SynC · SynC Standards
Electrical Equipment Labels
Contents
- 1Scope
- 2Referenced Standards
- 3Submittals
- 3.1Action Submittals
- 3.2Closeout Submittals
- 4Quality Assurance
- 4.1Label Product Listing
- 4.2Fabricator and Installer
- 4.3Coordination with the Studies
- 5Environmental and Service Conditions
- 6Nameplate Material and Construction
- 6.1Nameplate Material
- 6.2Nameplate Colors
- 6.3Character Heights and Lettering
- 6.4Nameplate Attachment
- 7Equipment Identification Nameplates
- 7.1Nameplate Content
- 7.2Disconnecting Means Identification
- 8Circuit Directories
- 9Safety Signs and Field Markings
- 9.1Sign Format and Stock
- 9.2Signs Required on Equipment
- 10Arc-Flash Warning Labels
- 10.1Label Product
- 10.2Interim Labeling and Replacement
- 10.3Label Location
- 11Available Fault Current Marking
- 12Emergency and Standby System Equipment Marking
- 13Installation
- 13.1Sequence
- 13.2Mounting Position
- 14Delivery, Storage, and Handling
- 15Warranty
- 16Spare Parts
Download
Build a datasheet from this standard
Start a project with this standard already attached — one click, no setup.
Use in a project
1 Scope
NOTE This standard governs what is fastened or adhered to the outside of an electrical enclosure after it arrives on site: the nameplate that names the equipment and says where it is fed from, the nameplate on each device and compartment inside a lineup, the circuit directory in a panelboard door, the signs NFPA 70 requires on the equipment itself, the arc-flash warning label as a printed product, and the available fault current marking. It settles the material, the colors, the character heights, the attachment and the installation of every one of them, so that each equipment standard can require a label and point here for how it is made. (1.1)
NOTE Three documents feed the labels under this standard and none of them is written here. The arc-flash label carries the values, the method, the operating states and the signal word that the label schedule of Arc Flash StudyArc-Flash StudyResolves to the current adopted revision.sync/arc-flash-study states for each bus; this standard governs the stock it is printed on, its size, its attachment and where it is fixed. The available fault current marking carries the value and the date Short Circuit StudyShort-Circuit StudyResolves to the current adopted revision.sync/short-circuit-study states. The designation and the source on every nameplate come from the one-line diagram. A label is only as correct as the document behind it, and a label printed from a draft is replaced when the document is final. (1.3)
NOTE The following are governed elsewhere and are outside this standard: (1.4)
- the marking of conductors, cables, raceways, box covers and underground runs, including the posted identification legend, which is governed by Electrical IdentificationWiring System IdentificationResolves to the current adopted revision.sync/electrical-identification
- the factory nameplate and the ratings, listing and warning markings the manufacturer applies to each product, which each product standard governs and which no field label covers or replaces
- the content of the arc-flash label, its method, its signal word, the operating states it reports and the label schedule it is printed from, which Arc Flash StudyArc-Flash StudyResolves to the current adopted revision.sync/arc-flash-study governs
- the available fault current value, its date and its re-study triggers, which Short Circuit StudyShort-Circuit StudyResolves to the current adopted revision.sync/short-circuit-study governs
- which disconnects at a service are marked, how they are grouped and the wording NFPA 70 Article 230 gives them, which Electrical Service EntranceElectrical Service EntranceResolves to the current adopted revision.sync/electrical-service-entrance governs
- the identification tags on medium-voltage cable, which Medium Voltage CablesMedium-Voltage CablesResolves to the current adopted revision.sync/medium-voltage-cables governs
- telecommunications labels and records under ANSI/TIA-606, which Structured CablingStructured Cabling SystemsResolves to the current adopted revision.sync/structured-cabling and Telecommunications Rooms And PathwaysTelecommunications Rooms and PathwaysResolves to the current adopted revision.sync/telecommunications-rooms-and-pathways govern
- the labels on temporary construction power equipment, which Temporary Facilities And ControlsTemporary Facilities and ControlsResolves to the current adopted revision.sync/temporary-facilities-and-controls governs
- the marking of the branch panelboards and feeders of a healthcare essential electrical system, which Healthcare Essential Electrical SystemsHealthcare Essential Electrical SystemsResolves to the current adopted revision.sync/healthcare-essential-electrical-systems governs, with the nameplate made under this standard
- the arc-flash risk assessment program, the energized work permit and the re-labeling cycle the Owner runs after turnover, which Electrical Safety ProgramElectrical Safety ProgramResolves to the current adopted revision.sync/electrical-safety-program governs
- pipe markers, valve tags and the nameplates on mechanical equipment, which Mechanical IdentificationMechanical IdentificationResolves to the current adopted revision.sync/mechanical-identification and Plumbing Piping IdentificationPlumbing Piping IdentificationResolves to the current adopted revision.sync/plumbing-piping-identification govern
- the signs on the door of an electrical room and the egress and accessibility signage of the building, which Electrical RoomsElectrical RoomsResolves to the current adopted revision.sync/electrical-rooms and Signage And Egress MarkingsCode-Required Signage and Egress MarkingsResolves to the current adopted revision.sync/signage-and-egress-markings govern
NOTE The decisions the engineer makes under this standard are few and independent of one another: the nameplate material and its colors, the character heights, the attachment method, the form of the circuit directory, the stock of the safety signs and of the arc-flash label, the form of the available fault current marking and of the emergency system marking, and the mounting height. What each label says is not a decision; it follows from NFPA 70 and from the one-line diagram. (1.5)
1.6 The text of each equipment nameplate and of each device nameplate shall be as listed on the nameplate schedule.
1.7 Where no nameplate schedule is issued, the Contractor shall prepare one from the one-line diagram and the panel schedules and shall submit it as an action submittal before any nameplate is fabricated.
1.8 The designation on every nameplate, directory and label shall match the designation of the same equipment on the one-line diagram, the panel schedules and the record drawings, and the Contractor shall report any disagreement between those documents to the Engineer of Record before fabrication.
2 Referenced Standards
2.1 Materials, fabrication and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2 Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
| Standard | Title |
|---|---|
| NFPA 70 | National Electrical Code (Articles 110.16, 110.21, 110.22, 110.24, 110.34, 230.2, 230.70, 230.85, 240.86, 250.21, 408.3, 408.4, 450.14, 690.13, 700.7, 700.10, 701.7, 702.7, 705.10, 705.12, 706.15 and 710.10) |
| NFPA 70E | Standard for Electrical Safety in the Workplace (Section 130.5(H), Equipment Labeling) |
| ANSI Z535.1 | Safety Colors |
| ANSI Z535.4 | Product Safety Signs and Labels |
| UL 969 | Marking and Labeling Systems |
| OSHA 29 CFR 1910.303 | Electrical, General (paragraph (e), Marking) |
| OSHA 29 CFR 1910.145 | Specifications for Accident Prevention Signs and Tags |
NOTE NFPA 70 says which labels an installation carries and the few words some of them must use; NFPA 70E 130.5(H) says what the arc-flash label states; ANSI Z535.4 says how a safety sign is laid out and colored so that a worker reads it the same way on every piece of equipment; UL 969 is the test that a pressure-sensitive label stays adhered and legible under the heat, humidity and exposure it is listed for. The four do not overlap, and this standard cites each for its own part. (2.3)
3 Submittals
3.1 Action Submittals
3.1.1 The Contractor shall submit the following for review, and shall not release any nameplate, directory, sign or arc-flash label for fabrication until the submittals have been returned:
- The nameplate schedule listing every nameplate under this standard by equipment designation, with its text line by line, its size, its character heights, its material, its colors and its attachment, cross-referenced to the one-line diagram
- Product data for each nameplate material, each pressure-sensitive label stock with its UL 969 listing and the temperature, humidity and outdoor exposure the listing covers, each sign stock and each adhesive and fastener
- One sample of each nameplate material in each color scheme, engraved with representative text at each character height specified
- One sample of each safety sign type in the ANSI Z535.4 format, and one arc-flash label of the selected stock printed from one line of the label schedule delivered under Arc Flash StudyArc-Flash StudyResolves to the current adopted revision.sync/arc-flash-study
- The circuit directory template, showing the columns, the font and the holder or cover it is installed in
- The available fault current marking in the selected form, printed with the value and date Short Circuit StudyShort-Circuit StudyResolves to the current adopted revision.sync/short-circuit-study states for one item of service equipment
Action Submittals Requiredcheckbox
☑ Nameplate schedule with text, size, character heights, material, colors and attachment
☑ Product data for nameplate materials, label stocks with UL 969 listings, adhesives and fasteners
☑ Engraved sample of each nameplate material and color scheme
☑ Sample safety sign and sample arc-flash label printed from the study
☑ Circuit directory template
☐ Available fault current marking sample
NOTE The nameplate schedule is reviewed against the one-line diagram line by line, because a nameplate that names the wrong source sends the next electrician to the wrong panel to de-energize it, and no quality of engraving corrects that. (3.1.2)
3.1.3 Where the Contractor proposes a material, a color scheme or an attachment differing from the datasheet selection, the proposal shall be identified as a deviation on the transmittal and shall state what is offered in place of each selected item.
3.2 Closeout Submittals
3.2.1 The Contractor shall deliver the following at substantial completion:
- The record nameplate schedule reflecting every nameplate as installed, in an editable electronic format the Owner can reprint from
- The record circuit directory of every panelboard, switchboard and motor control center as installed, in the same editable format
- A photograph of the installed arc-flash label and of the available fault current marking on each item of equipment that carries one, indexed by the equipment designation
- The written warranty required under this standard
- A signed receipt from the Owner for the spare stock delivered
Closeout Submittals Requiredcheckbox
☑ Record nameplate schedule in editable format
☑ Record circuit directories in editable format
☑ Photographs of installed arc-flash labels and available fault current markings
☑ Written warranty
☑ Spare stock receipt
NOTE The editable schedule and directory are what let the Owner replace one nameplate or reprint one directory after a circuit is moved without re-creating the format, and they are the deliverable that keeps the labels matching the installation after the Contractor has left. (3.2.2)
4 Quality Assurance
4.1 Label Product Listing
4.1.1 Every pressure-sensitive label, including the arc-flash label, the safety signs and the circuit directory insert where it is adhesive, shall be of a stock listed to UL 969 for the surface it is applied to and for the temperature, humidity and exposure of its installed location.
4.1.2 The label manufacturer's printing system, meaning the printer, the ribbon or ink and the overlaminate where one is used, shall be the combination covered by the UL 969 listing of the stock, so that the printed legend is within the listing and not only the blank stock.
NOTE A UL 969 listing covers a stock, an adhesive and a printing method as one system, and a legend printed on listed stock with an unlisted ribbon fades while the stock stays put; the blank label and the printed label are two different products, and the listing of the second is the one that matters. (4.1.3)
4.2 Fabricator and Installer
4.2.1 Engraved nameplates shall be fabricated by a shop that produces engraved nameplates for electrical equipment as a regular line of work, or by the equipment manufacturer's nameplate service.
4.2.2 Labels and nameplates shall be installed by the electrical Contractor's own personnel, who shall verify the text of each against the reviewed nameplate schedule before it is fixed.
4.3 Coordination with the Studies
4.3.1 Arc-flash labels shall be printed only from the final label schedule delivered under Arc Flash StudyArc-Flash StudyResolves to the current adopted revision.sync/arc-flash-study, and no arc-flash label shall be printed from a draft schedule, from the report's results tables in place of the schedule, or from any other source.
4.3.2 Available fault current markings shall be printed only from the value and date delivered under Short Circuit StudyShort-Circuit StudyResolves to the current adopted revision.sync/short-circuit-study, or from the serving utility's written statement where Electrical Service EntranceElectrical Service EntranceResolves to the current adopted revision.sync/electrical-service-entrance permits that source, and from no other number.
4.3.3 Where an item of equipment that its product standard requires to carry an arc-flash label does not appear on the label schedule, the Contractor shall refer the equipment to the study's engineer before printing, and shall not infer a value from an adjacent bus.
5 Environmental and Service Conditions
NOTE A conditioned electrical room is where most of the labels under this standard are installed, and the materials offered as the norm are rated for that service; an outdoor enclosure, a wash-down area, a chemical room, a boiler room and a classified location are different services, and the clauses below raise the material at those locations without changing the selection for the rest of the project. (5.1)
5.2 Labels and nameplates on equipment installed outdoors shall be of a material, an adhesive and a printing system rated by their manufacturer for continuous exposure to sunlight and moisture across the range from Site Ambient Temperature MinimumSite Ambient Temperature MinimumParameterEach project supplies its own value.site-ambient-temperature-minimum to Site Ambient Temperature MaximumSite Ambient Temperature MaximumParameterEach project supplies its own value.site-ambient-temperature-maximum, and an engraved plastic nameplate installed outdoors shall be of an ultraviolet-stabilized laminate.
5.3 Labels and nameplates on equipment in a wash-down area, a chemical storage or feed room, or a location the Contract Documents classify as corrosive shall be of engraved stainless steel, engraved ultraviolet-stabilized plastic, or a label stock the manufacturer rates for the chemical exposure of that location, with stainless steel fasteners.
5.4 Labels and nameplates on equipment whose enclosure surface exceeds 60°C in service, including the enclosures of transformers, drives, resistors and heating equipment, shall be of a material and an adhesive rated for the surface temperature stated on the product's data.
5.5 Labels on an enclosure in a hazardous (classified) location shall be attached by adhesive or by the enclosure manufacturer's own nameplate provision, and no hole shall be drilled in an enclosure listed for a classified location for a label.
NOTE A hole drilled in an explosionproof or dust-ignitionproof enclosure voids its listing, and the flame path of such an enclosure is not restored by a sealant; the adhesive label is therefore the rule in a classified location, and its stock is one listed for the temperature class of the enclosure. (5.6)
5.7 Labels installed where equipment is hosed down or steam cleaned shall have no exposed paper core, and an engraved laminate at such a location shall have its edges sealed by the fabricator.
6 Nameplate Material and Construction
6.1 Nameplate Material
6.1.1 Equipment nameplates and device nameplates shall be of the material indicated in the datasheet, except where a clause of this standard requires a different material at a location.
Nameplate Materialselect
Engraved laminated plastic, three-ply with a contrasting core
Engraved anodized aluminum
Engraved or etched stainless steel
Printed polyester label with overlaminate, pressure-sensitive
NOTE Engraved laminated plastic is the nameplate on most distribution equipment, because the core color is the legend and cannot fade or peel, a shop engraves it to a consistent depth, it takes screws or adhesive, and it is the cheapest to replace one at a time, which is why it is the default; its limits are heat above the laminate's rating and the ultraviolet exposure of an unstabilized grade outdoors. Anodized aluminum is engraved through the anodized layer to a bright legend and withstands sun, heat and most weather, at the cost of a legend that reads as metal on metal in dim light and a plate that dents. Stainless steel is the plate that survives wash-down, chemicals and abuse and is the rule of a treatment plant or a food process area, at the highest cost and with a legend that needs filling to read. A printed polyester label with an overlaminate is the lowest cost and the fastest to produce in quantity, prints in full color and is the natural product where a project labels hundreds of small enclosures, and its life is the life of the adhesive and the overlaminate in that environment, which the UL 969 listing states. (6.1.2)
6.1.3 Engraved laminated plastic nameplates shall be of a rigid laminate with a core color contrasting with the face, engraved through the face into the core, with characters of uniform depth and no burr, chip or feathered edge.
6.1.4 Engraved metal nameplates shall be engraved to a depth that remains legible after the surface is scratched, and the engraved characters shall be filled with a contrasting enamel or epoxy fill.
6.1.5 Printed polyester nameplates shall be printed by thermal transfer or by a method the stock's UL 969 listing covers, with an overlaminate over the legend, and shall not be printed by a method that leaves the legend on the surface unprotected.
6.1.6 The thickness of engraved nameplates shall be not less than the thickness indicated in the datasheet.
Engraved Nameplate Thicknessrange
Not less than
in
0.031250.06250.093750.125
NOTE A 1/16 in laminate is the thickness most engraved nameplates are made to, rigid enough not to bow under two screws and thin enough to engrave in one pass, which is why it is the default; 1/32 in is a flexible laminate used only where the plate is adhered to a curved or small surface, and 1/8 in is bought where the plate is large, where it is screwed to an uneven surface, or where the fabricator's stock for a metal plate is that thickness. (6.1.7)
6.2 Nameplate Colors
6.2.1 Nameplates on equipment of the normal power system shall have the face and character colors indicated in the datasheet.
Normal Power Nameplate Colorsselect
White face with black characters
Black face with white characters
Gray face with black characters
Clear face with white core, black characters
NOTE Black characters on a white face read at the greatest distance under the lighting of an electrical room and photograph legibly for the record, and they are the colors of most normal power nameplates, which is why they are the default; white on black is the convention of some Owners and utilities and reads better on a light-colored enclosure; gray on black suits a dark enclosure finish; a clear face over a white core is specified where the enclosure color is to show through the plate. The choice is the Owner's convention first and legibility second, and a project with an Owner standard follows it. (6.2.2)
6.2.3 Where the project's system color convention under Electrical IdentificationWiring System IdentificationResolves to the current adopted revision.sync/electrical-identification assigns a color to a system other than normal power, the nameplate on each item of equipment of that system shall have a face of that color with characters of a contrasting color, so that the equipment of a system is recognizable by its nameplate color from across the room.
NOTE One convention names the system colors for the whole project, and it lives with the wiring identification because the same colors band the raceways, mark the box covers and appear on the posted legend; the nameplate takes the color from that convention rather than naming its own, so that an emergency panelboard, its feeder raceway and its junction boxes are all the one color. (6.2.4)
6.2.5 Equipment that serves more than one system, including a transfer switch and a panelboard with separately identified sections, shall carry a nameplate in the color of the system it supplies, and each source or section shall additionally be identified at its own connection point or section by a nameplate in the color of that source or section's system.
6.3 Character Heights and Lettering
6.3.1 Characters on every nameplate shall be capital letters in a sans-serif typeface, engraved or printed in one style across the project.
6.3.2 The equipment designation on the first line of an assembly or equipment nameplate shall be of a character height not less than that indicated in the datasheet.
Equipment Designation Character Heightrange
Not less than
in
0.250.3750.50.751
6.3.3 The remaining lines of an assembly or equipment nameplate, stating the voltage, the rating, the source and the system, shall be of a character height not less than that indicated in the datasheet.
Equipment Nameplate Secondary Line Character Heightrange
Not less than
in
0.1250.18750.250.3750.5
6.3.4 Device, compartment and unit nameplates inside a lineup, and the nameplates of disconnects, starters and small enclosures, shall be of a character height not less than that indicated in the datasheet.
Device and Compartment Nameplate Character Heightrange
Not less than
in
0.1250.18750.250.3750.5
NOTE A 1/2 in designation reads from the working clearance in front of the equipment and from the room door, and 1/4 in secondary lines and 3/16 in device nameplates read from the working position without stooping; these are the heights most nameplate schedules carry, which is why they are the defaults. A larger designation is specified in a high-bay room, on outdoor equipment read from a walkway, and on equipment above eye level; a smaller device nameplate is accepted only where the device face has no room for 3/16 in characters, and the panel schedule then carries the full text. (6.3.5)
6.3.6 Nameplate layout shall place the equipment designation alone on the first line and the remaining information on the lines below in the same order on every nameplate of the project.
6.4 Nameplate Attachment
6.4.1 Nameplates shall be attached by the method indicated in the datasheet, except where a clause of this standard requires a different method at a location.
Nameplate Attachment Methodselect
Stainless steel self-tapping screws or drive rivets
Stainless steel screws or rivets with a pressure-sensitive adhesive backing
High-bond acrylic foam adhesive only
Equipment manufacturer's nameplate holder or nameplate recess
NOTE Screws or rivets hold a nameplate for the life of the equipment through the heat cycling of an electrical room and the sun of an outdoor enclosure, which is why they are the default on distribution equipment; they need a hole, which is the reason they are forbidden where a hole would void a listing or a rating. Fasteners with an adhesive backing hold the plate flat during installation and keep it in place if a screw loosens, at a small added cost. High-bond foam adhesive alone needs no hole and is the attachment on a glass window, a plastic deadfront and an enclosure whose rating a hole would compromise, and it holds only on a clean smooth surface within the adhesive's temperature rating, failing first on a hot or outdoor enclosure. A manufacturer's holder or recess is the attachment where the equipment provides one, and it holds the standard plate the manufacturer sizes it for. (6.4.2)
6.4.3 Fasteners shall not penetrate into the wiring space of an enclosure, shall not reduce the clearance to any live part, and shall not interfere with a door, latch, hinge or cover.
6.4.4 Nameplates on an enclosure rated NEMA Type 3R, 4, 4X or 12 shall be attached by adhesive, by the manufacturer's provision, or by fasteners with sealing washers in a manner the enclosure manufacturer states keeps the enclosure's rating, and no nameplate fastener shall be driven through the top or a gasketed surface of such an enclosure.
6.4.5 Nameplates on a drawout unit, a removable door or a cover that can be fitted in another position shall be attached to the stationary structure beside the unit, door or cover, or to both the structure and the removable part, so that the identification stays with the position.
NOTE A nameplate attached to a bucket door alone travels with the bucket when buckets are swapped, and the next technician reads the wrong motor on the door in front of a different starter; the structure nameplate is the one that stays true. (6.4.6)
6.4.7 Adhesive-attached nameplates and labels shall be applied to a surface cleaned of oil, dust, overspray and protective film, dry, and within the application temperature range the adhesive manufacturer states, with the plate pressed to the surface for the dwell time that manufacturer states.
7 Equipment Identification Nameplates
7.1 Nameplate Content
7.1.1 Every item of electrical distribution equipment, including each switchgear and switchboard lineup, each panelboard, each motor control center, each transformer, each transfer switch, each generator, each drive, each disconnect, each enclosed overcurrent device and each separately enclosed starter or contactor, shall carry a field-applied equipment nameplate on its front, readable without opening a door or removing a cover.
7.1.2 Each equipment nameplate shall state the equipment designation and the source from which the equipment is fed, with the source named by its designation and its location, in accordance with NFPA 70 408.4(B) for switchboards, switchgear and panelboards and with NFPA 70 110.22(A) for every disconnecting means.
7.1.3 In addition to the designation and the source, each equipment nameplate shall state the items indicated in the datasheet, in the text listed on the nameplate schedule.
Equipment Nameplate Content Beyond Designation and Sourcecheckbox
☑ System voltage with the number of phases and wires
☑ Main bus, frame or continuous current rating
☑ Main device rating where a main is furnished
☑ Short-circuit current rating of the assembly
☑ System served, where other than normal power
☑ Load served, for a disconnect, starter, drive, transformer or transfer switch
☐ Control voltage, where the equipment has a control circuit
☐ Transformer kVA with primary and secondary voltages
7.1.4 Where a product standard in this library lists the content of the nameplate on its equipment, that list governs for that equipment and is added to the content selected here, and the nameplate schedule carries the union of the two.
NOTE The source on a nameplate is the designation and the room of the overcurrent device that feeds the equipment, not the name of the room the equipment stands in; a nameplate that reads a designation alone satisfies no one at 2 a.m., and NFPA 70 408.4(B) is the rule that puts the source on it. (7.1.5)
7.1.6 Each device, compartment, unit and section inside a lineup, including each breaker, each switch, each starter unit, each drive unit, each feeder tap and each cable compartment door, shall carry a device nameplate stating the device designation and the load it serves, matching the one-line diagram, in the text listed on the nameplate schedule.
7.1.7 A spare device shall carry a device nameplate reading SPARE, a prepared space shall carry one reading SPACE, and no device nameplate shall read FUTURE or any other word that leaves the status of the position open.
NOTE A breaker marked SPARE is one the next electrician loads without research, and one marked FUTURE is one that sends them looking for a drawing that no longer exists; the two words are a status, and the status is kept current with the directory. (7.1.8)
7.2 Disconnecting Means Identification
7.2.1 Each disconnecting means shall be marked to indicate its purpose, naming the equipment it disconnects and the source that feeds it, in accordance with NFPA 70 110.22(A), and the marking shall not read only DISCONNECT, SWITCH or a device designation.
7.2.2 A motor disconnect shall name the motor and the driven equipment, and a disconnect for a utilization appliance shall name the appliance, in each case by the designation the mechanical or process schedules give it.
7.2.3 Where a transformer's disconnecting means is not within sight of the transformer, the location of the disconnecting means shall be field marked on the transformer, in accordance with NFPA 70 450.14, and where any other equipment's disconnecting means is permitted out of sight by the article that governs that equipment, the same marking shall be applied to that equipment.
7.2.4 Where a disconnect is one of a group, its marking shall distinguish it from the others of the group so that it can be identified without operating it.
8 Circuit Directories
8.1 Every panelboard, every switchboard and switchgear lineup and every motor control center shall carry a circuit directory that identifies the load served by each device and the use of each spare and space, in accordance with NFPA 70 408.4(A), in the form indicated in the datasheet.
Circuit Directory Formselect
Printed card in the manufacturer's directory holder inside the door
Printed card under a clear rigid cover fastened to the door face
Engraved laminated plastic directory plate fastened to the door face
Printed laminated card adhered inside the door
NOTE The printed card in the holder the manufacturer builds into the door is the directory of most panelboards, because it is reprinted from the record file and slid in when a circuit changes, which is why it is the default; a card under a clear cover on the door face is read without opening the door and suits a switchboard or motor control center whose directory is long; an engraved plate cannot be altered without a new plate, which some Owners want on life-safety equipment and which costs a plate at every circuit change; a laminated card adhered inside the door is the lowest cost and the one that is torn off and replaced with handwriting first. (8.2)
8.3 Each circuit description shall identify the load by its type and by the room number or area it serves, and a circuit serving a single item of equipment shall name that equipment by its schedule designation, so that the load is identifiable with specificity from the directory alone.
8.4 A description reading LIGHTS or RECEPTACLES with no location shall not be accepted, and a description shall not depend on a transient condition of occupancy, such as a tenant's name, where a room number or a permanent area name exists.
8.5 Each spare device shall be entered as SPARE and each prepared space as SPACE, and no position in the directory shall be left blank.
8.6 The directory shall be machine printed in a font not smaller than the size indicated in the datasheet, and no directory or correction shall be handwritten.
Circuit Directory Font Sizerange
Not less than
pt
8101214
NOTE A 10 point font fills a 42-circuit card in the standard holder and reads without a light, which is why it is the default; 8 point is accepted only where a dense switchboard directory would otherwise run to two cards, and 12 or 14 point is specified where the directory is read from the door face at a distance or by a maintenance staff who have asked for it. (8.7)
8.8 The directory shall be completed from the circuits as verified at testing under the equipment's standard, and not from the design panel schedule, and shall be installed before the equipment is turned over.
8.9 Where a circuit is reassigned during construction or during the warranty period while the Contractor is on site, the Contractor shall reprint and reinstall the directory, and shall deliver the revised record file.
8.10 Where a panelboard supplies a healthcare essential electrical system branch or a separately identified section, the directory shall identify the branch or the section each device belongs to as Healthcare Essential Electrical SystemsHealthcare Essential Electrical SystemsResolves to the current adopted revision.sync/healthcare-essential-electrical-systems requires.
9 Safety Signs and Field Markings
9.1 Sign Format and Stock
9.1.1 Every field-applied hazard marking under this standard, including the arc-flash warning label, shall be laid out in the ANSI Z535.4 format with a signal word panel, the safety alert symbol where the signal word is DANGER, WARNING or CAUTION, a message panel, and a pictorial where one is prescribed, and shall be of a stock durable for the environment of its location, in accordance with NFPA 70 110.21(B).
9.1.2 The signal word panel shall carry the signal word in the colors ANSI Z535.1 assigns it: white on safety red for DANGER, black on safety orange for WARNING, black on safety yellow for CAUTION, and white on safety blue for NOTICE.
9.1.3 No hazard marking shall be handwritten, and a field-entered value on a hazard marking shall be entered with a permanent marker of the type the label manufacturer's listing covers, only in a field the printed label provides for it.
9.1.4 Safety signs, other than the arc-flash label, shall be of the stock indicated in the datasheet.
Safety Sign Stockselect
Printed polyester label with overlaminate, pressure-sensitive
Printed vinyl label with overlaminate, pressure-sensitive
Engraved laminated plastic plate in ANSI Z535 colors
Printed aluminum sign, mechanically fastened
NOTE A polyester label with an overlaminate is printed in the ANSI Z535 colors on demand, carries a UL 969 listing for most indoor and sheltered outdoor exposures, and is the stock of most safety signs on electrical equipment, which is why it is the default; vinyl conforms to a curved or textured surface and is the stock chosen for a small or rounded enclosure, with a shorter life in sunlight than polyester; an engraved plate reproduces the signal word colors in the laminate's core and face and survives wash-down and abuse, and it carries no pictorial unless one is engraved; a printed aluminum sign is the stock of an outdoor switchyard, a generator yard and a rooftop, mechanically fastened, and is the costliest per sign. (9.1.5)
9.2 Signs Required on Equipment
9.2.1 Each item of service equipment, each meter disconnect, each emergency disconnect and each additional service, feeder or branch circuit supplying the building shall carry the markings and the plaque NFPA 70 230.2(E), 230.70(B) and 230.85 require, in the wording and at the locations Electrical Service EntranceElectrical Service EntranceResolves to the current adopted revision.sync/electrical-service-entrance requires, with the sign made under this standard.
9.2.2 Where a building or structure is supplied by more than one power source, including a utility service and an interactive inverter, an energy storage system, a generator or a stand-alone source, a permanent plaque or directory shall be installed at each service equipment location and at each point of interconnection, denoting every power source on or in the premises and the location of each source's disconnecting means, in accordance with NFPA 70 705.10 and 710.10.
9.2.3 Where an emergency power source is installed, a sign shall be placed at the service entrance equipment indicating the type and location of each on-site emergency power source, in accordance with NFPA 70 700.7(A), and the corresponding signs NFPA 70 701.7 and 702.7 require shall be placed where a legally required or an optional standby source is installed.
9.2.4 Where a photovoltaic system or an energy storage system is installed, each disconnecting means and the point of interconnection shall carry the markings NFPA 70 690.13 and 706.15 require, with the content Photovoltaic SystemsPhotovoltaic SystemsResolves to the current adopted revision.sync/photovoltaic-systems and Battery Energy Storage SystemsBattery Energy Storage SystemsResolves to the current adopted revision.sync/battery-energy-storage-systems require and the sign made under this standard.
9.2.5 Where a backfed overcurrent device is connected to a power source output, the device shall carry the warning marking NFPA 70 705.12 requires, stating that the device is a power source output connection and is not to be relocated.
9.2.6 Where the system relies on a series-rated combination of overcurrent devices, the equipment enclosure shall be field-marked to indicate that it has been applied with a series combination rating and that identified replacement components are required, in accordance with NFPA 70 110.22(B) and 110.22(C) and 240.86, with the rating as Short Circuit StudyShort-Circuit StudyResolves to the current adopted revision.sync/short-circuit-study states it.
9.2.7 Where an ungrounded system is installed, the source or the first disconnecting means of the system shall be marked with the caution NFPA 70 250.21(C) prescribes, stating that the system is ungrounded and the voltage between conductors.
9.2.8 Where a high-leg delta system is installed, the equipment at which the high leg terminates shall be marked at the high-leg terminal with the phase voltage to ground, in accordance with NFPA 70 408.3(F)(1), in addition to the orange identification of the conductor that Electrical IdentificationWiring System IdentificationResolves to the current adopted revision.sync/electrical-identification requires.
9.2.9 Where equipment operating at more than 1000 V is installed, each enclosure and each entrance to it shall carry the warning sign NFPA 70 110.34(C) prescribes.
NOTE Each marking in this article is triggered by a condition of the one-line diagram, and none of them is a datasheet choice: a project with one utility service and no on-site source carries none of the source plaques, and a project with a generator, an inverter and a series-rated panelboard carries all of them. The Contractor reads the triggers from the reviewed one-line diagram and the study reports, and the nameplate schedule lists each sign the triggers call for. (9.2.10)
10 Arc-Flash Warning Labels
10.1 Label Product
10.1.1 An arc-flash warning label shall be applied to each item of equipment the label schedule delivered under Arc Flash StudyArc-Flash StudyResolves to the current adopted revision.sync/arc-flash-study lists, in accordance with NFPA 70 110.16(A), printed with the content, the values, the operating states and the signal word that schedule states for the bus, and no label under this standard shall state an arc-flash value from any other source.
10.1.2 The arc-flash label shall be of the stock indicated in the datasheet.
Arc-Flash Label Stockselect
Printed polyester label with overlaminate, pressure-sensitive
Printed vinyl label with overlaminate, pressure-sensitive
Engraved laminated plastic plate with a printed insert under a clear window
Printed aluminum or stainless steel plate, mechanically fastened
NOTE A polyester label with an overlaminate prints the signal word colors and the pictorial in one pass, is reprinted when the study is revised, and lasts the review interval of the study in a conditioned or sheltered location, which is why it is the default; vinyl conforms to a curved enclosure and fades sooner in sunlight; an engraved plate with a window holds a printed insert that is swapped at each study revision while the plate and its fasteners stay, and suits a wash-down area; a printed metal plate is the product of an outdoor switchyard or a rooftop, where an adhesive label fails within a few seasons, and it is replaced whole at each revision. (10.1.3)
10.1.4 The data block of the arc-flash label shall be printed in characters not smaller than the height indicated in the datasheet, and the signal word in characters not smaller than twice that height.
Arc-Flash Label Data Block Character Heightrange
Not less than
in
0.093750.1250.18750.25
NOTE A 1/8 in data block reads from the working distance the label itself states, and fits the values on the label sizes the stock manufacturers supply, which is why it is the default; 3/32 in fits a label on a small enclosure at the limit of legibility, and 3/16 in or 1/4 in is specified where the label is read from the floor on equipment mounted high or behind a barrier. (10.1.5)
10.1.6 The equipment designation and the bus identifier printed on the arc-flash label shall match the designation on the equipment nameplate and the line of the label schedule the label was printed from, so that a label can be traced to the schedule that produced it.
10.2 Interim Labeling and Replacement
10.2.1 Where equipment is energized before the final study values are available, the equipment shall be labeled as indicated in the datasheet.
Arc-Flash Label Before the Study Is Finalradio
● Generic arc-flash warning label at energization, replaced by the study label
○ No energization until the study label is installed
NOTE A generic warning per NFPA 70 110.16(A) at energization, replaced by the study label when the values arrive, is what most projects do, because the study's settings are verified only after the equipment is installed and energized, which is why it is the default; holding energization until the study label is on the door is the rule of an Owner whose safety program forbids a generic label and of a project whose study is finished before equipment delivery, at the cost of a schedule dependency on the study. (10.2.2)
10.2.3 Where a generic label is installed, it shall carry the signal word WARNING, the arc-flash pictorial and the instruction to wear appropriate personal protective equipment, shall carry no numeric value, and shall be removed when the study label is installed.
10.2.4 The final arc-flash labels shall be installed within the number of days indicated in the datasheet after the Contractor receives the final label schedule, and in every case before substantial completion.
Days to Install Final Arc-Flash Labels After Receipt of the Label Schedulerange
Not more than
days
714306090
NOTE Thirty days covers printing, the submittal of the printed sample and a site visit to every piece of equipment on most projects, which is why it is the default; a shorter period is set where the Owner occupies before the study arrives, and a longer one where a campus study covers hundreds of buses and the labels are installed building by building. (10.2.5)
10.3 Label Location
10.3.1 Each arc-flash label shall be placed on the front of the equipment, on or beside the door or cover a worker opens to perform the task the study rates, where it is read before that door or cover is opened, and at each other face, section or compartment of the equipment for which the label schedule lists a separate label.
10.3.2 Arc-flash labels shall not be placed on a removable cover that can be refitted elsewhere, on a drawout unit, or where a door in its open position hides the label of the adjacent section.
11 Available Fault Current Marking
11.1 The maximum available fault current and the date it was calculated shall be field-marked on each item of service equipment other than one supplying a dwelling unit, in accordance with NFPA 70 110.24(A), with the value and the date that Short Circuit StudyShort-Circuit StudyResolves to the current adopted revision.sync/short-circuit-study states, in the form indicated in the datasheet.
Available Fault Current Marking Formradio
○ Separate label beside the equipment nameplate
○ Field on the arc-flash warning label
○ Line on the equipment nameplate
NOTE A separate label is revised under NFPA 70 110.24(B) without touching the nameplate or the arc-flash label, and it is read by the inspector who looks for it beside the nameplate; a field on the arc-flash label keeps the two study values on one sign and is revised with it; a line on the engraved nameplate is permanent until the nameplate is replaced, which an Owner who re-engraves at every modification accepts and others do not. No form is the norm across projects, so the field carries no default; the one condition that decides it is how the Owner intends to revise the value after a service modification. (11.2)
11.3 The available fault current marking shall be of a stock that lasts in the environment of the service equipment under the Environmental and Service Conditions of this standard, and shall carry the signal word NOTICE where it is a separate label in the ANSI Z535.4 format.
11.4 Where Electrical Service EntranceElectrical Service EntranceResolves to the current adopted revision.sync/electrical-service-entrance requires the marking of NFPA 70 110.16(B) on service equipment rated 1200 A or more, that marking shall be made on the arc-flash label or on a separate label of the same stock, and shall not duplicate a value already printed on the arc-flash label of the same equipment.
12 Emergency and Standby System Equipment Marking
12.1 Each transfer switch, generator, panelboard, enclosure and other item of equipment of an emergency system shall be permanently marked so that it is readily identified as a component of the emergency system, in accordance with NFPA 70 700.10(A), and the equipment of a legally required standby system, an optional standby system and a critical operations power system shall be marked as NFPA 70 Articles 701, 702 and 708 respectively require, in the form indicated in the datasheet.
Emergency and Standby Equipment Marking Formselect
Equipment nameplate in the system color, naming the system
Separate system label beside the equipment nameplate
Equipment nameplate in the system color and a separate system label
NOTE A nameplate in the system color that names the system is one plate and is the form of most projects that color-code nameplates; a separate system label is added to a nameplate of the normal color where the Owner's convention keeps every nameplate the same color, and it is the only form available on equipment whose nameplate the manufacturer furnished; both together give the recognition of the color and the words of the label and are the form some healthcare and data center Owners require. The choice follows the nameplate color convention selected under this standard, so the field carries no default. (12.2)
NOTE The marking of the boxes and raceways of these systems is governed by Electrical IdentificationWiring System IdentificationResolves to the current adopted revision.sync/electrical-identification, and the marking under this article is the one on the equipment enclosure. (12.3)
12.4 Equipment of a healthcare essential electrical system shall be marked with the branch it serves as Healthcare Essential Electrical SystemsHealthcare Essential Electrical SystemsResolves to the current adopted revision.sync/healthcare-essential-electrical-systems requires, with the nameplate made under this standard.
13 Installation
13.1 Sequence
13.1.1 Equipment nameplates, device nameplates and the signs required on equipment shall be installed before the equipment is energized, and in every case before the equipment is turned over to the Owner.
13.1.2 Circuit directories shall be installed after the circuits have been verified at testing and before the equipment is turned over.
NOTE The sequence puts the designation and the source on the door before the first person opens it energized, and leaves the directory until the circuits are real; a directory printed from the design schedule is the one the commissioning agent finds wrong. (13.1.3)
13.2 Mounting Position
13.2.1 The equipment nameplate on floor-standing equipment shall be mounted at the height above the finished floor indicated in the datasheet, measured to the centerline of the nameplate, and at the same height on every lineup, section and freestanding enclosure of the project.
Equipment Nameplate Mounting Heightrange
in
4854606672
NOTE Sixty inches puts the nameplate at the eye level of a standing worker and above the handles and meters of most equipment fronts, and it is the height most projects use, which is why it is the default; a lower height is used where the equipment is short or the nameplate must clear a window, and a higher one where the equipment is read over a barrier or from a mezzanine. (13.2.2)
13.2.3 The equipment nameplate on wall-mounted equipment shall be mounted on the front cover or door, centered near the top where the cover construction permits, and at a consistent position on like equipment.
13.2.4 Device nameplates shall be mounted on or directly adjacent to the device, compartment or unit they identify, in a position that remains visible with the device in any operating position.
13.2.5 Nameplates and labels shall be mounted level and square to the enclosure, shall not cover the manufacturer's nameplate, listing mark, rating marking or warning marking, and shall not cover a vent, a window, a meter, an indicator or an operating handle.
13.2.6 Where an existing label on reused equipment conflicts with a label under this standard, the Contractor shall remove the existing label, and no two labels stating different values for the same quantity shall remain on one enclosure.
NOTE Two labels on one door that disagree about the source or the fault current leave the worker to guess which is current, and the guess is the hazard; the old label comes off when the new one goes on. (13.2.7)
14 Delivery, Storage, and Handling
14.1 Nameplates, labels and sign stock shall be delivered in the fabricator's packaging, each nameplate marked with its equipment designation from the nameplate schedule, and shall be checked on receipt against the schedule for text and quantity.
14.2 Pressure-sensitive label stock and adhesives shall be stored indoors within the temperature and humidity range and the shelf life the manufacturer states, and stock past its shelf life shall not be used.
14.3 Engraved nameplates shall be stored flat, protected from scratching and from solvents, and a nameplate with a chipped edge, a scratched face or a filled character that has lifted shall not be installed.
15 Warranty
15.1 The Contractor shall warrant every nameplate, label, directory and sign under this standard against fading, delamination, lifting, peeling, corrosion, loss of fill and loss of legibility, and against disagreement with the installation as turned over, for the period indicated in the datasheet, measured from the date of substantial completion.
Label Warranty Periodrange
Not less than
years
1235
NOTE One year is the general-conditions warranty and is what a label and nameplate package commonly carries, because the labels are a small part of a larger electrical warranty, which is why it is the default; two to five years is specified where the Owner has had adhesive labels fail in an unconditioned or outdoor location and wants the replacement cost on the Contractor through that exposure. (15.2)
15.3 A label that fails within the warranty period shall be replaced by the Contractor at no cost to the Owner, including a label whose failure is traced to a stock not rated for the conditions of its location that were known from the Contract Documents, and the replacement shall be of a stock rated for those conditions.
15.4 A repair or replacement performed under this warranty shall itself be warranted for a full new term equal to the original period from the date the replacement is completed, or for the remainder of the original period, whichever ends later.
16 Spare Parts
16.1 The Contractor shall deliver blank nameplate stock of the selected material and each color scheme used, in the quantity indicated in the datasheet, together with the editable record nameplate schedule and record directories, so that the Owner can add or replace a nameplate to the project convention.
Spare Blank Nameplates Deliveredrange
nameplates
5102050
NOTE Ten blanks of each color cover the first few years of moved circuits and added disconnects on most projects and cost little, which is why they are the default; zero records that the Owner has its own engraving source, and a larger stock suits a campus or a plant with a maintenance shop that engraves its own. (16.2)
16.3 The Contractor shall deliver one unopened roll or pack of each pressure-sensitive label stock used for safety signs and arc-flash labels, so that a damaged sign can be reprinted to the same stock and listing.
This standard is written and maintained by SynC and licensed under Creative Commons Attribution 4.0. You may share and adapt it, including commercially, provided you credit SynC Standards, link to the license, and indicate any changes. Each standard is drafted from cited sources under published authoring rules, reviewed before adoption, and corrected in the open. Keep the attribution and notice below with any copy; it carries the warranty notice the license asks you to retain.
"Electrical Equipment Labels," SynC Standards, revision 10. Licensed under CC BY 4.0 (https://creativecommons.org/licenses/by/4.0/). Source: https://synergyinconstruction.com/standards/general/equipment-labeling. Reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.