1 Scope

NOTE This standard governs the signs a building must carry because the means-of-egress and accessibility provisions of the adopted code say so: what each sign reads, where it sits, and how its raised characters and Braille are made. The signs are non-illuminated, their messages are fixed by the code rather than chosen by the designer, and an inspector checks each one against the code text at the final inspection. (1.1)
NOTE The sign types in this set are the tactile exit signs at exit doors, the stairway identification and floor-level signs inside exit stairways, the identification, instruction, and directional signs that serve an area of refuge and an accessible means of egress, the elevator emergency-use sign and the hoistway floor designations, the occupant load posting, the NO EXIT sign, and the notice sign at a main exit door secured with a key-operated lock. (1.2)
NOTE The following are governed elsewhere and are outside this standard: (1.3)
  • exit signs of every illumination type, including photoluminescent and self-luminous signs, and luminous egress path markings with the ambient light that charges them, which are furnished under Emergency And Egress LightingEmergency and Egress LightingResolves to the current adopted revision.sync/emergency-and-egress-lighting
  • room and space identification signs, including the tactile restroom sign and its pictogram, wayfinding, regulatory and informational panels, dimensional letters, and the sign and message schedule for them, which are furnished under SignageSignageResolves to the current adopted revision.sync/signage
  • accessible entrance signs, accessible-route markers outside the building, and exit discharge signs on the site, which are furnished under Exterior SignageExterior SignageResolves to the current adopted revision.sync/exterior-signage
  • panic hardware, fire exit hardware, closers, electrified locking, and the release signage furnished with delayed egress and sensor-released locking, which are furnished under Door HardwareDoor HardwareResolves to the current adopted revision.sync/door-hardware
  • audible and visible fire alarm notification appliances, which are furnished under Fire Alarm SystemsFire Alarm SystemsResolves to the current adopted revision.sync/fire-alarm-systems
  • slip-resistant stair nosings, which are furnished under Metal Stairs And RailingsMetal Stairs and RailingsResolves to the current adopted revision.sync/metal-stairs-and-railings
  • pipe markers, duct labels, valve tags, and equipment nameplates, which are furnished under Mechanical IdentificationMechanical IdentificationResolves to the current adopted revision.sync/mechanical-identification and Plumbing Piping IdentificationPlumbing Piping IdentificationResolves to the current adopted revision.sync/plumbing-piping-identification
  • electrical equipment labels and arc-flash labels, which are furnished under Equipment LabelingElectrical Equipment LabelsResolves to the current adopted revision.sync/equipment-labeling
  • extinguisher identification furnished with the cabinet under Fire Extinguishers And CabinetsPortable Fire Extinguishers and CabinetsResolves to the current adopted revision.sync/fire-extinguishers-and-cabinets, and sprinkler riser and control-valve signs furnished under Common Work Results Fire SuppressionCommon Work Results for Fire SuppressionResolves to the current adopted revision.sync/common-work-results-fire-suppression
  • the two-way communication station itself at an area of refuge, and the workplace accident-prevention signs of OSHA 29 CFR 1910.145 and ANSI Z535, which no standard in this library covers
NOTE Three decisions in this standard are independent of one another and are made separately: the fabrication process and plate material that every raised-character sign shares, the form of each sign type where the code leaves the form open, and the mounting method. The message and the position of each sign are not decisions; they follow from the code. (1.4)
1.5 The sign types, the quantity of each, the message of each, and the location of each shall be as indicated on the life-safety plan and the sign schedule.
1.6 Where tactile room-identification signs are furnished under SignageSignageResolves to the current adopted revision.sync/signage on the same project, the signs under this standard shall match them in typeface, corner treatment, plate color, and character color, so that the tactile signs of the building read as one family.
1.7 The Contractor shall furnish the plate size, the mounting height, and the attachment of every sign to the trades that build the walls before the walls are closed, so that blocking is placed where a mechanically fastened sign needs it under Gypsum Board AssembliesGypsum Board AssembliesResolves to the current adopted revision.sync/gypsum-board-assemblies.

2 Referenced Standards

2.1 Materials, fabrication, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2 Where referenced standards conflict, the more stringent requirement shall govern unless the Architect directs otherwise in writing.
2.3 The edition of ICC A117.1 that governs is the edition Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code adopts by reference, and the 2010 ADA Standards for Accessible Design apply in parallel as federal law, so a sign is checked against both.
Standard Title
International Building Code Chapter 10, Means of Egress; Chapter 11, Accessibility; Chapter 30, Elevators and Conveying Systems
International Fire Code Chapter 10, Means of Egress
NFPA 101 Life Safety Code (Chapter 7, Means of Egress)
ICC A117.1 Accessible and Usable Buildings and Facilities (Chapter 7, Communication Elements and Features)
2010 ADA Standards for Accessible Design Americans with Disabilities Act Standards for Accessible Design (Sections 216 and 703)
ASME A17.1/CSA B44 Safety Code for Elevators and Escalators
NFPA 80 Standard for Fire Doors and Other Opening Protectives
ASTM D4802 Poly(Methyl Methacrylate) Acrylic Plastic Sheet
ASTM B209 Aluminum and Aluminum-Alloy Sheet and Plate
ASTM A666 Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar
ASTM E84 Surface Burning Characteristics of Building Materials
ASTM D1308 Effect of Household Chemicals on Clear and Pigmented Organic Finishes
NOTE The 2010 ADA Standards and ICC A117.1 agree on nearly every sign provision, and where they differ on a dimension the stricter of the two is the one that satisfies both; the differences are small enough that one sign design satisfies both standards when it is drawn to the stricter value at each point. (2.4)

3 Submittals

3.1 Action Submittals

3.1.1 The Contractor shall submit the following for review and shall not release signs for fabrication until the submittals have been returned:
  • A sign schedule listing every sign under this standard by mark, sign type, verbatim message including capitalization, plate size, plate material, fabrication process, color scheme, mounting method, and mounting height to the reference point ICC A117.1 uses, cross-referenced to the life-safety plan
  • Shop drawings for each sign type showing the plate, the raised character height and typeface, the Braille cell layout and its separation from the raised characters, the pictogram field where one is present, the edge treatment, and the mounting detail
  • Product data for the plate material, the photopolymer or raster system, the adhesive, and the fasteners, giving the fire performance of plastics, the light reflectance value of each color, and the finish
  • One full-size production sample of each tactile sign type showing the actual substrate, colors, raised characters, Braille, and finish
  • Color samples for every plate and character color, each labeled with its light reflectance value
Action Submittals Requiredcheckbox
☑ Sign schedule with mark, type, verbatim message, size, material, process, colors, mounting, and height
☑ Shop drawings for each sign type
☑ Product data for plate material, raised-copy system, adhesive, and fasteners
☑ Full-size production sample of each tactile sign type
☐ Color samples labeled with light reflectance values
NOTE The sign schedule is reviewed against the life-safety plan word for word, because a tactile exit sign whose message names the wrong door function, or a stairway sign that omits the terminus, is a code deficiency that no quality of fabrication cures. (3.1.2)
3.1.3 Where the Contractor proposes a process, material, or mounting differing from the datasheet selection, the proposal shall be identified as a deviation on the transmittal and shall state what is offered in place of each selected item.

3.2 Informational Submittals

3.2.1 The Contractor shall submit the following with or before the action submittals:
  • The fabricator's qualification statement required under Quality Assurance
  • The approved occupant load for each assembly room or space, as issued by the authority having jurisdiction, before the posting for that room is fabricated
  • The stairway designations, the floors each stairway serves, the roof-access condition, and the re-entry condition of each stairway, as confirmed against the life-safety plan before the stairway signs are fabricated
  • The elevator installer's confirmation of which elevator signs the elevator installation furnishes, where the datasheet assigns the hoistway floor designations to the elevator installation
Informational Submittals Requiredcheckbox
☑ Fabricator qualification statement
☑ Approved occupant load for each assembly room or space
☑ Stairway designation, floors served, roof-access, and re-entry confirmation
☐ Elevator installer's confirmation of signs furnished with the elevator

3.3 Closeout Submittals

3.3.1 The Contractor shall deliver the following at substantial completion:
  • A record sign schedule reflecting every field change to message, location, or mounting height
  • The mounting height and location verification record required under this standard
  • Maintenance data stating the cleaning agents the finish withstands, the adhesive and fastener used at each mounting condition, and the fabricator's part designation for each sign type so that a damaged sign can be reordered to match
  • The written manufacturer warranty and the written Contractor installation warranty
  • A signed receipt from the Owner for the spare signs delivered
Closeout Submittals Requiredcheckbox
☑ Record sign schedule
☑ Mounting height and location verification record
☑ Maintenance data with cleaning agents and reorder designations
☑ Manufacturer and Contractor warranties
☑ Spare sign receipt

4 Quality Assurance

4.1 Source of Supply

NOTE Raised characters and Braille from two fabricators differ in dot profile, stroke, and edge sharpness in ways a hand reads at once, and plates from two color lots read as two colors under the same light, which is why the signs of one building are held to one source wherever the project allows it. (4.1.1)
NOTE Holding the signs under this standard and the tactile room-identification signs under SignageSignageResolves to the current adopted revision.sync/signage to one fabricator makes every tactile sign in the building one family, at the cost of tying two packages to one supplier's lead time; holding only this standard's signs to one source keeps the packages independent and relies on the family-matching clause in Scope for the rest. Multiple fabricators are what a project with a long-lead or proprietary room-sign system buys, with the matching done by sample. (4.1.2)
4.1.3 The source of supply for the signs under this standard shall be as indicated in the datasheet.
Source of Supplyradio
○ One fabricator for every sign under this standard and every tactile room-identification sign on the project
● One fabricator for every sign under this standard
○ Multiple fabricators, with typeface, Braille profile, and colors matched by sample

4.2 Fabricator Qualifications

4.2.1 The fabricator shall have produced raised-character and Braille signs to ICC A117.1 Chapter 7 on not fewer than the number of completed projects indicated in the datasheet.
Fabricator Comparable Projectsrange
Not less than
projects
13510
4.2.2 The fabricator shall measure the raised character height, the stroke width, the Braille dot height and spacing, and the character-to-Braille separation on the production sample of each sign type with a gauge and shall report the measurements with the sample.
NOTE Braille that reads correctly is a matter of dot geometry to a few thousandths of an inch, and the only way to know a fabricator holds it is to measure a sample; a visual review of a photograph proves nothing about the dots. (4.2.3)

4.3 Approved Samples

4.3.1 The approved full-size sample of each sign type shall set the standard of quality for character edge, Braille dot form, color, and finish for every sign of that type.
4.3.2 A sign that departs visibly from its approved sample shall be replaced at the Contractor's expense.
4.3.3 Approved samples shall be retained on the site until the mounting height verification is complete, after which they shall be delivered to the Owner as part of the spare signs.

5 Environmental and Service Conditions

NOTE A conditioned interior corridor is where most of the signs under this standard are installed, and the plate materials and adhesives offered as the norm are rated for that service; an exit stairway in an unheated or unconditioned building, a loading dock, a parking structure, a natatorium, or a door that opens to the weather is a different service, and the clauses below raise the material at those locations without changing the selection for the rest of the building. (5.1)
5.2 Signs installed in an unconditioned space, a parking structure, or a location exposed to the weather shall be of a plate material, a raised-copy system, and an adhesive the fabricator rates for the temperature and moisture of that location, and plastic plates at those locations shall be ultraviolet-stabilized.
5.3 Signs installed in a natatorium, a food-processing area, or a wash-down area shall be of a plate material and fasteners that withstand the chlorinated or cleaning-agent atmosphere of that area, and aluminum plates at those locations shall be anodized or coated.
5.4 Signs installed where they can be struck, in a gymnasium, a corridor of a detention or correctional occupancy, a loading dock, or a parking structure, shall be of metal or of a plastic plate the fabricator rates as impact-resistant and shall be mechanically fastened with tamper-resistant fasteners regardless of the mounting method selected elsewhere in this standard.
5.5 Plastic sign plates shall have a flame spread index and a smoke-developed index, tested in accordance with ASTM E84, within the limits Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code sets for interior wall finish in the space where the sign is installed.
5.6 Sign finishes shall withstand the cleaning agents named in the maintenance data without loss of gloss, color change, or lifting of applied characters when tested in accordance with ASTM D1308.

6 Tactile Sign Construction

6.1 Raised Copy Fabrication Process

6.1.1 Every sign under this standard that carries raised characters and Braille shall be fabricated by the process indicated in the datasheet.
Raised Copy Fabrication Processselect
Photopolymer, raised characters and Braille integral with the face sheet
Applied raised characters with raster-bead Braille in an acrylic plate
Applied raised characters with raster-bead Braille in a metal plate
Cast metal with integral raised characters and Braille
Injection-molded or thermoformed plastic with integral raised characters and Braille
NOTE No process is the norm across projects, because the choice turns on sign count, on the plate material the building's sign family uses, and on the service the sign sees. Photopolymer forms the characters and the dots in one exposure of a light-sensitive sheet, so the copy cannot delaminate and the Braille geometry is as accurate as the artwork, and it is the process of most high-count projects; the face sheet is a plastic laminated to its backer, so it is a conditioned-interior product unless the fabricator rates it otherwise. Raster-bead Braille sets a spherical bead into a drilled hole, with the characters cut and applied separately, so the plate can be any machinable material, including the metals photopolymer cannot be, and the bead profile is uniform; an applied character can be pried off, which is why raster signs in abuse-prone locations are specified with the characters pinned as well as bonded. Cast metal gives the most durable sign and the one that survives weather and abuse, at the highest cost and the longest lead time, and its Braille dots are only as round as the pattern and the casting allow. Molded plastic is the lowest cost at high volume and is limited to the sign formats the fabricator tools. (6.1.2)
6.1.3 Raised characters that are applied rather than integral shall be bonded to the plate with an adhesive the fabricator rates for the plate material.
6.1.4 Applied raised characters shall be pinned as well as bonded where the sign is installed in an abuse-prone location named in this standard.

6.2 Plate Material and Thickness

6.2.1 The plate material of every sign under this standard shall be as indicated in the datasheet.
Sign Plate Materialselect
Acrylic sheet
Phenolic or melamine composite sheet
Aluminum sheet or plate
Stainless steel sheet
Bronze or brass plate
NOTE Acrylic to ASTM D4802 is the plate of most interior tactile signs, because it takes paint, subsurface color, and photopolymer lamination equally well and is the least costly to fabricate; phenolic and melamine composites resist impact and moisture better than acrylic and are the plate of choice in schools and transit; aluminum to ASTM B209 is the plate of stairway signs and of exterior-door signs that must survive weather, and is anodized or painted; stainless steel to ASTM A666 is specified where the sign family is stainless or where corrosion and abuse both apply; bronze and brass are specified where the building's hardware and signage finish is bronze, at the highest material cost. The plate is chosen to match the building's sign family first and the service second, which is why the field carries no default. (6.2.2)
6.2.3 The plate thickness of every sign under this standard shall be not less than the thickness indicated in the datasheet.
Plate Thicknessrange
Not less than
in
0.06250.1250.18750.250.3750.5
NOTE A plate of 1/8 in is the thickness most interior tactile signs are made to in every material, which is why it is the default; a thinner plate is a decal-like applique that bows on an uneven wall, and a thicker plate is bought where the sign family calls for a dimensional edge, where a metal plate must resist denting, or where the sign is edge-exposed to abuse. (6.2.4)
6.2.5 The edges of every plate shall be finished smooth with no sharp corner, and the corner treatment, square or radiused, shall match the approved sample.

6.3 Characters, Braille, and Contrast

6.3.1 Raised characters and Braille on every sign under this standard shall conform to ICC A117.1 Chapter 7 and to Section 703 of the 2010 ADA Standards for character case, style, proportion, height, stroke, spacing, Braille grade, dot form, dot dimensions, and the separation of the Braille from the characters and from the sign edge.
NOTE The character height, the stroke, and the Braille dimensions are fixed by the accessibility standard and are not selections, which is why this standard cites the standard rather than restating the values; the fabricator draws the sign to the edition in force and the sample is measured against it. (6.3.2)
6.3.3 Braille shall be contracted Braille with domed or rounded dots, and the Braille translation shall be checked by a transcriber or a translation tool certified for contracted Braille before the artwork is released.
NOTE A Braille cell that is dimensionally perfect and reads the wrong word is the deficiency a sighted reviewer cannot see; the translation check is what catches an uncontracted word, a dropped indicator, or a number sign, and it is a line item in the fabrication sequence because of that. (6.3.4)
6.3.5 Visual characters, where separate from the raised characters, shall conform to ICC A117.1 for case, style, height for the viewing distance, stroke, and spacing.
6.3.6 Whether the raised characters on a tactile sign also serve as the sign's visual characters shall be as indicated in the datasheet.
Visual Characters on Tactile Signsradio
● Raised characters serve as the visual characters
○ Separate visual characters duplicate the raised copy
NOTE A single set of raised characters that meets the visual requirements as well is the construction of most tactile signs, which is why it is the default; a separate visual set is used where the sign family wants a larger or lowercase visual legend above the tactile line, and it lengthens the plate. (6.3.7)
6.3.8 Characters, Braille, and their background shall have a non-glare finish, and the characters and Braille shall contrast with their background, either light on a dark field or dark on a light field, as indicated in the datasheet.
Character and Field Contrast Orientationradio
○ Light characters on a dark field
○ Dark characters on a light field
NOTE The orientation follows the building's sign family and its wall colors, and neither reads better in the abstract, so the field carries no default; a light field shows handling soil sooner, and a dark field shows scratches in a glossy plastic sooner, which is why the finish is non-glare in both cases. (6.3.9)
6.3.10 The difference in light reflectance value between the characters and Braille and their background field shall be not less than the value indicated in the datasheet.
Light Reflectance Value Differencerange
Not less than
% LRV
5060708090
6.3.12 The typeface and the plate and character colors of the sign family shall be as indicated in the datasheet.
Sign Family Typeface and Colorstext
Enter value...

6.4 Sign Mounting Method

6.4.1 The mounting method for the signs under this standard shall be as indicated in the datasheet, except where a clause of this standard requires mechanical fastening at a location.
Sign Mounting Methodselect
High-bond foam tape with a perimeter bead of silicone adhesive
Exposed mechanical fasteners through the plate face
Concealed mechanical fasteners on a back bracket or standoffs
High-bond foam tape and silicone adhesive with tamper-resistant mechanical fasteners
NOTE Tape and silicone is the mounting of most interior tactile signs on painted gypsum board, because it needs no blocking, leaves no hole when a sign is relocated, and holds a plate of the default thickness for the life of the finish, which is why it is the default; it fails on a textured, dusty, or freshly painted wall and on masonry, and it does not resist a deliberate pull. Exposed fasteners hold on any substrate and are the mounting of stairway signs on masonry and concrete, at the cost of a visible fastener head that the sign family might not accept. Concealed fasteners on a bracket or standoffs give the dimensional look some sign families call for and resist a casual pull, and need blocking in a framed wall. Tape with tamper-resistant fasteners is the mounting in abuse-prone locations and in any building whose Owner has lost signs to theft. (6.4.2)
6.4.3 Signs mounted on glass shall be mounted with an adhesive the fabricator rates for glass, with a backer or a second face so that the adhesive is not visible through the glass, and no fastener shall be drilled through a glass lite.
6.4.4 Fasteners at a sign mounted on masonry, concrete, or tile shall be set in anchors rated for the substrate, and fasteners at a sign mounted on a framed wall shall engage blocking or a backing plate rather than the wall board alone.

7 Tactile Exit Signs

NOTE A tactile exit sign is the sign that lets a person who cannot see the illuminated exit sign find the exit by hand; it is required at the doors the adopted code names and is a separate sign from the illuminated exit sign, which is furnished under Emergency And Egress LightingEmergency and Egress LightingResolves to the current adopted revision.sync/emergency-and-egress-lighting and which the tactile sign never replaces. (7.1)
7.2 A tactile exit sign with raised characters and Braille shall be provided at each door the adopted code requires one at, including the doors to exit stairways, exit ramps, exit passageways, and the exit discharge, in accordance with the means-of-egress provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code.
7.3 The raised-character message of each tactile exit sign shall be the message Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code assigns to the function of the door it marks, naming the exit, the exit stair with the direction of travel, the exit ramp, the exit passageway, or the exit route as that function requires, and no other words shall be added to the raised line.
NOTE The code assigns the message by what lies beyond the door, so the message is read from the life-safety plan and not from the door's room name; a door into an exit stairway reads as the stair with its direction, a door from an exit passageway to the outside reads as the exit, and a door along a corridor that is itself the exit route reads as the route. (7.4)
7.5 Where a tactile exit sign and a tactile room-identification sign furnished under SignageSignageResolves to the current adopted revision.sync/signage both fall at one door, the two shall be combined on one plate or stacked on the latch side so that each remains within the mounting height range the accessibility standard allows, and the arrangement shall be shown on the shop drawings.

8 Stairway Identification Signs

8.1 Whether stairway identification signs are provided shall be as indicated in the datasheet.
Stairway Identification Signsselect
Not required by the adopted code and not provided
Provided at each floor landing of each interior exit stairway the adopted code requires them in
Provided at each floor landing of every interior exit stairway regardless of the number of stories
Derived — the number of stories each interior exit stairway connects and the stairway signage provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code (by default)
NOTE The International Building Code requires the sign in stairways connecting more than a stated number of stories, and NFPA 101 sets its own threshold, so whether a given stairway needs the sign follows from the story count and the governing code; an Owner extends them to every stairway where firefighters, security staff, or a large population benefit from knowing where every stair goes. (8.2)
8.3 Each stairway identification sign shall state the stairway designation, the floor level of the landing, the upper and lower terminus of the stairway, whether the stairway provides roof access, and the level of exit discharge, as the stairway signage provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code require, and the stairway designation shall match the one on the life-safety plan.
8.4 Where a stairway door is locked from the stair side so that re-entry to the floor is prevented, the sign the adopted code requires on the stair side of that door, stating the re-entry condition and the nearest floors with re-entry, shall be provided at that door.
NOTE A sign that reads only the stair name does not satisfy either code; the terminus and the roof-access statement are what let a firefighter decide whether this stair reaches the fire floor and the roof, and the floor level is what lets an occupant in smoke know how far down the discharge is. A sign missing any element is replaced at inspection, which is why the designations, floors served, roof access, and re-entry condition are confirmed in writing before fabrication. (8.5)
8.6 The floor-level identification on each landing shall be tactile, with raised characters and Braille conforming to the Tactile Sign Construction section of this standard, and shall be located where the accessibility provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code and ICC A117.1 require it.
8.7 The format of the stairway identification sign shall be as indicated in the datasheet.
Stairway Identification Sign Formatradio
○ One plate carrying the visual stairway statement and the tactile floor level
○ Separate visual stairway sign and tactile floor-level sign
NOTE One plate puts the whole statement where a reader finds it in one place and is one sign to mount per landing; two plates let the visual sign be the large aluminum plate the stair side of the door needs and the tactile sign the smaller plate at the accessible mounting height beside it, which is how the two heights the codes name are both met when the door and the wall space do not allow one plate to satisfy both. The choice follows from the wall space at the landing and the sign family, so the field carries no default. (8.8)
8.9 The plate material of the stairway identification signs shall be as indicated in the datasheet.
Stairway Identification Sign Plate Materialselect
Acrylic sheet
Phenolic or melamine composite sheet
Aluminum sheet or plate
Stainless steel sheet
Photopolymer-faced aluminum
NOTE The stairway sign is the largest plate under this standard and hangs in a stair that is often unconditioned, lit at the code minimum, and struck by whatever is carried up it, so its material is chosen apart from the rest of the family: acrylic matches the interior signs and is the lowest cost; phenolic and melamine composites take the abuse of a school or transit stair; aluminum is the plate of most stairway signs because it is rigid at the size, takes weather, and holds painted copy; stainless steel is specified where the stair finish is stainless or the atmosphere is corrosive; photopolymer-faced aluminum carries integral tactile copy on a plate that does not bow. No material is the norm, because the choice follows from the stair's service and the family. (8.10)
8.11 The visual characters of the stairway statement shall be of the height and stroke the stairway signage provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code require, in a contrasting color, and the sign shall be mounted at the height and position those provisions require on the stair side of the door at each landing.
8.12 Where an exit stairway serves as the required means of egress from a roof, the roof-level sign shall state the roof access, and where a stairway continues below the level of exit discharge, the sign at the discharge level shall direct occupants to the exit so that they do not continue downward.

9 Area of Refuge and Accessible Means of Egress Signs

9.1 Whether the sign set for areas of refuge and the accessible means of egress is provided shall be as indicated in the datasheet.
Area of Refuge and Accessible Means of Egress Signsselect
Not provided, no area of refuge or inaccessible exit in the building
Identification, instruction, and directional signs at each area of refuge and each exit that is not an accessible means of egress
Derived — the accessible means of egress design on the life-safety plan and the area of refuge provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code (by default)
NOTE An area of refuge exists only where the life-safety plan creates one, and in a fully sprinklered building the code often lets the exit stairway or the elevator lobby serve without one, so the sign set follows from the plan rather than from a preference; where no area of refuge exists and every exit is accessible, no sign in this section is required. (9.2)
9.3 Each area of refuge shall be identified by a sign bearing the International Symbol of Accessibility and the words the adopted code prescribes for an area of refuge, in accordance with the area of refuge signage provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code, with raised characters and Braille where those provisions or ICC A117.1 require them.
9.4 Directional signs bearing the International Symbol of Accessibility shall be provided at each exit door and along each exit access that does not itself provide an accessible means of egress, indicating the direction to the nearest area of refuge or accessible means of egress, where Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code requires them.
9.5 At each area of refuge provided with a two-way communication station, an instruction sign shall be posted adjacent to the station stating how to summon assistance, how the response is given, and the written identification of the location, as the two-way communication provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code require.
9.6 The Contractor shall confirm with the installer of the two-way communication station, which is not furnished under this standard, whether its faceplate carries the instruction legend before the instruction sign is fabricated.
9.7 The format of the instruction sign at each two-way communication station shall be as indicated in the datasheet.
Area of Refuge Instruction Sign Formatradio
○ Separate instruction plate mounted adjacent to the communication station
○ Instruction legend integral to the communication station faceplate
○ Combined identification and instruction plate at the communication station
NOTE A separate plate is fabricated with the rest of the signs and placed wherever the station sits, so it survives a change of station supplier; a legend on the station faceplate comes from the station's installer and leaves nothing for this standard to furnish at that location but the identification sign; a combined plate puts the area of refuge identification and the instructions on one sign at the station, which fits a small refuge where the station is beside the door. The choice follows from who furnishes the station and when it is known, so the field carries no default. (9.8)
9.9 Where an exit that is not an accessible means of egress leads occupants to a location from which no accessible route continues, the sign the adopted code requires at that exit, stating that the exit is not accessible and directing to the accessible means of egress, shall be provided.

10 Elevator Signs

10.1 A sign reading that elevators are not to be used in a fire emergency and directing occupants to the exit stairs, in the pictorial form ASME A17.1/CSA B44 prescribes, shall be provided at each elevator landing call station on every floor, in accordance with the elevator provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code.
NOTE The elevator emergency-use sign is a life-safety sign with a prescribed pictograph and is specified here rather than left to the elevator installation because the elevator contract commonly stops at the hoistway entrance and the sign hangs on the wall beside the call station; where the elevator installation furnishes it, the sign under this standard is omitted at that location and the record schedule says so. (10.2)
10.3 Where an elevator is designed as an occupant evacuation elevator or as a fire service access elevator, the additional lobby signs the adopted code requires for that elevator shall be provided, with the messages those provisions prescribe.
10.4 The hoistway entrance at each landing shall carry the floor designation in raised characters and Braille on both jambs, at the height and position ICC A117.1 and the 2010 ADA Standards require, and the furnisher of those designations shall be as indicated in the datasheet.
Hoistway Jamb Floor Designations Furnished Byradio
○ This standard, as part of the building sign family
○ The elevator installation
NOTE The jamb designations are furnished either way, and the choice is whether they match the building's signs or the elevator manufacturer's standard plates; furnishing them under this standard makes every raised-character sign on a floor one family and requires the elevator installer to receive and mount them or to leave the jambs clear, while leaving them with the elevator puts them in the elevator installer's hands with no coordination but no family match. Neither is the norm, so the field carries no default. (10.5)
10.6 Where the hoistway jamb designations are furnished under this standard, the Contractor shall deliver them to the elevator installer before the hoistway entrances are set, together with the mounting template, and shall confirm in writing that the elevator installation will not furnish a duplicate set.

11 Occupant Load Posting

11.1 In each assembly room or space the adopted code requires a posting in, the approved occupant load shall be posted in a conspicuous place near the main exit or exit access doorway of the room, in accordance with the occupant load provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code, and the posting shall be legible, permanent, and maintained.
NOTE The occupant load on the posting is the value the authority having jurisdiction approves, and it is not computed by the Contractor or the fabricator; the posting is fabricated after that value is issued, and where the certificate of occupancy is the instrument that issues it, the holder is installed and the insert follows. (11.2)
11.3 The form of the occupant load posting shall be as indicated in the datasheet.
Occupant Load Posting Formradio
○ Permanent plaque with the approved occupant load engraved or printed on it
○ Frame holder receiving a printed insert
NOTE A permanent plaque matches the building's sign family and cannot be swapped for a false value, but a change of use or a re-approval means a new plaque; a frame holder receives the card the authority issues and is updated by replacing the insert, at the cost of an insert that can be removed or faded. The choice follows from how the authority having jurisdiction issues the value and how often the Owner expects it to change, so the field carries no default. (11.4)
11.5 Where a frame holder is selected, the holder shall be sized to receive the card or insert the authority having jurisdiction issues, shall hold the insert behind a clear rigid face, and shall be mounted as indicated in the datasheet.
Occupant Load Frame Mountingradio
● Surface-mounted
○ Recessed into the wall
NOTE A surface-mounted holder is the construction of most postings and needs no wall opening, which is why it is the default; a recessed holder is specified where the sign family is flush or where a projecting frame beside a door would be struck, and it needs a framed opening and, in a rated wall, a listed treatment under Fire Rated Wall And Floor AssembliesFire-Resistance-Rated AssembliesResolves to the current adopted revision.sync/fire-rated-wall-and-floor-assemblies. (11.6)
11.7 Where the room is also provided with the occupant load statement on a tactile room-identification sign under SignageSignageResolves to the current adopted revision.sync/signage, the posting under this standard is still required, because the code posting is a separate instrument that the authority having jurisdiction inspects and updates.

12 Egress Door Notice Signs

12.1 NO EXIT Signs

12.1.1 The policy for NO EXIT signs shall be as indicated in the datasheet.
NO EXIT Sign Policyselect
Not provided
At each door, passage, and stairway NFPA 101 requires one at
At every door, passage, and stairway that could be mistaken for an exit, whether or not the adopted code requires it
Derived — whether NFPA 101 is in force under Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code and the doors, passages, and stairways the life-safety plan marks as likely to be mistaken for an exit (by default)
NOTE NFPA 101 requires a NO EXIT sign at any door, passage, or stairway that is neither an exit nor a way to one and that could be mistaken for one; the International Building Code has no such requirement, so under that code alone the sign is an Owner's choice. Storage, mechanical, and electrical room doors that open onto a corridor near an exit are the doors most often mistaken, and the sign at them is inexpensive and prevents the dead-end search that costs time in an evacuation, which is why many Owners provide them under either code. (12.1.2)
12.1.3 Each NO EXIT sign shall read as NFPA 101 prescribes, with the word NO in the larger letters and the word EXIT below it in the smaller letters that code names, and the sign shall carry no other message.
12.1.4 NO EXIT signs shall be mounted on or adjacent to the door, passage, or stairway they mark, at a height readable from the approach, and a NO EXIT sign shall not be placed where it could be read as marking an exit door.

12.2 Key-Locked Main Exit Door Sign

12.2.1 The hardware schedule under Door HardwareDoor HardwareResolves to the current adopted revision.sync/door-hardware identifies the main exit doors fitted with a key-operated lock.
12.2.2 At each main exit door fitted with a key-operated lock as the adopted code permits for the occupancy, a durable sign reading that the door is to remain unlocked when the building is occupied shall be provided on or adjacent to the door, in the letters Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code prescribes, and the sign shall be visible from the egress side.
NOTE The key-operated main exit lock is a code exception that trades hardware for a sign and an operating rule, so the sign is a condition of the lock rather than an accessory to it; where the sign is missing, the lock is a violation, which is why its presence is checked against the hardware schedule before the doors are hung. (12.2.3)
12.2.4 The construction of the key-locked main exit door sign and of each NO EXIT sign shall be as indicated in the datasheet.
Egress Door Notice Sign Constructionradio
○ Rigid plate with applied or engraved copy
○ Adhesive vinyl applied to the door face or the glazing
○ Engraved laminate plate
NOTE A rigid plate matches the sign family and is mounted to the wall or the door with the mounting selected under this standard; adhesive vinyl is the construction of most notices at storefront entrances, where it goes on the glass and no plate would sit, and it is the construction a fire door accepts without a fastener; an engraved laminate plate is the lowest cost rigid sign and is the construction of most NO EXIT signs on back-of-house doors. The choice follows from the door type and the sign family, so the field carries no default. (12.2.5)

12.3 Signs on Fire Door Assemblies

12.3.1 A sign attached to a fire door leaf shall be attached with adhesive and shall not exceed the area NFPA 80 permits for a sign on a fire door, and no screw, bolt, or other fastener shall be driven into a labeled leaf or frame for a sign.
12.3.2 A sign on a fire door shall not cover the fire door label, the vision panel, or any hardware, and a sign that would exceed the permitted area shall be mounted on the wall adjacent to the door instead.
NOTE NFPA 80 permits a sign on a fire door only within a stated fraction of the door face and only by adhesive, because a screw hole is a field modification of a labeled assembly and a large plate changes how the leaf behaves in a fire; the restriction is the reason a NO EXIT sign or a notice sign at a rated door is a small adhesive sign or a wall-mounted plate rather than a plate screwed to the leaf. (12.3.3)

13 Installation

13.1 Mounting Location and Height

13.1.1 Each tactile sign shall be mounted at the height to the baseline of the raised characters, on the latch side of the door, within the clear floor space, and clear of the door swing, as ICC A117.1 Chapter 7 and the accessibility provisions of Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code require, and the installer shall measure every sign to the reference point the standard uses before releasing it.
13.1.2 Where there is no wall space on the latch side of a single door, or at a pair with no inactive leaf, the sign shall be mounted where the accessibility standard directs for that condition, on the right-hand side of the opening or on the nearest adjacent wall, and the position shall be shown on the shop drawings.
NOTE Latch-side mounting is the single most common field error on tactile signs, because a crew centers the sign on the door or mounts it on the push side where the wall is open; both are deficiencies that require relocation and a patched wall, which is why the position is laid out and checked before the adhesive is set. (13.1.3)
13.1.4 The Contractor shall lay out the position of each tactile sign against the door swing, the stops and holders, the casework, and the wall-mounted equipment at the opening before mounting, so that no leaf in its open position, no stop, and no equipment obstructs the sign or the clear floor space in front of it.
13.1.5 Where a wall-mounted item at an opening would obstruct a tactile sign in its code-required position, the Contractor shall report the conflict to the Architect before mounting either item, and shall not relocate the sign out of its code-required position to resolve it.
13.1.6 Signs other than tactile signs shall be mounted at the height and position the provision that requires each sign prescribes, and where that provision prescribes none, at a height readable from the approach and as indicated on the sign schedule.

13.2 Attachment to Walls, Doors, and Glass

13.2.1 Surfaces receiving adhesive-mounted signs shall be clean, dry, free of dust and release agents, and painted finishes shall have cured for the period the adhesive manufacturer requires before a sign is applied.
13.2.2 Adhesive-mounted signs shall be pressed to the wall for the dwell time the tape manufacturer requires and shall not be disturbed until the silicone bead has cured.
NOTE A tape bond made to a wall painted the same week, or to a textured or dusty surface, lets go within the first year, usually in summer, and the sign is found on the floor; the cure period and the surface condition are the whole of the adhesive's performance. (13.2.3)
13.2.4 Mechanically fastened signs shall be fastened with the fasteners and anchors the fabricator provides for the substrate, driven through the holes the fabricator drills, and no fastener shall be driven through raised copy or Braille.
13.2.5 A sign mounted on a fire-resistance-rated wall shall be mounted without reducing the rating of the assembly, and a recessed holder in a rated wall shall be installed in a listed treatment under Fire Rated Wall And Floor AssembliesFire-Resistance-Rated AssembliesResolves to the current adopted revision.sync/fire-rated-wall-and-floor-assemblies.
13.2.6 Signs shall be installed plumb and level, with the raised characters horizontal.
13.2.7 A sign installed out of plumb by more than the tolerance stated on the approved shop drawings shall be reset at the Contractor's expense.

13.3 Field Verification

13.3.1 After installation, the Contractor shall verify the mounting height, the latch-side position, the clear floor space, and the message of the signs under this standard against the record sign schedule and ICC A117.1, and shall record each verified sign by mark.
13.3.2 The share of the installed tactile signs verified by measurement shall be not less than the percentage indicated in the datasheet, and the signs measured shall include every tactile exit sign and every tactile floor-level sign.
Tactile Signs Verified by Measurementrange
Not less than
% of installed tactile signs
102550100
NOTE Measuring every tactile sign is the practice on most projects, because the signs are few relative to the building and a single sign out of range is a citation at the final accessibility inspection, which is why 100 percent is the default; a sample is accepted on a large repetitive building where the installer's first floors have verified clean and the remaining floors repeat them. (13.3.3)
13.3.4 A sign found out of position or out of height shall be relocated at the Contractor's expense, the wall shall be patched and finished to match, and the sign shall be re-verified and the record corrected.
13.3.5 The verification record shall be delivered as a closeout submittal and shall be the baseline the Owner's accessibility consultant or the authority having jurisdiction compares against at inspection.

14 Delivery, Storage, and Handling

14.1 Signs shall be delivered in the fabricator's protective packaging, each sign labeled with its mark from the sign schedule, and shall be inspected on receipt for damage to raised copy, Braille, and finish.
14.2 Signs shall be stored indoors, flat or on edge as the fabricator directs, within the temperature range the fabricator states for the plate material and the adhesive, and protected from moisture, abrasion, and sunlight until installation.
14.3 Tactile signs shall be handled by their edges, and a sign whose raised characters, Braille dots, or finish are scratched, dented, lifted, or soiled beyond cleaning shall not be installed.
14.4 Adhesive tape and silicone shall be stored within the shelf life and temperature range their manufacturers state, and tape past its shelf life shall not be used.
NOTE Tactile signs are made to order and carry a lead time of several weeks for standard formats and longer for cast metal and custom families, and the stairway and occupant load signs cannot be fabricated until their content is confirmed; the submittal and procurement schedule allows for the confirmation steps this standard requires so that sign installation does not hold the final inspection. (14.5)

15 Warranty

15.1 The fabricator shall warrant every sign under this standard against delamination of the face sheet, lifting or loss of applied characters or Braille beads, fading or color change beyond the approved sample, and corrosion of metal plates, for the period indicated in the datasheet, measured from the date of substantial completion.
Sign Warranty Periodrange
Not less than
years
123510
NOTE A one-year warranty is the general-conditions minimum and is what a laminate or vinyl sign commonly carries; a photopolymer or raster acrylic sign is commonly warranted for three to five years against delamination and lifting, and a cast metal sign for five to ten years against corrosion; no period is the norm across the materials this standard admits, so the field carries no default and the period is set to the process and plate selected. (15.2)
15.3 Where the contract documents state a longer warranty period than the datasheet, the longer period shall govern.
15.4 The Contractor shall warrant the installation, including the adhesion of every adhesive-mounted sign, the anchorage of every fastened sign, and the position and height of every tactile sign, for the project warranty period.
15.5 A repair or replacement performed under this warranty shall itself be warranted for a full new term equal to the original period from the date the repair is completed, or for the remainder of the original period, whichever ends later.

16 Spare Parts

16.1 The Contractor shall deliver spare signs of each tactile sign type under this standard, in the quantity indicated in the datasheet as a percentage of the installed count of each type, and shall obtain a signed receipt for them.
Spare Signs Furnishedrange
% of installed count of each sign type
251025
NOTE A spare quantity is sized to the installed count and to how fast the Owner can reorder a matching sign, so no quantity is the norm and the field carries no default; a zero records that the Owner reorders on damage and accepts the lead time, and a spare set lets a stolen or damaged tactile exit sign be replaced the same day so that the opening is not out of compliance until the fabricator ships. (16.2)
16.3 Where a frame holder is selected for the occupant load posting, the Contractor shall deliver blank inserts for each holder in the quantity indicated in the datasheet.
Spare Occupant Load Inserts per Holderrange
inserts
12510
NOTE Two blank inserts per holder is what most Owners accept, enough to replace a faded card and to post a re-approved value once without a reorder, which is why it is the default; a venue whose approved load changes by event configuration carries more. (16.4)
16.5 Spare signs shall be of the same fabricator, process, plate material, and colors as the installed signs, shall be delivered in the fabricator's packaging, and shall be labeled with the sign type and message they duplicate.