Electrical Acceptance Testing
P1 batch 4: hazardous-location installations, document confidentiality and AI use, generator paralleling switchgear, interrupter switchgear, medium-voltage drives and metal-enclosed bus now owned; bare-text mentions re-pointed to the new standards
Showing changes from Rev 4
to Rev 5
in Electrical Acceptance Testing.
---
title: Electrical Acceptance Testing
…17 unchanged lines
- the short-circuit, coordination, and arc-flash studies, under [[sync/short-circuit-study]], [[sync/protective-coordination-study]], and [[sync/arc-flash-study]]; the tests under this standard verify that the installed settings match those studies and do not perform them
- factory tests, witnessed or certified, under the equipment standard for each product
−- the construction, ratings, and field test lists of the equipment itself, under [[sync/low-voltage-switchgear]], [[sync/medium-voltage-switchgear]], [[sync/low-voltage-switchboards]], [[sync/panelboards]], [[sync/motor-control-centers]], [[sync/combination-motor-starters]], [[sync/medium-voltage-transformers]], [[sync/low-voltage-dry-type-transformers]], [[sync/secondary-unit-substations]], [[sync/automatic-transfer-switches]], [[sync/generators]], and the other equipment standards named in this standard
+- the construction, ratings, and field test lists of the equipment itself, under [[sync/low-voltage-switchgear]], [[sync/medium-voltage-switchgear]], [[sync/metal-enclosed-interrupter-switchgear]], [[sync/generator-paralleling-switchgear]], [[sync/medium-voltage-bus-duct]], [[sync/medium-voltage-drives]], [[sync/low-voltage-switchboards]], [[sync/panelboards]], [[sync/motor-control-centers]], [[sync/combination-motor-starters]], [[sync/medium-voltage-transformers]], [[sync/low-voltage-dry-type-transformers]], [[sync/secondary-unit-substations]], [[sync/automatic-transfer-switches]], [[sync/generators]], and the other equipment standards named in this standard
- commissioning process management, functional performance testing, and systems integration testing, under [[sync/commissioning]]
- the facility's written electrical safety program, its energized work permits, and its lockout procedures, under [[sync/electrical-safety-program]]
…202 unchanged lines
- "Dry-type transformers rated 1000 V and below"
- "Medium-voltage switchgear"
+ - "Metal-enclosed interrupter switchgear"
- "Low-voltage switchgear"
- "Low-voltage switchboards"
- "Panelboards"
- "Motor control centers and enclosed motor controllers"
- "Enclosed switches and busway"
+ - "Metal-enclosed bus above 600 V"
- "Medium-voltage circuit breakers"
- "Low-voltage power circuit breakers and insulated-case circuit breakers"
…471 unchanged lines
## Where a test performed under this standard is later shown to have been performed with an uncalibrated instrument, at a voltage other than the one this standard assigns, or against a criterion other than the governing one, the testing organization shall repeat the test at no cost to the Owner, and where the equipment has since been energized, shall perform it at the next outage the Owner makes available.