Elevators
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 5
to Rev 6
in Elevators.
---
title: Elevators
…105 unchanged lines
- "Standby power operation sequence"
- "Sample warranty and warranty-period maintenance scope"
+constraint: all_of
```
…28 unchanged lines
- "Proposed acceptance test plan"
- "Manufacturer's installation instructions and Maintenance Control Program documents on site"
+constraint: all_of
```
…37 unchanged lines
- "Keys, diagnostic tool, software access and credentials"
- "Warranty documents and callback contact information"
+constraint: all_of
```
…9 unchanged lines
```datasheet
−label: Minimum Manufacturer Experience with the Furnished Drive Type
+label: Manufacturer Experience with the Furnished Drive Type
type: range
unit: years
…2 unchanged lines
step: 1
default: 5
+constraint: min
```
…70 unchanged lines
- "Engineer of Record and the Architect"
- "Owner's representative"
+constraint: all_of
```
…39 unchanged lines
setpoints: [1500, 2000, 2100, 2500, 3000, 3500, 4000, 4500, 5000, 6000, 8000, 10000]
default: deferred
+constraint: exact
```
…9 unchanged lines
setpoints: [75, 100, 125, 150, 200, 250, 300, 350, 400, 500, 700, 800, 1000, 1200, 1400, 1600, 1800, 2000]
default: deferred
+constraint: exact
```
…288 unchanged lines
- "Load weighing bypass of hall calls at a set load"
- "Energy-saving standby that dims car lighting and stops the fan when idle"
+constraint: all_of
```
…67 unchanged lines
setpoints: [0.125, 0.25, 0.375, 0.5]
default: 0.25
+constraint: max
```
…18 unchanged lines
```datasheet
−label: Maximum Horizontal Vibration
+label: Horizontal Vibration
type: range
unit: milli-g peak-to-peak
min: 8
max: 30
setpoints: [8, 10, 12, 15, 18, 20, 25, 30]
+constraint: max
```
### Where ride quality is measured, the sound level in the car at rated speed with the fan off shall not exceed the value indicated in the datasheet.
```datasheet
−label: Maximum In-Car Sound Level at Rated Speed
+label: In-Car Sound Level at Rated Speed
type: range
unit: dB(A)
min: 48
max: 65
setpoints: [48, 50, 52, 55, 58, 60, 65]
+constraint: max
```
…31 unchanged lines
setpoints: [32, 36, 42, 48, 54, 60]
default: deferred
+constraint: exact
```
…9 unchanged lines
setpoints: [84, 96, 108, 120]
default: deferred
+constraint: exact
```
…192 unchanged lines
- "Two-speed ventilation fan in the canopy"
- "Hinged or removable car ceiling access for lamp replacement"
+constraint: all_of
```
…196 unchanged lines
drawing_ref: "the life safety plans and the code analysis"
default: deferred
+constraint: all_of
```
…33 unchanged lines
step: 1
default: deferred
+constraint: exact
```
…182 unchanged lines
- "Emergency communication end to end"
- "Accessibility dimensions, reach ranges and signal timing"
+constraint: all_of
```
…26 unchanged lines
setpoints: [0, 3, 6, 12, 18, 24]
default: 12
+constraint: min
```
…27 unchanged lines
max: 24
setpoints: [1, 2, 4, 8, 24]
+constraint: max
```
…14 unchanged lines
setpoints: [1, 2, 3, 5]
default: 1
+constraint: min
```
…43 unchanged lines
- "Recommended spare parts list with part numbers and sources"
- "Hoistway and machine room access keys and fixture keys"
+constraint: all_of
```
## The record wiring diagrams furnished shall reflect the controller as adjusted at acceptance, including every field change, and a straight-line diagram shall be kept in a holder in the machine room or control space as ASME A17.1 requires.
## Where diagnostic credentials are furnished, the Contractor shall record them in a sealed envelope delivered to the Owner's designated representative and shall not retain a credential the Owner has not authorized in writing after the maintenance period ends.