventilation Type
type: select
options:
- "Solid (non-ventilated) — dry storage only"
- "Louvered door (general athletic/gym ventilation)"
- "Full-perforated door (high airflow, wet team rooms)"
- "Diamond-perforated door and sides (maximum airflow, pool/aquatic)"
default: "Louvered door (general athletic/gym ventilation)"
```
Louvers and perforations shall be formed in the door (and, for diamond ventilation, the sides) without sharp edges. In humid and aquatic environments, ventilation alone does not protect plain steel; specify galvannealed substrate per Materials, or select a non-metallic locker per [[sync/plastic-lockers]].
# Latching and Locking
The latching mechanism holds the door closed and engages the lock; the lock secures the contents. The two are selected together. Recessed handles and recessed latches reduce snag and vandalism in corridors and athletic rooms; surface lift handles are simpler and lower cost for supervised employee use. Multi-point latching distributes the holding force along the door height and resists prying in abuse-prone applications.
## Latch and Handle
```datasheet
label: Latch and Handle Type
type: select
options:
- "Recessed handle, single-point latch (low-abuse, recessed lock pocket)"
- "Recessed handle, three-point latch (corridor/athletic, anti-pry)"
- "Surface lift handle, single-point latch (supervised employee)"
- "Surface lift handle, multi-point latch"
default: "Recessed handle, three-point latch (corridor/athletic, anti-pry)"
```
Three-point (multi-point) latching engages the door at the top, center, and bottom of the frame and is the standard for unsupervised corridor and athletic lockers because it resists the pry-at-a-corner attack that defeats single-point latches. The recessed handle houses the lock in a protected pocket so the lock body cannot be struck or pried.
## Locking Method
The locking method shall be selected for the Owner's access-control needs, the user population, and the willingness to manage keys, combinations, or batteries. Built-in combination locks suit schools and shared institutional use; padlock hasps let users supply their own locks; key locks suit assigned employee lockers; electronic locks suit day-use and shared lockers where users set their own code per use.
```datasheet
label: Locking Method
type: select
options:
- "Recessed padlock hasp (user-supplied padlock)"
- "Built-in combination lock (single-combination, assigned)"
- "Built-in resettable/multi-user combination lock (shared/day-use)"
- "Built-in key lock (cam/cylinder, keyed, master-keyed)"
- "Electronic keypad/RFID lock (programmable, day-use or assigned)"
- "Provision for Owner-furnished lock (hasp/cutout only)"
default: "Built-in combination lock (single-combination, assigned)"
```
```datasheet
label: Built-In Lock Keying / Control
type: radio
options:
- "Keyed alike within control group, master-keyed (key locks)"
- "Combination set list provided to Owner (combination locks)"
- "Owner-programmed at commissioning (electronic locks)"
- "Not applicable (user-supplied padlock)"
default: "Combination set list provided to Owner (combination locks)"
```
#### Electronic locks shall be specified with a clearly defined power source (battery or hard-wired) and a documented mechanical or master override for lockout recovery.
Where electronic locks are hard-wired or networked, coordinate power and data rough-in with the electrical trade before fabrication. Where battery-powered, the closeout submittal shall state the battery type and the expected service interval.
# Accessories and Trim
Trim and accessories finish a locker installation, close gaps to walls and soffits, keep dust and debris off and out of the lockers, and identify openings. They are selected for the installation condition and the housekeeping environment.
## Sloped Tops
```datasheet
label: Sloped Tops
type: radio
options:
- "Continuous sloped tops (prevents storage/dust accumulation atop lockers)"
- "Flat tops (storage shelf above, low-dust environment)"
default: "Continuous sloped tops (prevents storage/dust accumulation atop lockers)"
```
Continuous sloped tops, typically 16-gauge with an approximately 18-degree pitch, shall be specified for corridor, athletic, and public installations to prevent the locker tops from becoming a dust shelf and an informal storage surface. Omitting sloped tops in a dusty or unsupervised environment is a common and avoidable maintenance failure. Sloped-top end closures and splice covers shall be furnished to finish exposed ends and joints.
## Base
```datasheet
label: Locker Base
type: select
drawing_ref: true
options:
- "Closed (front and end) base over legs (conceals legs, finished appearance)"
- "Z-base / channel base, 4 in (raises lockers, creates toe space)"
- "Z-base / channel base, 6 in"
- "Legs exposed (utility/back-of-house)"
- "No base — lockers set directly on finished floor"
default: "Closed (front and end) base over legs (conceals legs, finished appearance)"
```
A Z-base (channel base) raises the lockers off the floor and creates a recessed toe space, improving appearance and simplifying floor cleaning; closed bases conceal legs for a finished look in public areas. Coordinate the base condition with the finished flooring and base trades.
## End Panels, Filler Panels, and Recess Trim
```datasheet
label: Exposed-End Treatment
type: radio
options:
- "Finished end panels at all exposed locker ends"
- "No finished ends (ends concealed by walls)"
default: "Finished end panels at all exposed locker ends"
```
```datasheet
label: Filler Panels at Walls / Obstructions
type: radio
options:
- "Provide filler panels to close gaps to walls, columns, and obstructions"
- "Not required (lockers fit module exactly)"
default: "Provide filler panels to close gaps to walls, columns, and obstructions"
```
```datasheet
label: Recess Trim
type: radio
drawing_ref: true
options:
- "Provide recess trim where lockers are recessed into wall/soffit"
- "Not required (lockers not recessed)"
default: "Not required (lockers not recessed)"
```
Finished end panels shall close exposed locker ends; filler panels shall close the gaps between lockers and walls, columns, or obstructions; and recess trim shall bridge the gap to the wall and soffit where lockers are recessed. Gap and obstruction conditions are not always apparent until field measurement, so filler and trim quantities shall be confirmed against field dimensions before fabrication.
## Number Plates
```datasheet
label: Number Plates
type: radio
options:
- "Provide number plates, sequence per Owner schedule"
- "Provide number plates, sequential by bank"
- "Not required"
default: "Provide number plates, sequence per Owner schedule"
```
Number plates shall be riveted to each door at a consistent location. The numbering sequence shall be coordinated with the Owner's locker-assignment scheme; an arbitrary sequence forces the Owner to renumber after installation.
## Interior Equipment and Benches
```datasheet
label: Interior Equipment
type: checkbox
options:
- "Coat hooks / single-prong wall hooks"
- "Double-prong ceiling hooks"
- "Coat rod (single-tier garment lockers)"
- "Top shelf"
- "Footwear shelf / bottom shelf"
default: "Top shelf"
```
```datasheet
label: Locker-Room Benches
type: radio
drawing_ref: true
options:
- "Provide benches (hardwood top on pedestals), lengths per drawings"
- "Not required"
default: "Not required"
```
Where benches are provided, hardwood bench tops on metal pedestals are the standard; bench lengths and locations shall be [[drawing: as indicated]]. Where accessibility requires it, at least one bench complying with the accessible-bench provisions of the accessibility standard shall be provided in each locker room — see Accessibility below.
# Accessibility
## Coverage
Where lockers are provided, accessible lockers shall be provided in accordance with the adopted accessibility standard. The 2010 ADA Standards (Sections 225 and 811) and ICC A117.1 require that at least 5 percent of lockers of each type, but no fewer than one of each type, comply. "Each type" includes each functional class of locker (for example, full-height garment lockers and box lockers are different types and each requires its accessible share). The number, type, and location of accessible lockers shall be [[drawing: as indicated on the locker plans and accessibility compliance documents]]; the Architect is responsible for confirming the count and configuration from the accessibility compliance path.
```datasheet
label: Accessible Locker Quantity Basis
type: radio
drawing_ref: true
options:
- "5 percent of each type, minimum one of each type (per ADA 811 / A117.1)"
- "Greater quantity as indicated on the drawings"
default: "5 percent of each type, minimum one of each type (per ADA 811 / A117.1)"
```
## Reach Ranges and Operable Parts
The defining requirement for an accessible locker is that its usable storage and every operable part fall within the reach range. Accessible lockers are normally located in a single tier or in the lower tier of a multi-tier bank so that the opening and the lock are reachable from a seated position.
#### The usable storage in an accessible locker shall be within an unobstructed forward or side reach range of 15 in. minimum to 48 in. maximum above the finished floor.
#### Every operable part of an accessible locker — handle, lock, keypad, and latch — shall be within the 15 in. to 48 in. reach range and shall be operable with one hand without tight grasping, pinching, or twisting of the wrist, and with no more than 5 lbf of force.
```datasheet
label: Accessible Locker Operable-Parts Height (AFF)
type: range
unit: in AFF
options:
min: 15
max: 48
setpoints: [15, 36, 44, 48]
default: 44
```
```datasheet
label: Accessible Locker Lock Type
type: select
options:
- "Built-in combination lock with large, easy-grip dial/buttons"
- "Electronic keypad/RFID lock (no grasping or twisting)"
- "Recessed padlock hasp (only where padlock meets operable-parts criteria)"
default: "Electronic keypad/RFID lock (no grasping or twisting)"
```
A conventional small combination dial or a key cam lock that must be pinched and twisted does not meet the operable-parts criteria; accessible lockers shall use a lock operable with a closed fist or one easy motion. A clear floor space and an accessible route shall be provided at each accessible locker; verify this clearance against the locker plan.
## Accessible Benches
Where benches are required in a locker room, at least one bench shall comply with the accessible-bench provisions (seat height, depth, back support, and clear floor space) of the accessibility standard. The accessible bench and its clear floor space shall be coordinated with the locker layout so the clearance is not blocked by a locker bank.
# Fabrication
Lockers shall be fabricated to the dimensions and configuration shown on the approved shop drawings. Welded lockers shall be factory-welded into rigid units with welds ground smooth at exposed surfaces before finishing. KD lockers shall be fabricated with formed, flanged components that assemble into square, rigid banks with mechanical fasteners. Doors shall be formed with a continuous channel or box section at the lock edge and shall be hung to operate freely without binding, with the latch engaging the strike fully. Louvers, perforations, and ventilation openings shall be formed without sharp or burred edges. All components shall be cleaned, phosphatized, and powder-coated after forming and welding so that cut and formed edges are coated.
#### All exposed welds shall be ground smooth before finishing.
#### All sheared and formed edges shall be free of burrs and sharp edges.
# Installation
## Coordination and Blocking
Lockers shall be installed after the wall and floor finishes are complete and the building is enclosed and conditioned. The Contractor shall verify before installation that solid in-wall blocking has been provided where lockers, trim, or benches anchor to walls. Blocking is furnished and installed under the wall trades; the locker Contractor shall confirm its presence and location against the shop drawings and notify the Architect of any missing or mislocated blocking before proceeding. Anchoring lockers or benches to gypsum board without blocking is a primary cause of failure and shall not be permitted.
```datasheet
label: In-Wall Blocking Verified Before Installation
type: radio
options:
- "Yes — blocking verified at all wall anchorage points before installation"
- "Not applicable — no wall-anchored components"
default: "Yes — blocking verified at all wall anchorage points before installation"
```
## Anchorage
Lockers shall be set level and plumb, shimmed as required, and anchored to the building structure. Banks shall be bolted together into continuous runs and anchored to the floor and, where backs are accessible, to the wall. Anchorage shall use fasteners appropriate to the substrate — expansion or wedge anchors into concrete, anchors into masonry, and through-bolts or lag screws into in-wall blocking within stud walls. Tall lockers shall be anchored at the top to the wall or, where freestanding, braced back-to-back, so they cannot tip.
```datasheet
label: Anchorage Condition
type: select
drawing_ref: true
options:
- "Floor-anchored and wall-anchored (back to wall)"
- "Floor-anchored and top-anchored to wall (tall single-row banks)"
- "Back-to-back freestanding, floor-anchored and braced"
- "Recessed into wall opening, anchored to surrounding structure"
default: "Floor-anchored and wall-anchored (back to wall)"
```
## Seismic Restraint
```datasheet
label: Seismic Anchorage Required
type: radio
drawing_ref: true
options:
- "Yes — seismic anchorage per ASCE/SEI 7 and sealed calculations"
- "No — not required by the seismic design category"
default: "No — not required by the seismic design category"
```
Where the seismic design category requires anchorage of nonstructural components, lockers (particularly banks 60 in. or taller) shall be anchored vertically and laterally to resist the seismic forces determined per ASCE/SEI 7, in accordance with the sealed anchorage calculations and details submitted under Submittals. Seismic restraint is determined by the project's seismic design category and the locker height and weight; the Architect and Structural Engineer shall confirm the requirement. Anchorage relying solely on sheet-metal screws into unbraced studs does not satisfy a seismic anchorage requirement.
## Adjustment and Cleaning
After installation the Contractor shall adjust every door so it operates freely, latches fully, and the lock engages; verify that accessible lockers' operable parts are within the reach range and operable as specified; install all trim, number plates, and accessories; and clean all surfaces. Protective coverings shall remain in place until adjustment and cleaning are complete. Doors that bind, latches that do not engage, and finish damage shall be corrected; deep scratches and corroded components shall be replaced rather than field-repaired, because field touch-up does not reproduce the baked finish.
# Warranty
```datasheet
label: Locker Warranty Period
type: select
options:
- "1 year from substantial completion — standard"
- "5 years from substantial completion"
- "Lifetime limited warranty against defects (welded heavy-duty programs)"
default: "5 years from substantial completion"
```
The manufacturer shall warrant the lockers against defects in materials and workmanship — including finish adhesion, door and latch operation, and structural integrity of the body and frame — for the specified period. Welded heavy-duty locker programs commonly carry substantially longer warranties than standard-duty KD lockers; where the project uses welded construction, the longer warranty should be obtained and documented. The warranty shall not cover abuse beyond the rated service condition, improper cleaning chemicals, or modifications made without the manufacturer's authorization.
```datasheet
label: Lock Warranty
type: select
options:
- "Manufacturer's standard lock warranty (mechanical locks)"
- "Extended electronic-lock warranty including controller and keypad"
default: "Manufacturer's standard lock warranty (mechanical locks)"
```
```datasheet
label: Contractor Installation Warranty
type: select
options:
- "1 year from substantial completion"
- "2 years from substantial completion"
default: "1 year from substantial completion"
```
The Contractor shall warrant the installation — including level and plumb setting, anchorage and seismic restraint, door alignment, and compliance of accessible lockers with the reach-range and operable-parts requirements — for the specified period. Deficiencies attributable to installation workmanship shall be corrected by the Contractor at no cost to the Owner.
+---
+title: Metal Lockers
+category: Architectural / Specialties
+toc_depth: 3
+description: >
+ When to use: Factory-fabricated metal (steel) lockers for athletic and locker-room, employee and industrial, and school corridor applications, furnished as knocked-down (KD) standard-duty, heavy-duty, or fully welded assemblies. Covers steel sheet and component gauges, powder-coat finish over phosphatized steel, locker types and tiers (single, double, triple, box, Z-tier), ventilation (louvers, perforations, diamond), latching and locking (recessed handle, padlock hasp, built-in combination or key, electronic), trim and accessories (sloped tops, closed and Z bases, end and filler panels, number plates, benches), accessibility under the ADA Standards and ICC A117.1, and anchorage including seismic restraint.
+ Not intended for: Plastic, solid-polymer (HDPE), or phenolic lockers (see [[sync/plastic-lockers]]); wood and high-pressure-laminate casework and cubbies (see [[sync/wood-and-laminate-casework]]); wire-mesh storage partitions and tool cribs; bulk shelving and pallet rack; mailbox and parcel-delivery lockers; refrigerated or electronically managed asset-management lockers as a packaged building system; toilet compartments (see [[sync/toilet-compartments]]).
+---
+
+# Scope {toc}
+
+## This standard covers the furnishing and installation of factory-fabricated metal lockers and their trim, accessories, and anchorage. {note}
+## A metal locker is an assembly of formed steel sheet — a body (back, sides, top, and bottom), a door, and a door frame — joined either by mechanical fasteners (knocked-down, or KD, construction) or by welding, and finished with a baked powder-coat enamel. {note}
+## The scope includes the selection of construction grade to match the service duty, the steel gauges of each component, the ventilation type appropriate to the contents stored, the latching and locking method, the trim and accessories that finish a locker installation, the dimensional and operational requirements for accessible lockers, and the anchorage and seismic restraint of the installed run. {note}
+
+## This standard establishes the material, construction, finish, hardware, accessibility, and installation requirements for the lockers shown on the locker drawings. {note}
+
+## The single most consequential decision in this standard is matching the construction grade to the service duty. {note}
+## A standard-duty KD locker that performs adequately in a supervised employee coat room will be pried, dented, and racked out of service within a season in an unsupervised school corridor or a high-turnover athletic locker room. {note}
+## The narrative below ties each construction grade and gauge to the occupancy and abuse level in which it is the appropriate choice, so that the specifier selects the locker from the actual service environment rather than from first cost alone. {note}
+## Plastic, polymer, and phenolic lockers are an alternative to steel where moisture, corrosion, or hose-down cleaning rules steel out; those materials are addressed in [[sync/plastic-lockers]] and are noted here only as a selection branch. {note}
+
+## The locker layout — the number of lockers, the tier arrangement, the individual opening sizes, the bank lengths, and the location of accessible lockers — shall be [[drawing: as indicated on the locker plans and elevations]].
+## This work shall be coordinated with [[sync/gypsum-board-assemblies]] and [[sync/unit-masonry]] for in-wall blocking and wall-anchorage backing.
+## This work shall be coordinated with the flooring and base trades for the floor condition beneath closed and Z bases.
+## This work shall be coordinated with [[sync/toilet-compartments]] and [[sync/toilet-accessories]] where lockers adjoin a locker-room wet area.
+## This work shall be coordinated with the electrical trade where electronic locks require power or network connection.
+
+# Referenced Standards {toc}
+
+## The materials, fabrication, finish, and installation of metal lockers are governed by the standards listed in the table below. {note}
+
+| Standard | Title |
+|----------|-------|
+| ASTM A1008/A1008M | Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy |
+| ASTM A1011/A1011M | Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy |
+| ASTM A653/A653M | Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process |
+| ASTM D3359 | Standard Test Methods for Rating Adhesion by Tape Test |
+| ASTM B117 | Standard Practice for Operating Salt Spray (Fog) Apparatus |
+| ASTM D2794 | Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact) |
+| ASTM D523 | Standard Test Method for Specular Gloss |
+| ANSI/BHMA A156.5 | Cylinders and Input Devices for Locks (key and electronic locking, where applicable) |
+| ICC A117.1-2017 | Accessible and Usable Buildings and Facilities |
+| 2010 ADA Standards for Accessible Design | Americans with Disabilities Act Accessibility Standards (Sections 225 and 811, Storage) |
+| ASCE/SEI 7 | Minimum Design Loads and Associated Criteria for Buildings and Other Structures (nonstructural component anchorage) |
+| IBC Chapter 8 | International Building Code — Interior Finishes |
+
+## Materials, fabrication, finish, and installation shall comply with the latest adopted edition of the referenced standards.
+## Where the contract documents or the adopted building code impose more stringent requirements than a referenced standard, the more stringent requirement shall govern.
+## The Contractor shall resolve conflicts in writing with the Architect before fabrication begins.
+
+# Submittals {toc}
+
+## Action Submittals {toc}
+
+### Action submittals are reviewed and returned before fabrication. {note}
+### They establish the product, its dimensions, its finish performance, and — where required — its seismic anchorage. {note}
+
+```datasheet
+label: Action Submittals Required
+type: checkbox
+options:
+ - "Product data for locker type, construction grade, ventilation, and lock"
+ - "Dimensioned shop drawings (plans and elevations) with tier and opening sizes"
+ - "Color and finish samples (full color line)"
+ - "Sample lock and recessed handle of each type"
+ - "Finish test reports (D3359 adhesion, B117 salt spray, D2794 impact, D523 gloss)"
+ - "Accessible locker reach-range and operable-parts verification"
+ - "Seismic anchorage calculations and details (where required by SDC)"
+default: "Dimensioned shop drawings (plans and elevations) with tier and opening sizes"
+```
+
+### The following submittals shall be submitted for review and returned before fabrication begins.
+### Product data shall be submitted for each locker type, construction grade, ventilation type, and lock, and shall include the steel gauge of the body, door, and frame; the finish system; the available colors; and the lock function and keying or programming.
+### Shop drawings shall be submitted showing scaled plans and elevations of each locker location, every locker bank, the tier arrangement and individual opening sizes, bank lengths and overall dimensions, the location and tier of each accessible locker, trim, sloped-top, base, end-panel, and filler-panel locations, the number-plate sequence, bench locations, and the anchorage and seismic-restraint details with connection to the building structure.
+### Shop drawings shall identify which lockers are accessible and shall show the reach-range compliance of the accessible lockers' operable parts.
+### Color and finish samples covering the manufacturer's full color line, and — where requested — a sample lock and recessed handle of each specified type, shall be submitted.
+### Finish test reports demonstrating compliance with the adhesion (ASTM D3359), corrosion-resistance (ASTM B117), impact (ASTM D2794), and gloss (ASTM D523) requirements specified under Materials shall be submitted.
+### Where the project is in a seismic design category that requires anchorage of nonstructural components, signed and sealed anchorage calculations and details prepared in accordance with ASCE/SEI 7 for the locker height, weight, and base condition shall be submitted.
+
+## Closeout Submittals {toc}
+
+### Closeout submittals are delivered at substantial completion and hand the Owner the documentation needed to operate, maintain, and control access to the lockers. {note}
+
+```datasheet
+label: Closeout Submittals Required
+type: checkbox
+options:
+ - "Care and maintenance instructions"
+ - "Manufacturer warranty documentation"
+ - "Master keying schedule / combination / programming record (to Owner)"
+ - "Attic-stock locks, number plates, and touch-up paint inventory"
+default: "Care and maintenance instructions"
+```
+
+### At substantial completion the Contractor shall provide the manufacturer's care and maintenance instructions, the manufacturer's written warranty, a master keying schedule or combination/programming record for the installed locks, and an inventory of attic-stock parts (number plates, locks, and touch-up paint) where specified.
+### Lock control documentation shall be transmitted directly to the Owner's designated representative and shall not be left with the lockers.
+
+# Quality Assurance {toc}
+
+## Manufacturer Qualifications {toc}
+
+### The manufacturer shall be a firm regularly engaged in the fabrication of metal lockers of the type, construction grade, and lock specified, with a minimum of five years of production experience and products in service in comparable applications.
+
+### Lockers, trim, accessories, and locks within a single installation shall be the product of a single manufacturer to ensure dimensional fit and finish match.
+
+## Single-Source Responsibility {toc}
+
+### Trim, fillers, sloped tops, and bases are fabricated to the manufacturer's locker module and frame profile; mixing trim from one manufacturer with lockers from another produces misaligned joints and exposed gaps. {note}
+### Locks are machined to the manufacturer's door and frame preparation. {note}
+
+```datasheet
+label: Single-Source Responsibility
+type: radio
+options:
+ - "All lockers, trim, accessories, and locks from a single manufacturer"
+ - "Lockers and accessories furnished as a coordinated package by a single supplier"
+default: "All lockers, trim, accessories, and locks from a single manufacturer"
+```
+
+### The locker body, door, frame, trim, and lock shall be a matched system from one source.
+
+## Field Measurements {toc}
+
+### Bank lengths, recess depths, soffit heights, and the as-built location of walls and columns determine the number of lockers, the trim, and the filler panels required. {note}
+
+### The Contractor shall verify field dimensions at each locker location before fabrication.
+### Where field conditions differ from the contract drawings, the Contractor shall notify the Architect before fabrication so that openings, trim, and fillers can be adjusted.
+
+# Materials {toc}
+
+## Steel Sheet {toc}
+
+```datasheet
+label: Steel Substrate
+type: radio
+options:
+ - "Cold-rolled carbon steel sheet (ASTM A1008), standard dry interior"
+ - "Galvannealed steel sheet (ASTM A653), elevated humidity / intermittent moisture"
+default: "Cold-rolled carbon steel sheet (ASTM A1008), standard dry interior"
+```
+
+### Locker components shall be formed from prime, commercial-quality mild steel sheet, free of surface imperfections.
+### Cold-rolled sheet shall conform to ASTM A1008/A1008M.
+### Where hot-rolled sheet is used for heavier structural members, it shall conform to ASTM A1011/A1011M.
+### Where lockers will be exposed to elevated humidity or intermittent moisture, zinc-coated (galvannealed) sheet conforming to ASTM A653/A653M shall be specified for the body and door so that the steel substrate resists corrosion at coating defects.
+### In sustained-wet or hose-down environments, steel lockers shall not be used and a non-metallic locker per [[sync/plastic-lockers]] shall be selected instead.
+
+## Component Gauges by Construction Grade {toc}
+
+### The steel gauge of each component is the physical measure of locker duty. {note}
+### Gauge is expressed as a sheet-metal gauge number, where a lower number is a thicker, heavier sheet. {note}
+### The body, door, and frame each carry a gauge appropriate to the construction grade; the door and the frame — the components that take direct abuse — are heavier than the body in every grade. {note}
+### The values below are the procurable standards across the major manufacturers for each grade. {note}
+
+### Standard-duty KD lockers ship as flat components fastened together in the field. {note}
+### They are the economical choice for supervised, low-abuse employee, office, and light-commercial applications. {note}
+### Standard-duty bodies are typically 24-gauge with 16-gauge door frames and 16-gauge doors. {note}
+
+### Heavy-duty KD lockers use heavier body and door sheet and reinforced frames while retaining field-assembled KD construction. {note}
+### They are the appropriate selection for school corridors and general institutional use. {note}
+### Heavy-duty bodies are typically 16-gauge with 14- or 16-gauge door frames and 14- or 16-gauge doors. {note}
+
+### Welded (fully assembled) lockers arrive as rigid, factory-welded units with no field-fastened body seams to loosen, racking-resistant frames, and the highest abuse resistance. {note}
+### They are the appropriate selection for athletic and team locker rooms, public recreation, corrections, and any environment with heavy abuse or no supervision. {note}
+### Welded bodies are typically 16-gauge with 12- or 14-gauge frames and 14- or 16-gauge doors. {note}
+
+```datasheet
+label: Construction Grade
+type: select
+options:
+ - "Standard-duty knocked-down (KD) — supervised, low-abuse employee/office"
+ - "Heavy-duty knocked-down (KD) — school corridor, general institutional"
+ - "Welded — athletic/team room, recreation, corrections, high-abuse"
+default: "Heavy-duty knocked-down (KD) — school corridor, general institutional"
+```
+
+```datasheet
+label: Locker Body Gauge
+type: radio
+options:
+ - "24 gauge (standard-duty)"
+ - "16 gauge (heavy-duty / welded)"
+default: "16 gauge (heavy-duty / welded)"
+```
+
+```datasheet
+label: Door Frame Gauge
+type: radio
+options:
+ - "16 gauge (standard / heavy-duty)"
+ - "14 gauge (heavy-duty)"
+ - "12 gauge (welded high-abuse)"
+default: "16 gauge (standard / heavy-duty)"
+```
+
+```datasheet
+label: Door Gauge
+type: radio
+options:
+ - "16 gauge (standard / heavy-duty)"
+ - "14 gauge (heavy-duty / welded)"
+default: "16 gauge (standard / heavy-duty)"
+```
+
+### The construction grade shall be selected to match the service duty: standard-duty KD for supervised low-abuse employee and office use, heavy-duty KD for school corridors and general institutional use, and welded for athletic and team rooms, recreation, corrections, and any high-abuse or unsupervised environment.
+### Standard-duty lockers shall not be specified for unsupervised school corridors, athletic rooms, or any high-abuse application.
+### Door frame vertical members shall form a continuous integral door strike the full height of the opening.
+### KD body seams shall be flanged to provide a double thickness of metal at joints and corners.
+
+## Finish {toc}
+
+### The five-stage (or better) pretreatment — clean, rinse, iron- or zinc-phosphate conversion, rinse, seal — is essential: powder coat applied over unphosphatized steel loses adhesion and the finish fails at the first impact or scratch. {note}
+
+```datasheet
+label: Finish Gloss (ASTM D523, 60-degree)
+type: select
+options:
+ - "Low gloss / matte (hides scratches and fingerprints, athletic/corridor)"
+ - "Medium / satin gloss"
+ - "High gloss"
+default: "Low gloss / matte (hides scratches and fingerprints, athletic/corridor)"
+```
+
+```datasheet
+label: Salt-Spray Exposure (ASTM B117) Minimum
+type: range
+unit: h
+options:
+ min: 250
+ max: 1000
+ setpoints: [250, 500, 750, 1000]
+default: 500
+```
+
+```datasheet
+label: Finish Color
+type: select
+drawing_ref: true
+options:
+ - "Manufacturer's standard color (single, as selected)"
+ - "Two-tone (body one color, doors another)"
+ - "Custom color match (extended lead time)"
+default: "Manufacturer's standard color (single, as selected)"
+```
+
+### Lockers shall be finished with a baked thermoset powder-coat enamel electrostatically applied over a cleaned, phosphatized steel substrate.
+### The cured finish shall meet the performance requirements specified below.
+### Finish adhesion shall be not less than rating 4B when tested per ASTM D3359 (cross-cut tape test).
+### Finish corrosion resistance shall show no more than minimal undercutting at a scribe after 500 hours of salt-spray exposure per ASTM B117.
+### Finish impact resistance shall show no cracking or loss of adhesion at 80 in-lb direct impact per ASTM D2794.
+
+# Locker Types and Configuration {toc}
+
+## Tier Arrangement {toc}
+
+### The tier arrangement is the number of separately locking openings stacked within one locker frame height. {note}
+### More tiers give more openings per floor area at the cost of opening height. {note}
+
+### A single tier (one-tier) is one full-height opening per frame, suited to hanging coats and street clothes, and is the standard for employee and corridor lockers where garments are stored. {note}
+### A double tier (two-tier) stacks two openings, each roughly half the frame height — a common school-corridor configuration that doubles locker count where full-height hanging space is not required. {note}
+### A triple tier (three-tier) stacks three openings and is used where user count is high and stored items are small (gym clothes, books, personal effects). {note}
+### A box tier (four-, five-, or six-tier) provides four or more compact openings per frame for personal-item, valet, and day-use storage where many users share a small footprint. {note}
+### A Z-tier provides two interlocking Z-shaped openings per width, each giving partial hanging height at roughly half the floor area of a single-tier locker — a space-efficient compromise that still allows short garments to hang. {note}
+
+```datasheet
+label: Locker Tier
+type: select
+drawing_ref: true
+options:
+ - "Single tier (one-tier) — full-height, hanging garments"
+ - "Double tier (two-tier)"
+ - "Triple tier (three-tier)"
+ - "Box tier (four/five/six-tier) — compact personal items"
+ - "Z-tier — interlocking, partial hanging height, space-efficient"
+default: "Single tier (one-tier) — full-height, hanging garments"
+```
+
+### Tier shall be selected for the contents and the user: full-height single tier for hanging garments and street clothes, and box or triple tier for compact personal-item storage and high user counts.
+
+## Opening Size {toc}
+
+### The values below are the common procurable nominal sizes and serve as datasheet defaults where the drawings do not dictate otherwise. {note}
+
+```datasheet
+label: Locker Opening Width (nominal)
+type: range
+unit: in
+drawing_ref: true
+options:
+ min: 9
+ max: 24
+ setpoints: [9, 12, 15, 18, 24]
+default: 12
+```
+
+```datasheet
+label: Locker Depth (nominal)
+type: range
+unit: in
+drawing_ref: true
+options:
+ min: 12
+ max: 24
+ setpoints: [12, 15, 18, 21, 24]
+default: 15
+```
+
+```datasheet
+label: Locker Frame Height (excluding base/legs)
+type: range
+unit: in
+drawing_ref: true
+options:
+ min: 60
+ max: 72
+ setpoints: [60, 66, 72]
+default: 72
+```
+
+### Individual opening width, depth, and frame height shall be [[drawing: as indicated on the locker elevations]].
+
+## Ventilation {toc}
+
+### Non-ventilated solid doors are appropriate only for dry storage of non-perishable items. {note}
+### In humid and aquatic environments, ventilation alone does not protect plain steel; specify galvannealed substrate per Materials, or select a non-metallic locker per [[sync/plastic-lockers]]. {note}
+
+```datasheet
+label: Ventilation Type
+type: select
+options:
+ - "Solid (non-ventilated) — dry storage only"
+ - "Louvered door (general athletic/gym ventilation)"
+ - "Full-perforated door (high airflow, wet team rooms)"
+ - "Diamond-perforated door and sides (maximum airflow, pool/aquatic)"
+default: "Louvered door (general athletic/gym ventilation)"
+```
+
+### Lockers that store damp athletic clothing, footwear, or wet-weather garments shall be ventilated so that moisture and odor are not trapped.
+### The ventilation type shall be matched to the airflow needed: louvered doors for general athletic and gym use, and full perforation or diamond perforation for maximum airflow in wet team rooms and pool environments.
+### Louvers and perforations shall be formed in the door (and, for diamond ventilation, the sides) without sharp edges.
+
+# Latching and Locking {toc}
+
+## The latching mechanism holds the door closed and engages the lock; the lock secures the contents. {note}
+## The two are selected together. {note}
+## Recessed handles and recessed latches reduce snag and vandalism in corridors and athletic rooms; surface lift handles are simpler and lower cost for supervised employee use. {note}
+## Multi-point latching distributes the holding force along the door height and resists prying in abuse-prone applications. {note}
+
+## Latch and Handle {toc}
+
+### Three-point (multi-point) latching engages the door at the top, center, and bottom of the frame and is the standard for unsupervised corridor and athletic lockers because it resists the pry-at-a-corner attack that defeats single-point latches. {note}
+### The recessed handle houses the lock in a protected pocket so the lock body cannot be struck or pried. {note}
+
+```datasheet
+label: Latch and Handle Type
+type: select
+options:
+ - "Recessed handle, single-point latch (low-abuse, recessed lock pocket)"
+ - "Recessed handle, three-point latch (corridor/athletic, anti-pry)"
+ - "Surface lift handle, single-point latch (supervised employee)"
+ - "Surface lift handle, multi-point latch"
+default: "Recessed handle, three-point latch (corridor/athletic, anti-pry)"
+```
+
+### The latch and handle shall be selected for the service environment: recessed handles and recessed latches for corridor and athletic rooms to reduce snag and vandalism, and surface lift handles for supervised employee use.
+### Multi-point (three-point) latching shall be specified for unsupervised, abuse-prone corridor and athletic lockers to resist prying.
+
+## Locking Method {toc}
+
+### Built-in combination locks suit schools and shared institutional use; padlock hasps let users supply their own locks; key locks suit assigned employee lockers; electronic locks suit day-use and shared lockers where users set their own code per use. {note}
+### Where electronic locks are hard-wired or networked, power and data rough-in is coordinated with the electrical trade before fabrication. {note}
+
+```datasheet
+label: Locking Method
+type: select
+options:
+ - "Recessed padlock hasp (user-supplied padlock)"
+ - "Built-in combination lock (single-combination, assigned)"
+ - "Built-in resettable/multi-user combination lock (shared/day-use)"
+ - "Built-in key lock (cam/cylinder, keyed, master-keyed)"
+ - "Electronic keypad/RFID lock (programmable, day-use or assigned)"
+ - "Provision for Owner-furnished lock (hasp/cutout only)"
+default: "Built-in combination lock (single-combination, assigned)"
+```
+
+```datasheet
+label: Built-In Lock Keying / Control
+type: radio
+options:
+ - "Keyed alike within control group, master-keyed (key locks)"
+ - "Combination set list provided to Owner (combination locks)"
+ - "Owner-programmed at commissioning (electronic locks)"
+ - "Not applicable (user-supplied padlock)"
+default: "Combination set list provided to Owner (combination locks)"
+```
+
+### The locking method shall be selected for the Owner's access-control needs, the user population, and the willingness to manage keys, combinations, or batteries.
+### Electronic locks shall be specified with a clearly defined power source (battery or hard-wired).
+### Electronic locks shall be specified with a documented mechanical or master override for lockout recovery.
+### Where electronic locks are hard-wired or networked, power and data rough-in shall be coordinated with the electrical trade before fabrication.
+### Where electronic locks are battery-powered, the closeout submittal shall state the battery type and the expected service interval.
+
+# Accessories and Trim {toc}
+
+## Trim and accessories finish a locker installation, close gaps to walls and soffits, keep dust and debris off and out of the lockers, and identify openings. {note}
+## They are selected for the installation condition and the housekeeping environment. {note}
+
+## Sloped Tops {toc}
+
+### Omitting sloped tops in a dusty or unsupervised environment is a common and avoidable maintenance failure. {note}
+
+```datasheet
+label: Sloped Tops
+type: radio
+options:
+ - "Continuous sloped tops (prevents storage/dust accumulation atop lockers)"
+ - "Flat tops (storage shelf above, low-dust environment)"
+default: "Continuous sloped tops (prevents storage/dust accumulation atop lockers)"
+```
+
+### Continuous sloped tops, typically 16-gauge with an approximately 18-degree pitch, shall be specified for corridor, athletic, and public installations to prevent the locker tops from becoming a dust shelf and an informal storage surface.
+### Sloped-top end closures and splice covers shall be furnished to finish exposed ends and joints.
+
+## Base {toc}
+
+### A Z-base (channel base) raises the lockers off the floor and creates a recessed toe space, improving appearance and simplifying floor cleaning; closed bases conceal legs for a finished look in public areas. {note}
+
+```datasheet
+label: Locker Base
+type: select
+drawing_ref: true
+options:
+ - "Closed (front and end) base over legs (conceals legs, finished appearance)"
+ - "Z-base / channel base, 4 in (raises lockers, creates toe space)"
+ - "Z-base / channel base, 6 in"
+ - "Legs exposed (utility/back-of-house)"
+ - "No base — lockers set directly on finished floor"
+default: "Closed (front and end) base over legs (conceals legs, finished appearance)"
+```
+
+### The base condition shall be coordinated with the finished flooring and base trades.
+
+## End Panels, Filler Panels, and Recess Trim {toc}
+
+```datasheet
+label: Exposed-End Treatment
+type: radio
+options:
+ - "Finished end panels at all exposed locker ends"
+ - "No finished ends (ends concealed by walls)"
+default: "Finished end panels at all exposed locker ends"
+```
+
+```datasheet
+label: Filler Panels at Walls / Obstructions
+type: radio
+options:
+ - "Provide filler panels to close gaps to walls, columns, and obstructions"
+ - "Not required (lockers fit module exactly)"
+default: "Provide filler panels to close gaps to walls, columns, and obstructions"
+```
+
+```datasheet
+label: Recess Trim
+type: radio
+drawing_ref: true
+options:
+ - "Provide recess trim where lockers are recessed into wall/soffit"
+ - "Not required (lockers not recessed)"
+default: "Not required (lockers not recessed)"
+```
+
+### Finished end panels shall close exposed locker ends.
+### Filler panels shall close the gaps between lockers and walls, columns, or obstructions.
+### Recess trim shall bridge the gap to the wall and soffit where lockers are recessed.
+### Filler and trim quantities shall be confirmed against field dimensions before fabrication, because gap and obstruction conditions are not always apparent until field measurement.
+
+## Number Plates {toc}
+
+### An arbitrary numbering sequence forces the Owner to renumber after installation, so the sequence is set from the Owner's locker-assignment scheme. {note}
+
+```datasheet
+label: Number Plates
+type: radio
+options:
+ - "Provide number plates, sequence per Owner schedule"
+ - "Provide number plates, sequential by bank"
+ - "Not required"
+default: "Provide number plates, sequence per Owner schedule"
+```
+
+### Number plates shall be riveted to each door at a consistent location.
+### The numbering sequence shall be coordinated with the Owner's locker-assignment scheme.
+
+## Interior Equipment and Benches {toc}
+
+```datasheet
+label: Interior Equipment
+type: checkbox
+options:
+ - "Coat hooks / single-prong wall hooks"
+ - "Double-prong ceiling hooks"
+ - "Coat rod (single-tier garment lockers)"
+ - "Top shelf"
+ - "Footwear shelf / bottom shelf"
+default: "Top shelf"
+```
+
+```datasheet
+label: Locker-Room Benches
+type: radio
+drawing_ref: true
+options:
+ - "Provide benches (hardwood top on pedestals), lengths per drawings"
+ - "Not required"
+default: "Not required"
+```
+
+### Where benches are provided, hardwood bench tops on metal pedestals shall be the standard.
+### Bench lengths and locations shall be [[drawing: as indicated]].
+### Where accessibility requires it, at least one bench complying with the accessible-bench provisions of the accessibility standard shall be provided in each locker room (see Accessibility below).
+
+# Accessibility {toc}
+
+## Coverage {toc}
+
+### The 2010 ADA Standards (Sections 225 and 811) and ICC A117.1 require that at least 5 percent of lockers of each type, but no fewer than one of each type, comply. "Each type" includes each functional class of locker (for example, full-height garment lockers and box lockers are different types and each requires its accessible share). {note}
+
+```datasheet
+label: Accessible Locker Quantity Basis
+type: radio
+drawing_ref: true
+options:
+ - "5 percent of each type, minimum one of each type (per ADA 811 / A117.1)"
+ - "Greater quantity as indicated on the drawings"
+default: "5 percent of each type, minimum one of each type (per ADA 811 / A117.1)"
+```
+
+### Where lockers are provided, accessible lockers shall be provided in accordance with the adopted accessibility standard.
+### The number, type, and location of accessible lockers shall be [[drawing: as indicated on the locker plans and accessibility compliance documents]].
+### The Architect shall confirm the count and configuration of accessible lockers from the accessibility compliance path.
+
+## Reach Ranges and Operable Parts {toc}
+
+### The defining requirement for an accessible locker is that its usable storage and every operable part fall within the reach range. {note}
+### Accessible lockers are normally located in a single tier or in the lower tier of a multi-tier bank so that the opening and the lock are reachable from a seated position. {note}
+### A conventional small combination dial or a key cam lock that must be pinched and twisted does not meet the operable-parts criteria.
+
+```datasheet
+label: Accessible Locker Operable-Parts Height (AFF)
+type: range
+unit: in AFF
+options:
+ min: 15
+ max: 48
+ setpoints: [15, 36, 44, 48]
+default: 44
+```
+
+```datasheet
+label: Accessible Locker Lock Type
+type: select
+options:
+ - "Built-in combination lock with large, easy-grip dial/buttons"
+ - "Electronic keypad/RFID lock (no grasping or twisting)"
+ - "Recessed padlock hasp (only where padlock meets operable-parts criteria)"
+default: "Electronic keypad/RFID lock (no grasping or twisting)"
+```
+
+### The usable storage in an accessible locker shall be within an unobstructed forward or side reach range of 15 in. minimum to 48 in. maximum above the finished floor.
+### Every operable part of an accessible locker — handle, lock, keypad, and latch — shall be within the 15 in. to 48 in. reach range above the finished floor.
+### Every operable part of an accessible locker shall be operable with one hand without tight grasping, pinching, or twisting of the wrist, and with no more than 5 lbf of force.
+### Accessible lockers shall use a lock operable with a closed fist or one easy motion.
+### A clear floor space and an accessible route shall be provided at each accessible locker.
+### The clear floor space at each accessible locker shall be verified against the locker plan.
+
+## Accessible Benches {toc}
+
+### Where benches are required in a locker room, at least one bench shall comply with the accessible-bench provisions (seat height, depth, back support, and clear floor space) of the accessibility standard.
+
+### The accessible bench and its clear floor space shall be coordinated with the locker layout so the clearance is not blocked by a locker bank.
+
+# Fabrication {toc}
+
+## Lockers shall be fabricated to the dimensions and configuration shown on the approved shop drawings.
+
+## Welded lockers shall be factory-welded into rigid units with welds ground smooth at exposed surfaces before finishing.
+
+## KD lockers shall be fabricated with formed, flanged components that assemble into square, rigid banks with mechanical fasteners.
+
+## Doors shall be formed with a continuous channel or box section at the lock edge.
+## Doors shall be hung to operate freely without binding, with the latch engaging the strike fully.
+
+## Louvers, perforations, and ventilation openings shall be formed without sharp or burred edges.
+
+## All components shall be cleaned, phosphatized, and powder-coated after forming and welding so that cut and formed edges are coated.
+
+## All exposed welds shall be ground smooth before finishing.
+
+## All sheared and formed edges shall be free of burrs and sharp edges.
+
+# Installation {toc}
+
+## Coordination and Blocking {toc}
+
+### Blocking is furnished and installed under the wall trades; anchoring lockers or benches to gypsum board without blocking is a primary cause of failure. {note}
+
+```datasheet
+label: In-Wall Blocking Verified Before Installation
+type: radio
+options:
+ - "Yes — blocking verified at all wall anchorage points before installation"
+ - "Not applicable — no wall-anchored components"
+default: "Yes — blocking verified at all wall anchorage points before installation"
+```
+
+### Lockers shall be installed after the wall and floor finishes are complete and the building is enclosed and conditioned.
+### The Contractor shall verify before installation that solid in-wall blocking has been provided where lockers, trim, or benches anchor to walls.
+### The locker Contractor shall confirm the presence and location of blocking against the shop drawings and shall notify the Architect of any missing or mislocated blocking before proceeding.
+### Anchoring lockers or benches to gypsum board without blocking shall not be permitted.
+
+## Anchorage {toc}
+
+```datasheet
+label: Anchorage Condition
+type: select
+drawing_ref: true
+options:
+ - "Floor-anchored and wall-anchored (back to wall)"
+ - "Floor-anchored and top-anchored to wall (tall single-row banks)"
+ - "Back-to-back freestanding, floor-anchored and braced"
+ - "Recessed into wall opening, anchored to surrounding structure"
+default: "Floor-anchored and wall-anchored (back to wall)"
+```
+
+### Lockers shall be set level and plumb, shimmed as required, and anchored to the building structure.
+### Banks shall be bolted together into continuous runs and anchored to the floor and, where backs are accessible, to the wall.
+### Anchorage shall use fasteners appropriate to the substrate — expansion or wedge anchors into concrete, anchors into masonry, and through-bolts or lag screws into in-wall blocking within stud walls.
+### Tall lockers shall be anchored at the top to the wall or, where freestanding, braced back-to-back, so they cannot tip.
+
+## Seismic Restraint {toc}
+
+```datasheet
+label: Seismic Anchorage Required
+type: radio
+drawing_ref: true
+options:
+ - "Yes — seismic anchorage per ASCE/SEI 7 and sealed calculations"
+ - "No — not required by the seismic design category"
+default: "No — not required by the seismic design category"
+```
+
+### Seismic restraint is determined by the project's seismic design category and the locker height and weight. {note}
+
+### Where the seismic design category requires anchorage of nonstructural components, lockers (particularly banks 60 in. or taller) shall be anchored vertically and laterally to resist the seismic forces determined per ASCE/SEI 7, in accordance with the sealed anchorage calculations and details submitted under Submittals.
+### The Architect and Structural Engineer shall confirm the seismic-restraint requirement.
+### Anchorage relying solely on sheet-metal screws into unbraced studs shall not be accepted as satisfying a seismic anchorage requirement.
+
+## Adjustment and Cleaning {toc}
+
+### Field touch-up does not reproduce the baked finish, so damaged components are replaced rather than field-repaired. {note}
+
+### After installation the Contractor shall adjust every door so it operates freely, latches fully, and the lock engages.
+### After installation the Contractor shall verify that accessible lockers' operable parts are within the reach range and operable as specified.
+### After installation the Contractor shall install all trim, number plates, and accessories and shall clean all surfaces.
+### Protective coverings shall remain in place until adjustment and cleaning are complete.
+### Doors that bind, latches that do not engage, and finish damage shall be corrected.
+### Deep scratches and corroded components shall be replaced rather than field-repaired.
+
+# Warranty {toc}
+
+## Welded heavy-duty locker programs commonly carry substantially longer warranties than standard-duty KD lockers. {note}
+
+```datasheet
+label: Locker Warranty Period
+type: select
+options:
+ - "1 year from substantial completion — standard"
+ - "5 years from substantial completion"
+ - "Lifetime limited warranty against defects (welded heavy-duty programs)"
+default: "5 years from substantial completion"
+```
+
+```datasheet
+label: Lock Warranty
+type: select
+options:
+ - "Manufacturer's standard lock warranty (mechanical locks)"
+ - "Extended electronic-lock warranty including controller and keypad"
+default: "Manufacturer's standard lock warranty (mechanical locks)"
+```
+
+```datasheet
+label: Contractor Installation Warranty
+type: select
+options:
+ - "1 year from substantial completion"
+ - "2 years from substantial completion"
+default: "1 year from substantial completion"
+```
+
+## The manufacturer shall warrant the lockers against defects in materials and workmanship — including finish adhesion, door and latch operation, and structural integrity of the body and frame — for the specified period.
+## Where the project uses welded construction, the longer warranty offered by the welded program should be obtained and documented.
+## The warranty shall not cover abuse beyond the rated service condition, improper cleaning chemicals, or modifications made without the manufacturer's authorization.
+## The Contractor shall warrant the installation — including level and plumb setting, anchorage and seismic restraint, door alignment, and compliance of accessible lockers with the reach-range and operable-parts requirements — for the specified period.
+## Deficiencies attributable to installation workmanship shall be corrected by the Contractor at no cost to the Owner.

View current revision