Overhead Coiling Doors

Rev 2 · Updated Jun 4, 2026 · View history

1 Scope

NOTE This standard covers the furnishing, installation, and commissioning of overhead coiling doors and coiling closures in commercial, institutional, and industrial construction. (1.1)
NOTE The scope includes non-insulated and insulated coiling service doors, coiling counter doors and counter shutters, coiling grilles, and fire-rated coiling doors. (1.2)

1.3 Scope Basis

1.3.1Opening sizes, locations, fire ratings, and wind-load design pressures shall be as indicated on the contract drawings.
1.3.2This standard establishes the minimum performance, material, fabrication, operation, installation, and inspection requirements that apply to each of those conditions.

1.4 What a Coiling Door Is

NOTE Because the curtain coils rather than swings, a coiling door occupies almost no floor or ceiling space when open, which is why it is selected for openings where headroom is limited or where a horizontally tracked door would obstruct the space behind the opening. (1.4.2)
NOTE The trade-off is that the entire assembly is engineered as a balanced rolling system — the counterbalance spring, the curtain weight, the guide engagement, and the operator must be matched to the specific opening size and to the design wind load. (1.4.3)
NOTE A coiling door is not a catalog commodity that can be cut to fit in the field; each unit is fabricated for its opening and its loads. (1.4.4)

1.5 Coordination

1.5.1Coordinate this work with the structural and masonry trades that form the opening and provide the jambs and lintel to which guides and brackets anchor (see Unit Masonry and Structural Steel Framing).
1.5.2Coordinate this work with the electrical trade for power and control wiring to motor operators.
1.5.3Coordinate this work with Fire Alarm Systems for release of fire-rated coiling doors on alarm or detector signal.
1.5.4Coordinate this work with Firestopping where the head and jamb conditions of a rated door penetrate or terminate at a rated wall.

2 Referenced Standards

2.1Materials, fabrication, testing, and installation shall comply with the latest adopted edition of the referenced standards.

2.2 Conflict Precedence

2.2.1Where the contract documents or the adopted building code impose more stringent requirements than a referenced standard, the more stringent requirement shall govern.
2.2.2The Contractor shall resolve conflicts in writing with the Engineer of Record before proceeding.

2.3 Standards Table

Standard Title
ANSI/DASMA 102 Specifications for Sectional Doors (counterbalance, cable, and component safety-factor conventions applied to coiling assemblies)
ANSI/DASMA 105 Test Method for Thermal Transmittance and Air Infiltration of Garage Doors
ANSI/DASMA 108 Standard Method for Testing Sectional Garage Doors and Rolling Doors: Determination of Structural Performance Under Uniform Static Air Pressure Difference
ANSI/DASMA 115 Standard Method for Testing Sectional Garage Doors and Rolling Doors: Determination of Structural Performance Under Missile Impact and Cyclic Wind Pressure
ANSI/DASMA 118 Standard Method for Testing Sectional Garage Doors and Rolling Doors: Determination of Structural Performance Under Cyclic Wind Loading
NFPA 80 (2025 Edition) Standard for Fire Doors and Other Opening Protectives
NFPA 252 Standard Methods of Fire Tests of Door Assemblies
UL 10B Fire Tests of Door Assemblies (neutral-pressure test referenced for rolling steel fire doors and sensing edges)
UL 10C Positive Pressure Fire Tests of Door Assemblies
ANSI/UL 325 Standard for Door, Drapery, Gate, Louver, and Window Operators and Systems
ASTM E330 Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights, and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E283 Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences
ASTM E1886 Standard Test Method for Performance of Exterior Windows, Doors, Shutters, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials
ASTM E1996 Standard Specification for Performance of Exterior Windows, Doors, Shutters, and Impact Protective Systems Impacted by Windborne Debris
ASTM A653 Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
IBC Chapter 7 / Table 716.1(1) Fire and Smoke Protection Features — Opening Protectives
ASCE 7 Minimum Design Loads and Associated Criteria for Buildings and Other Structures (wind-load determination)

3 Submittals

3.1 Action Submittals

3.1.1The following submittals shall be submitted for review and returned before fabrication or procurement begins.
Action Submittals Requiredcheckbox
Door schedule cross-referenced to drawings
Shop drawings with clearance and anchorage details
Product data for curtain, finish, seals, operator, and controls
Wind-load calculations or test report (where design pressure specified)
Fire-door NRTL listing documentation (rated openings)
Operator and UL 325 entrapment-protection documentation (powered doors)
3.1.2Because each coiling door is engineered for its opening and loads, the submittal shall be specific to the door schedule and shall not consist of generic catalog literature alone.
3.1.3Submit a Door Schedule listing every coiling unit by mark number, including opening width and height, door type (service, insulated service, counter, grille, fire-rated), curtain material and gauge, fire-rating period where applicable, design wind-load pressure where applicable, operation type, mounting condition (face-of-wall or between-jambs), and finish.
3.1.4Submit Shop Drawings for each door type showing curtain slat profile, guide and bracket details, hood profile and projection, counterbalance barrel and spring data, bottom bar, required headroom and sideroom, anchorage to the structure, and the location of the fire-door label where applicable, indicating the clearances the door requires so that the opening and the surrounding construction can be verified before fabrication.
3.1.5Submit Product Data — the manufacturer's technical data for the curtain, finish system, weatherseals, operator, controls, and entrapment-protection devices.
3.1.6Submit Wind-Load Engineering — for doors with a specified design pressure, structural calculations or a current test report demonstrating compliance with ANSI/DASMA 108 (and ANSI/DASMA 115 or ASTM E1886/E1996 where windborne-debris resistance is required) at the design pressure for the opening.
3.1.7Submit Fire-Door Listing Documentation — for each fire-rated coiling door, the Nationally Recognized Testing Laboratory listing covering the door type, the rating period, the maximum size, the wall construction, and the release and reset mechanism.
3.1.8Submit Operator and UL 325 Compliance Documentation — for powered doors, the operator listing, the entrapment-protection scheme, and confirmation that the operator and its monitored safety devices comply with the edition of UL 325 in force.

3.2 Closeout Submittals

3.2.1At substantial completion the Contractor shall provide the following before final acceptance:
  • Operation and maintenance manuals for each door type, including lubrication points, counterbalance adjustment procedure, and operator and control programming
  • Final as-built door schedule reflecting field conditions
  • Warranty documentation from the door manufacturer and the operator manufacturer
  • For fire-rated coiling doors, the manufacturer's reset instructions and the record of the acceptance drop test performed under NFPA 80, together with written instruction to the Owner regarding the mandatory annual drop test and inspection
  • For powered doors, the record of the UL 325 entrapment-protection functional test
Closeout Submittals Requiredcheckbox
Operation and maintenance manuals
Final as-built door schedule
Warranty documentation (door and operator)
Fire-door reset instructions and acceptance drop-test record
Annual drop-test instruction package to Owner
UL 325 entrapment-protection functional test record

4 Quality Assurance

4.1 Manufacturer Qualifications

4.1.1The coiling door manufacturer shall demonstrate a minimum of five years of continuous production of coiling doors of the types and sizes required on the project.
4.1.2For fire-rated coiling doors, the manufacturer shall maintain a current, active listing with a Nationally Recognized Testing Laboratory for each rating period required on the project.

4.2 Installer Qualifications

4.2.1The installer shall be a firm trained and authorized by the door manufacturer to install and adjust the products supplied.
4.2.2For fire-rated coiling doors, the installer shall be qualified to install the listed release and reset mechanism and to perform the acceptance drop test in accordance with NFPA 80.

4.3 Single-Source Responsibility

Single-Source Responsibilityradio
Door, counterbalance, operator, and controls from one manufacturer or its authorized system
Operator and controls by others, coordinated by the door manufacturer
NOTE Single-source responsibility is preferred because the counterbalance, the curtain weight, the guide engagement, and the operator must be matched as a system; splitting responsibility across vendors creates a coordination gap precisely at the interface that determines whether the door is balanced and whether the operator can move the curtain without overloading. (4.3.1)

5 Performance

5.1 Performance Basis

NOTE The most common in-service failures of coiling doors trace to a performance requirement that was understated at procurement — a door selected without a wind-load rating that the code required for its location, a fire-rated door whose closing speed or reset behavior was never verified, or an exterior door with no air-infiltration limit on a conditioned building. (5.1.1)
5.1.2The requirements in this section stand independent of the catalog model and shall be satisfied for the specific opening.

5.2 Wind Load

5.2.1 Design Wind Pressure

Design Wind Pressure (positive/negative, ASCE 7)range
psf
15100
152025304050607080100
Default: 30 psf
5.2.1.1The design wind pressure for each exterior coiling door shall be determined in accordance with ASCE 7 for the building's risk category, basic wind speed, exposure, and the door's height and location on the wall, including the higher pressures that apply at building corners and edge zones.
NOTE Door manufacturers publish wind-load tables, but the design pressure is a property of the building and the opening, not of the door; it shall be established by the design team and indicated on the drawings. (5.2.1.2)

5.2.2 Structural Test Method

Wind-Load Structural Verificationradio
Manufacturer wind-load table covering the design pressure
Test report to ANSI/DASMA 108 / ASTM E330 at the design pressure
Not required (interior door)
5.2.2.1Each exterior coiling door shall be designed and, where required, tested to withstand the design wind pressure without permanent deformation that impairs operation.
5.2.2.2Structural performance shall be demonstrated under uniform static air pressure in accordance with ANSI/DASMA 108 or ASTM E330.

5.2.3 Windborne-Debris Resistance

Windborne-Debris (Impact) Rating Requiredradio
No — outside windborne-debris region
Yes — large- and small-missile impact per ASTM E1886/E1996
Yes — missile impact and cyclic wind per ANSI/DASMA 115
5.2.3.1In windborne-debris regions, exterior coiling doors shall additionally resist large- and small-missile impact and the subsequent cyclic pressure loading in accordance with ASTM E1886 and the impact classification of ASTM E1996, or the missile-impact and cyclic-wind method of ANSI/DASMA 115.
NOTE Windborne-debris resistance is a separate requirement from static wind pressure; a door rated for the static pressure is not necessarily impact-rated. (5.2.3.2)

5.3 Air Infiltration

Maximum Air Infiltration (ASTM E283 at 1.57 psf / 25 mph)range
cfm/sf
0.31.5
0.30.50.811.5
Default: 1 cfm/sf
5.3.1Exterior coiling doors on conditioned buildings shall have a maximum air-infiltration rate verified in accordance with ASTM E283 (or the air-infiltration method of ANSI/DASMA 105) at the specified test pressure.
NOTE Coiling-door curtains leak primarily at the slat interlocks, the guides, and the bottom bar, so the infiltration limit drives the selection of slat-interlock weatherseals, guide weatherstrip, and bottom-bar astragal. (5.3.2)

5.4 Fire Rating

5.4.1 Required Rating

Fire-Resistance Ratingradio
Not fire rated
3/4 hour (45 min) — corridor / partition opening
1-1/2 hour (90 min)
3 hour (180 min)
4 hour (240 min)
5.4.1.1The fire-protection rating of a coiling door shall be as required by the adopted building code for the rated wall in which it occurs.
NOTE Under IBC Table 716.1(1), the opening-protective rating is keyed to the wall rating; fire-rated coiling doors are commonly furnished in 3/4-hour, 1-1/2-hour, 3-hour, and 4-hour periods, and the required period for each opening shall be indicated on the drawings. (5.4.1.2)

5.4.2 Test Standard and Labeling

5.4.2.1Fire-rated coiling doors shall be tested and labeled in accordance with NFPA 252 or UL 10B and shall bear the label of a Nationally Recognized Testing Laboratory.
5.4.2.2The label shall remain legible and permanently affixed.
5.4.2.3The assembly as installed — curtain, guides, hood, release mechanism, and wall construction — shall match the conditions of the listing.
5.4.2.4Sensing edges used on powered fire-rated doors shall be tested and listed as components of the rolling steel fire-door assembly under UL 10B.

5.4.3 Release, Closing, and Reset

Fire-Door Release Methodradio
Fusible link (separates at 165°F) releasing the curtain to gravity close
Fail-safe electric (governor-controlled) release on fire alarm or detector signal, with fusible link backup
5.4.3.1On release, the curtain shall descend by gravity under the control of a speed governor, and the average closing speed shall be not less than 6 in./s and not more than 24 in./s in accordance with NFPA 80.
5.4.3.2After automatic closing the bottom bar shall come to rest in the fully closed position.
5.4.3.4A powered fire-rated door shall not reset until any fire-alarm relay has returned to its normal, non-alarm state.
5.4.3.5Coordinate the release with Fire Alarm Systems where alarm-initiated release is specified.

5.5 Cycle Life

Duty / Cycle-Life Classradio
Standard duty — up to 20 cycles/day
Heavy duty — 20 to 50 cycles/day
High cycle — 50+ cycles/day (cycle-tested barrel and counterbalance)
5.5.1The duty rating of a coiling door shall match its expected use.
NOTE A coiling counter door at a concession opens many times a day; a fire-rated door in a wall opening may operate only at the annual test. (5.5.2)
5.5.3Specify the duty class so that the counterbalance, guides, and operator are sized for the service.

5.6 Thermal Performance (Insulated Doors)

Insulated Curtain Thermal Value (R-value, ANSI/DASMA 105)range
hr·ft²·°F/Btu
611
67891011
Default: 8 hr·ft²·°F/Btu
5.6.1Where an insulated coiling door is specified on a conditioned opening, the curtain shall achieve the specified thermal value, verified in accordance with ANSI/DASMA 105.
NOTE Insulated coiling-door curtains use roll-formed slats sandwiching a foamed-in-place polyurethane core; procurable assemblies commonly reach an installed R-value in the range of about R-6 to R-11, with corresponding STC values in the low-to-upper 20s. (5.6.2)

6 Door Assembly

6.1 Door Type

Coiling Door Typeradio
Service door — interlocking steel slat curtain, non-insulated
Insulated service door — foamed slat curtain
Counter door — small opening over a counter or pass-through
Coiling grille — horizontal rods and vertical links (security/visibility)
Fire-rated coiling door — labeled assembly

6.2 Curtain and Slats

6.2.1 Slat Profile

Slat Profileradio
Flat / minimal-curve slat
Curved (crowned) slat
Insulated foamed flat slat (double-skin)
Grille — rod-and-link (not a slat curtain)
6.2.1.1The curtain shall consist of roll-formed interlocking slats.
6.2.1.2The selected slat profile shall be confirmed against the opening size and the design wind pressure, because slat stiffness contributes to the door's resistance to wind.
NOTE Flat-profile slats present a cleaner appearance and are common at storefront and architectural openings; curved (crowned) slats add stiffness and are common on larger industrial openings. (6.2.1.3)

6.2.2 Curtain Material

Curtain Materialradio
Galvanized steel (ASTM A653)
Aluminum
Stainless steel (Type 304)
NOTE Galvanized steel is the default for interior and most exterior openings. Aluminum is selected for corrosion resistance and reduced curtain weight, often on counter doors and grilles. Stainless steel is selected for corrosive, washdown, or food-service environments and for architectural exposure. (6.2.2.1)

6.2.3 Slat Gauge

Steel Slat Gaugeradio
24 gauge (small to moderate openings)
22 gauge
20 gauge
18 gauge (large or high-wind openings)
6.2.3.1The slat gauge shall be selected for the opening size and design wind pressure; larger and higher-pressure openings require heavier slats.
NOTE The default above covers typical commercial service-door openings. (6.2.3.2)

6.2.4 Windlocks

Windlocksradio
Not required at design pressure
Provided as required by wind-load listing
6.2.4.1Where the design wind pressure exceeds the capacity of the plain slat-in-guide engagement, the curtain shall be fitted with windlocks (slat-end clips that engage the guide) at the spacing required by the manufacturer's wind-load listing for the design pressure.

6.3 Hood

Hood Materialradio
Galvanized steel
Aluminum
Stainless steel
6.3.1A sheet-metal hood shall enclose the coiled curtain and barrel.
6.3.2The hood material shall match or be compatible with the curtain finish.
6.3.3On fire-rated doors the hood shall be of the type and gauge included in the listing.
6.3.4Provide an intermediate support at the hood mid-span on wide openings to prevent sag.

6.4 Guides

6.4.1The guides shall be structural angle or formed sections sized to retain the curtain under the design wind load and to resist the reaction from windlocks where used.
6.4.2Guides shall be fastened to the jamb at the spacing required by the wind-load listing.
6.4.3On fire-rated doors the guide depth and fastening shall match the listing.

6.5 Brackets and Barrel

6.5.1The brackets shall support the barrel and counterbalance at each end and shall transfer the curtain and wind reactions to the structure.
6.5.2The barrel (the steel pipe onto which the curtain coils) shall be sized so that deflection under the curtain load does not impair operation.

6.6 Counterbalance

6.6.1The counterbalance shall be a helical torsion spring assembly within the barrel, designed to balance the curtain weight throughout travel so that the door can be operated with the specified effort.
6.6.2Counterbalance design conventions shall follow the safe-conversion-of-spring-torque and minimum-life intent of ANSI/DASMA 102.
6.6.3Manual doors shall be balanced to be moved with reasonable effort and powered doors balanced to the operator's rating.
6.6.4The counterbalance shall be adjustable in the field to retension the curtain.

6.7 Bottom Bar

6.7.1The bottom bar shall be a formed or extruded section reinforcing the lower edge of the curtain and providing the surface for the bottom weatherseal.
6.7.2On powered doors the bottom bar shall carry the sensing edge where used for entrapment protection.
6.7.3The bottom bar shall seat squarely on the floor or sill in the closed position.

7 Operation and Operators

7.1 Operation Type

Operation Typeradio
Manual push-up
Manual chain hoist (hand chain and reduction)
Motor operator — wall/jamb mount
Motor operator — bracket/hood mount
Tube (barrel) motor — low headroom
7.1.1The means of operation shall be selected for the door size, weight, frequency of use, and whether powered operation is functionally required.
NOTE Manual push-up is suitable only for small, well-balanced doors. Chain hoist is the default for larger manually operated doors. Motor operation is selected for high-frequency use, large or heavy curtains, and remote or automated control. (7.1.2)

7.2 Motor Operator Controls

Operator Control Typeradio
Three-button (open / close / stop), constant-pressure close
Three-button momentary with monitored entrapment protection
Three-button with radio/remote and access-control interface
7.2.1Specify a manual override (chain hoist or hand crank) for powered doors so the curtain can be operated during a power failure.
7.2.2Coordinate operator electrical requirements — voltage, phase, disconnect, and conduit — with the electrical drawings.
7.2.3The operator location shall be confirmed against the available headroom and sideroom before rough-in.

7.3 UL 325 Entrapment Protection

UL 325 Entrapment Protection Schemeradio
Inherent reversing system plus monitored sensing edge (external)
Inherent reversing system plus monitored photo-eye (external)
Constant-pressure close (no automatic close) — where permitted
7.3.1Powered coiling doors shall comply with the edition of UL 325 in force.
7.3.2Under the 2016 and later requirements, each entrapment point shall be protected by at least two independent means of entrapment protection.
7.3.3Every external entrapment-protection device shall be monitored by the operator at least once per cycle for both proper operation and proper connection.
7.3.4On a monitored-device fault the operator shall inhibit powered closing.
NOTE An inherent reversing system alone does not satisfy the two-means requirement, and a duplicate of the same device does not count as the second means. (7.3.5)
7.3.6On a powered fire-rated door, the entrapment-protection devices shall be coordinated with the fire-door release so that an alarm-initiated gravity closing is not blocked by the entrapment devices, while normal powered operation remains protected.

8 Finishes

Curtain / Hood Finishradio
Mill galvanized (no topcoat)
Factory primer (field-finish by painting trade)
Factory-applied baked polyester powder coat
Anodized (aluminum)
No. 4 brushed (stainless)

8.1 Finish Coordination

8.1.1Where the curtain is factory-primed only, coordinate the topcoat with Exterior Painting or Interior Painting as applicable.
8.1.2Confirm color selection against the manufacturer's standard powder-coat range before order.

9 Weatherseals

Weatherseal Packagecheckbox
Bottom-bar astragal (floor seal)
Guide weatherstrip (jamb seals)
Header / hood baffle seal
Interlock slat seals (insulated doors)

9.1 Weatherseal Requirements

9.1.1Exterior and conditioned-opening doors shall be furnished with the weatherseals needed to meet the specified air-infiltration limit: a bottom-bar astragal sealing to the floor, guide weatherstrip sealing the curtain edges, a hood baffle or header seal at the head, and, on insulated doors, interlock seals between slats.
9.1.2Seals shall be replaceable without removing the curtain.

10 Installation

10.1 Opening Verification

10.1.1The opening shall be verified before installation begins: width, height, plumb of the jambs, level of the head and sill, and the available headroom above the lintel and the sideroom at each jamb.
NOTE Headroom and sideroom are the clearances the coil and its brackets require; a coiling door cannot be installed in less than its required clearances, and the most common field conflict is a coil that does not fit the headroom because the door type was selected without checking the shop-drawing clearances against the as-built opening. (10.1.2)
10.1.3Where clearances are tight, a low-headroom configuration (tube motor or reduced-coil design) shall be selected at the submittal stage, not discovered at installation.

10.2 Anchorage

10.2.1Guides, brackets, and the operator shall be anchored to the structural substrate using the fasteners and embedment shown on the wind-load and listing drawings; anchorage shall develop the wind and counterbalance reactions.
10.2.2Where the door anchors to masonry, coordinate the anchor type and location with Unit Masonry; where it anchors to steel, coordinate with Structural Steel Framing.
10.2.3Anchorage into hollow masonry or to studs without solid blocking shall not be substituted for the listed anchorage on a fire-rated or wind-rated door.

10.3 Fire-Rated Door Installation

10.3.1For a fire-rated coiling door the wall opening, the guides, the hood, and the release mechanism shall all be installed to match the conditions of the NRTL listing.
10.3.2Where the head or jamb of a rated door interfaces with a rated wall assembly, coordinate the joint with Firestopping.

10.4 Adjustment

10.4.1After installation the curtain shall be cycled and the counterbalance adjusted so that a manual door moves with the specified effort and a powered door runs without binding, with the bottom bar seating squarely at the closed position.

11 Field Testing

11.1 Operational Test

11.1.1Every coiling door shall be cycled through its full travel and adjusted so that it opens and closes smoothly, the curtain tracks in the guides without binding, the counterbalance holds the curtain at intermediate positions on manual doors, and the bottom bar seats fully closed and level.
11.1.2Powered doors shall be tested for correct open, close, stop, and reversing function and for manual override operation.

11.2 UL 325 Entrapment-Protection Test

11.2.1For each powered door, the entrapment-protection devices shall be functionally tested: obstructing the closing curtain shall cause the door to stop and reverse (or stop, per the listed behavior), and disconnecting or faulting a monitored external device shall inhibit powered closing.
11.2.2Record the result for closeout.

11.3 Fire-Door Acceptance Drop Test

Required Field Testscheckbox
Operational cycle and counterbalance adjustment (all doors)
UL 325 entrapment-protection functional test (powered doors)
NFPA 80 acceptance drop test, two cycles with reset (fire-rated doors)
11.3.1Each fire-rated coiling door shall be acceptance-tested by the manufacturer's qualified representative or trained installer in accordance with NFPA 80.
11.3.2The door shall be released by each means of activation and dropped to the fully closed position, the average closing speed verified to be between 6 in./s and 24 in./s, and the bottom bar confirmed to seat closed.
11.3.3The door shall then be reset per the manufacturer's instructions and the drop test repeated to verify that the release reset correctly — the test is performed and the door reset a minimum of two times.
11.3.4The acceptance test record shall be provided at closeout.
11.3.5The Owner shall be informed in writing that NFPA 80 requires every fire-rated coiling door to be drop-tested and inspected at least annually by a qualified technician for the life of the building, regardless of how often the door is otherwise operated, and that the records of those tests must be retained.
NOTE This annual obligation is the single most overlooked item in fire-rated coiling-door ownership; the closeout package shall make it explicit. (11.3.6)

12 Warranty

12.1 Warranty Requirements

12.1.1The door manufacturer shall warrant the coiling door against defects in materials and workmanship for the period specified below from the date of substantial completion.
12.1.2The operator and its controls shall carry the operator manufacturer's warranty.
12.1.3Warranty service shall include the labor to adjust or replace warranted components.

12.2 Warranty Periods

Door Manufacturer Warranty Periodradio
1 year
2 years
5 years (springs and curtain)
Operator Warranty Periodradio
1 year
2 years
5 years

Edit this page