Smoke Control Systems

Revision 2 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 12, 2026 +7 −7

Fix cross-reference library prefix syncs/ -> sync/
Showing changes from Rev 1 to Rev 2 in Smoke Control Systems.
---
title: Smoke Control Systems
26 unchanged lines
- Passive smoke barriers, smoke partitions, and architectural opening protectives, governed by the architectural and life-safety documents, except where their leakage values are inputs to the smoke control design
- Fire suppression piping, specified in the fire suppression documents
- Fire alarm initiating and notification devices, specified in [[syncs/fire-alarm-systems]]
- General comfort air distribution, specified in [[syncs/hvac-fans]]
+- Fire alarm initiating and notification devices, specified in [[sync/fire-alarm-systems]]
+- General comfort air distribution, specified in [[sync/hvac-fans]]
## Related work is specified in [[syncs/hvac-fans]], [[syncs/louvers-and-dampers]], [[syncs/fire-alarm-systems]], [[syncs/building-automation-system]], and [[syncs/testing-adjusting-and-balancing]]. {note}
+## Related work is specified in [[sync/hvac-fans]], [[sync/louvers-and-dampers]], [[sync/fire-alarm-systems]], [[sync/building-automation-system]], and [[sync/testing-adjusting-and-balancing]]. {note}
# Definitions {toc}
328 unchanged lines
### Smoke exhaust fan motors and controls shall be connected to the emergency power supply system in accordance with NFPA 110.
### Fans and fan accessories common to comfort and smoke service shall additionally comply with [[syncs/hvac-fans]]. {note}
+### Fans and fan accessories common to comfort and smoke service shall additionally comply with [[sync/hvac-fans]]. {note}
```datasheet
67 unchanged lines
### Smoke damper actuators shall be electric where required to support the supervised, addressable control and position feedback required by the smoke control panel.
### Dampers, sleeves, and access provisions common to general HVAC service shall additionally comply with [[syncs/louvers-and-dampers]]. {note}
+### Dampers, sleeves, and access provisions common to general HVAC service shall additionally comply with [[sync/louvers-and-dampers]]. {note}
```datasheet
122 unchanged lines
### The division of the FSCS scope between the fire alarm installer and the mechanical controls installer shall be coordinated and assigned so that programming, wiring, and status interfaces are complete with no gaps. {note}
### Fire alarm initiation, detection, and interface devices that activate the smoke control system are specified in [[syncs/fire-alarm-systems]], and the smoke control interface with general building controls is coordinated with [[syncs/building-automation-system]]. {note}
+### Fire alarm initiation, detection, and interface devices that activate the smoke control system are specified in [[sync/fire-alarm-systems]], and the smoke control interface with general building controls is coordinated with [[sync/building-automation-system]]. {note}
```datasheet
108 unchanged lines
### Special inspection of the smoke control system shall be performed by a qualified agency in accordance with the adopted building code.
### Air balancing of smoke control airflows shall be coordinated with [[syncs/testing-adjusting-and-balancing]]. {note}
+### Air balancing of smoke control airflows shall be coordinated with [[sync/testing-adjusting-and-balancing]]. {note}
```datasheet
96 unchanged lines
- Spare indicating lamps / LEDs
```