Electrical Safety Program

Rev 1 · Updated Jun 18, 2026 · View history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

NOTE The program applies to electrical equipment and circuits operating at 50 V or more, alternating or direct current, from 120 V branch circuits through 15 kV distribution. (1.2)
NOTE NFPA 70E sets 50 V as the threshold below which a written electrical safety program and the associated shock and arc flash protection requirements are not triggered. Above that threshold the full apparatus of risk assessment, boundaries, permits, and PPE applies, scaling in rigor with voltage and available fault current rather than switching on only at high voltage. (1.3)
NOTE The program covers hazard identification and arc flash risk assessment methodology, boundary and incident-energy labeling, energized electrical work permit (EEWP) procedures, lockout/tagout (LOTO), PPE selection, qualified-person work boundaries, training, and the program review cycle. (1.4)
NOTE This program consumes the output of the arc flash study; it does not specify the engineering calculation methodology. (1.5)
NOTE Incident energy, available fault current, clearing time, and the resulting PPE category for each piece of equipment are produced by the short-circuit study, the protective device coordination study, and the arc flash calculation. Those analyses are owned by Arc Flash Study and Short Circuit Study. This standard governs how that output is labeled, who may work inside the resulting boundaries, what permits and PPE are required, and how the program is maintained. (1.6)
NOTE Owner-furnished and contractor-submitted programs are both within scope. (1.7)
NOTE On many construction projects the Owner maintains a facility electrical safety program and each electrical contractor must either work under it or submit an equivalent program for review. This standard defines the content both must contain and the equivalency review that reconciles them, so that site-wide safety coverage has no gaps where one contractor's procedures fall short of the Owner's. (1.8)

2 Referenced Standards

2.1Work, equipment, and documentation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Authority Having Jurisdiction or the Owner's electrical safety authority directs otherwise in writing.
Standard Title
NFPA 70E-2024 Standard for Electrical Safety in the Workplace
NFPA 70 (NEC) 2023 National Electrical Code (Article 110.16)
IEEE 1584-2018 Guide for Performing Arc Flash Hazard Calculations
OSHA 29 CFR 1910 Subpart S Electrical Safety-Related Work Practices (General Industry)
OSHA 29 CFR 1910.147 The Control of Hazardous Energy (Lockout/Tagout)
OSHA 29 CFR 1926.417 Lockout and Tagging of Circuits (Construction)
OSHA 29 CFR 1926 Subpart K Electrical Safety (Construction)
ANSI Z535.4-2011 (R2017) Product Safety Signs and Labels
NFPA 70B-2023 Recommended Practice for Electrical Equipment Maintenance
2.3The NFPA 70E 2024 edition (effective May 13, 2023) shall be the governing edition for this program.
NOTE The 2024 edition introduced the requirement for a second qualified person during all justified energized work under a permit, and a hearing-protection mandate within the arc flash boundary. Programs still written to the 2021 edition omit both. The edition is named explicitly here so that submittals cannot satisfy this standard by citing a superseded edition. (2.4)

3 Submittals

3.1The Contractor shall submit the following action submittals for review and approval before any work on or near energized equipment begins:
  • Written Electrical Safety Program document, or a written statement electing to work under the Owner's program
  • Energized Electrical Work Permit (EEWP) form template
  • Lockout/Tagout written procedure, including group lockout provisions
  • PPE program identifying arc-rated clothing and equipment stocked by PPE category
  • Qualified-person roster with documented training and credentials
Action Submittalscheckbox
Electrical Safety Program document (or election to use Owner program)
EEWP form template
Lockout/Tagout written procedure (with group lockout)
PPE program by category
Qualified-person roster with training records
3.2The Contractor shall submit the following informational submittals:
  • Arc flash and shock risk assessment results, where the Contractor performs or updates the study
  • Arc flash label schedule keyed to equipment identification
  • Manufacturer arc rating (ATPV or EBT) certification for each arc-rated garment and hood
  • Insulating rubber glove and insulated-tool test certificates
Informational Submittalscheckbox
Arc flash and shock risk assessment results
Arc flash label schedule keyed to equipment IDs
Arc rating (ATPV/EBT) certification for arc-rated PPE
Insulating glove and insulated-tool test certificates
3.3The Contractor shall submit the following closeout submittals before project completion:
  • Final arc flash study report reflecting as-built system configuration
  • Training records for all electrical workers, with retraining dates
  • Periodic LOTO inspection records for the construction period
Closeout Submittalscheckbox
Final as-built arc flash study report
Training records with retraining dates
Periodic LOTO inspection records

4 Quality Assurance

4.1The electrical safety program shall be administered by a designated electrical safety authority responsible for the program's content, currency, and enforcement.
4.2All work on or near energized conductors operating at 50 V or more shall be performed only by qualified persons as defined in this program.
4.3The arc flash and shock risk assessment shall be performed by, or under the direct supervision of, a licensed professional engineer.
4.4Qualified persons shall be trained in and demonstrate the skills and techniques required to distinguish exposed energized parts, determine nominal voltage, and identify the approach distances corresponding to that voltage.
NOTE NFPA 70E and OSHA 1910.332 define a qualified person by demonstrated ability, not by job title or seniority. The definition is task- and equipment-specific: a worker qualified on 480 V panelboards is not automatically qualified on 15 kV switchgear. The program's roster must therefore record the equipment classes and voltage ranges each person is qualified for, not a blanket designation. (4.5)
4.6Unqualified persons shall not cross the limited approach boundary unless continuously escorted by a qualified person and protected from contact with energized parts.

5 Hazard Identification and Risk Assessment

5.1Before any work that exposes a worker to an electrical hazard, the qualified person shall perform a shock risk assessment and an arc flash risk assessment for the task.
NOTE The risk assessment is the gate that decides whether work proceeds energized or de-energized, what boundaries apply, and what PPE is required. It is performed for the specific task and equipment condition (covers on versus removed, doors open versus closed), not once for the facility. The facility arc flash study supplies the incident energy and boundary numbers; the task-level assessment applies them to the work actually being done. (5.2)
5.3The default condition for all work shall be an electrically safe work condition established by de-energizing and applying lockout/tagout; energized work shall be performed only when justified under an EEWP.
5.4The PPE selection method governing this program shall be specified so that field workers do not mix methods on the same equipment.
Arc Flash PPE Selection Methodradio
Incident Energy Analysis Method (IEEE 1584-2018)
PPE Category Method (NFPA 70E Table 130.5(G))
5.5Where the incident energy analysis method is used, PPE shall be selected from the incident energy (cal/cm²) at the working distance, not from a category number.
NOTE The PPE category number (1 through 4) and the incident energy value in cal/cm² are not interchangeable. When a study reports incident energy, the field selection is made against the actual calculated value at the labeled working distance. Treating a 12 cal/cm² result as "Category 2 because it is over 8" misreads the methods and can under-protect the worker. (5.6)
5.7The PPE category method shall not be applied to any task or equipment not covered by NFPA 70E Table 130.5(G).
NOTE The category table covers a defined set of equipment types, voltages, available fault currents, and clearing times. Tasks or equipment outside those parameters - including many medium-voltage configurations and any equipment whose fault current or clearing time exceeds the table's stated limits - have no valid category entry. Such tasks require the incident energy analysis method. Defaulting the whole facility to the category table without checking coverage is a common and dangerous error. (5.8)
5.9Tasks with calculated incident energy exceeding 40 cal/cm² shall not be performed energized.
5.10The available incident energy threshold shall be defined consistently with the arc flash boundary, the distance at which incident energy equals 1.2 cal/cm².
NOTE 1.2 cal/cm² is the onset of a second-degree burn on unprotected skin. The arc flash boundary marks where a worker without arc-rated protection would receive that exposure during an arc event, and is calculated per IEEE 1584-2018 for each equipment location. (5.11)

6 Approach Boundaries and Labeling

6.1Each piece of equipment likely to require examination, adjustment, servicing, or maintenance while energized shall bear an arc flash warning label.
6.2Arc flash labels shall display all of the required fields so that the worker can select boundaries and PPE without consulting the study report at the equipment.
NOTE NEC 110.16(B), added for industrial occupancies in the 2023 NEC, makes the label more prescriptive than the prior general-warning-only requirement. The label must carry the data the worker needs at the point of work: nominal voltage, the arc flash boundary, the incident energy or required PPE, the working distance the incident energy was calculated at, the available short-circuit current, and the protective device clearing time. A label missing the working distance is non-compliant because the incident energy is only valid at that distance. (6.3)
6.4Arc flash labels shall include the fields configured below at minimum.
Arc Flash Label Required Fieldscheckbox
Nominal system voltage
Arc flash boundary distance
Incident energy (cal/cm²) or PPE category
Working distance
Available short-circuit current
Protective device clearing time
Limited approach boundary
Restricted approach boundary
6.5Arc flash labels shall conform to ANSI Z535.4 signal-word, color, and format conventions.
6.6The arc flash boundary, the limited approach boundary, and the restricted approach boundary shall all be established for each energized work task.
Approach Boundaries Established Per Taskcheckbox
Arc flash boundary
Limited approach boundary
Restricted approach boundary
NOTE The limited approach boundary is the distance from an exposed energized conductor within which a shock hazard exists. (6.7)
6.8Unqualified persons shall not cross the limited approach boundary unescorted.
NOTE The restricted approach boundary is the distance within which shock protection techniques and equipment are required. (6.9)
6.10Only qualified persons are permitted inside the restricted approach boundary.
6.11Arc flash labels shall not be finalized or installed until the short-circuit study, protective device coordination study, and arc flash calculations are complete.
NOTE A label can only be printed once the incident energy and boundaries are known, and those depend on the upstream studies in Arc Flash Study and Short Circuit Study. Installing placeholder or pre-study labels creates a false sense of compliance and exposes workers to wrong PPE selections. Label production is therefore sequenced after the study, not concurrent with equipment delivery. (6.12)
6.13Arc flash labels shall be replaced whenever the arc flash study is revised.
NOTE Labels derived from a superseded study are non-compliant the moment the study changes, because the incident energy, boundary, or clearing time the worker relies on no longer matches the installed system. The program must tie label replacement to the study update cycle so a system change never leaves stale labels in service. Label graphics, fonts, and materials beyond arc flash content are governed by Equipment Labeling. (6.14)

7 Energized Electrical Work Permit

7.1Energized work shall be performed only under an approved Energized Electrical Work Permit, except for the limited testing, troubleshooting, and voltage-measurement tasks that NFPA 70E permits without one.
7.2An EEWP shall be justified only where de-energizing introduces additional or increased hazards, or is infeasible due to equipment design or operational limitations; convenience shall not be accepted as justification.
NOTE NFPA 70E 130.2 sets a strict justification standard. "It would take too long to shut down" or "the schedule does not allow an outage" are not acceptable. The justification must be safety- or feasibility-based: interrupting life-support or critical ventilation, a continuous process that cannot be interrupted without greater hazard, or equipment that genuinely cannot be tested de-energized. The permit forces that justification to be written down and approved before work, not asserted after. (7.3)
7.4A second qualified person shall be present for all justified energized work performed under an EEWP.
NOTE The 2024 edition of NFPA 70E requires a second qualified person for energized work under a permit, both to assist with the task and to be positioned to release emergency response if an incident occurs. Programs written to earlier editions omit this and must be updated. The second person is a permit condition, not a discretionary addition. (7.5)
7.6The EEWP shall document the scope of work, the justification, the results of the shock and arc flash risk assessment, the boundaries, the required PPE, and the approvals required before work begins.
EEWP Required Contentcheckbox
Description and scope of energized work
Justification for energized work
Shock and arc flash risk assessment results
Approach and arc flash boundaries
Required PPE by category or incident energy
Job briefing completed and documented
Authorizing signatures
7.7A job briefing covering the hazards, procedures, special precautions, and emergency response shall be conducted and documented before energized work begins.

8 Lockout/Tagout Program

8.1The program shall include a written lockout/tagout procedure establishing the energy control steps required to place equipment in an electrically safe work condition.
NOTE LOTO is the default path to safe work and the alternative the EEWP justification is measured against. The written procedure defines, for each equipment category, where energy is isolated, how it is locked and tagged, how stored energy is released, and how the absence of voltage is verified before work. NFPA 70E Article 120 and OSHA 1910.147 both require a written, equipment-specific procedure rather than a generic notice. (8.2)
8.3The construction-phase LOTO procedure shall reference OSHA 29 CFR 1926.417, not only the general-industry 1910.147 requirements.
NOTE The construction standard differs from general industry. 1926.417 requires circuits to be rendered inoperative and tagged at all points of energization during construction work; its requirements are not identical to 1910.147. A specification that copies general-industry LOTO language verbatim without the construction citation leaves a gap during the build phase, when much of the energized-adjacent work actually occurs. (8.4)
8.5The written LOTO procedure shall, at minimum, establish the energy control elements configured below.
LOTO Procedure Elementscheckbox
Equipment categories covered
Sequence of isolation steps
Stored-energy release and verification
Absence-of-voltage test before contact
Individual lock and tag application
Group lockout procedure for multi-craft work
Lock and tag removal and re-energization steps
8.6The program shall include a group lockout procedure for work in which more than one worker or more than one craft is on the same equipment simultaneously.
NOTE A single-person LOTO procedure is insufficient when several contractors work the same equipment at once, because any one worker removing a lock could re-energize the circuit on the others. Group lockout - a lockout box or hasp that holds every affected worker's individual lock, with no single person able to release the energy alone - is required wherever multi-craft or multi-contractor work overlaps on one piece of equipment. (8.7)
8.8The absence of voltage shall be verified with an adequately rated, tested instrument before any worker contacts a conductor presumed de-energized.
8.9The voltage-testing instrument shall be checked against a known energized source immediately before and after the absence-of-voltage test.
8.10Periodic inspection of the energy control procedure shall be performed at least annually.
NOTE OSHA 1910.147(c)(6) requires the employer to inspect each energy control procedure at least annually to verify that workers are following it and that the procedure remains adequate. The inspection is documented and identifies the procedure, the workers included, and the inspector. On long-duration construction this falls within the project; the program must schedule it rather than assume the facility's annual cycle covers project-specific procedures. (8.11)
LOTO Periodic Inspection Intervalselect
Annually (OSHA minimum)
Semiannually
Quarterly

9 Personal Protective Equipment

9.1Arc-rated PPE shall be selected for each task from the incident energy at the working distance or, where the category method applies, from the required PPE category.
9.2All garments and equipment specified as arc protection shall carry a documented arc rating; flame-resistant clothing without an arc rating shall not be accepted as arc protection.
NOTE Arc-rated and flame-resistant (FR) are not synonyms. All arc-rated clothing is FR, but not all FR clothing has been tested and assigned an arc thermal performance value (ATPV) or breakopen threshold (EBT). Specifying "any FR clothing" without a minimum arc rating per category permits garments that have never been arc-tested. Each garment must carry a documented cal/cm² rating meeting or exceeding the category minimum. (9.3)
9.4PPE shall be stocked by category so that the minimum arc rating required for each category is available before work begins.
PPE Categories Stocked On Sitecheckbox
Category 1 - minimum 4 cal/cm² arc rating
Category 2 - minimum 8 cal/cm² arc rating
Category 3 - minimum 25 cal/cm² arc rating
Category 4 - minimum 40 cal/cm² arc rating
9.5Category 1 PPE shall provide a minimum arc rating of 4 cal/cm², comprising arc-rated shirt and pants or coverall, safety glasses, hearing protection, hard hat, and leather gloves.
9.6Category 2 PPE shall provide a minimum arc rating of 8 cal/cm², adding an arc-rated balaclava and face shield or arc flash hood.
NOTE Category 2 is the most common configuration for commercial panelboard and MCC work. (9.7)
9.8Category 3 PPE shall provide a minimum arc rating of 25 cal/cm², comprising an arc flash suit jacket and pants, arc flash hood, and insulating rubber gloves with leather protectors.
9.9Category 4 PPE shall provide a minimum arc rating of 40 cal/cm², comprising a multi-layer arc flash suit, full arc flash hood, and Class 0 or Class 00 insulating rubber gloves with leather protectors.
9.10All personnel within the arc flash boundary shall wear hearing protection.
NOTE The 2024 edition of NFPA 70E requires hearing protection for everyone inside the arc flash boundary, recognizing that the acoustic energy of an arc blast can cause hearing damage independent of the thermal hazard. This applies to observers and assistants within the boundary, not only the worker on the equipment. (9.11)
9.12Insulating rubber gloves shall be tested and certified at intervals not exceeding the configured period.
Insulating Glove Test Intervalselect
6 months
12 months
9.13Arc-rated flame-resistant clothing shall be laundered in accordance with the manufacturer's instructions; processes or additives that degrade the arc rating shall not be used.
NOTE Chlorine bleach, fabric softeners, and high-temperature industrial laundering can strip or mask the flame-resistant treatment of arc-rated garments, reducing the arc rating without any visible change. The program must specify laundering that preserves the rating and prohibit consumer additives that compromise it. (9.14)
9.15Voltage-rated insulated hand tools conforming to IEC 60900 (1000 V AC) shall be used for any task requiring contact with or proximity to energized conductors.
9.16Voltage testers and clamp meters shall be rated CAT III or CAT IV per IEC 61010 for the circuit on which they are used.

10 Training

10.1Every qualified person shall complete documented electrical safety training before being assigned work on or near energized equipment.
10.2Training shall cover hazard recognition, the boundaries, the risk assessment procedure, the selection and use of PPE, LOTO, and emergency response including release of energized victims and CPR.
NOTE OSHA 1910.332 and NFPA 70E both make training the foundation of qualified-person status. The content must be specific to the hazards the worker faces and the equipment worked, and must include emergency response, because the person best positioned to act after an arc or shock incident is the trained co-worker already on site. (10.3)
10.4Workers shall be retrained at intervals not exceeding the configured period, and whenever the program changes, an audit reveals deficiencies, or new equipment or procedures are introduced.
Retraining Intervalselect
1 year
2 years
3 years
10.5Training records shall document each worker's name, the training content, the dates of training and retraining, and the means used to verify competency.
10.6Training records shall be retained for the configured period and made available on request.
Training Record Retentionselect
Duration of employment plus 3 years
Duration of employment plus 1 year
3 years

11 Program Review and Maintenance

11.1The arc flash study and the labels and PPE assignments derived from it shall be reviewed at intervals not exceeding the configured period, or whenever a system change affects available fault current or protective device clearing time, whichever occurs first.
Arc Flash Study Review Intervalselect
5 years (NFPA 70E maximum)
3 years
1 year
11.2Any modification that changes available fault current, protective device settings, or clearing time shall trigger re-evaluation of the affected arc flash study results and replacement of the affected labels.
NOTE A new transformer, an upgraded service, a relay setting change, or a breaker replacement can move incident energy and boundaries up or down. The five-year interval is a ceiling, not a license to ignore changes within it. Equipment maintenance condition, addressed in NFPA 70B, also affects clearing time: a breaker that no longer clears in its rated time raises incident energy even with no design change. The program ties re-evaluation to the change, not only to the calendar. (11.3)
11.4The overall electrical safety program shall be audited at intervals not exceeding three years to verify that the program is being followed and remains current with the adopted edition of NFPA 70E.
11.5Contractor-submitted electrical safety programs shall be reviewed for equivalency with the Owner's program before the contractor performs energized-adjacent work.
NOTE An unreviewed contractor program creates a gap in site-wide coverage: the contractor may use different boundaries, different PPE assignments, or a weaker LOTO procedure than the facility requires. The equivalency review confirms the contractor's program meets or exceeds the Owner's on every element of this standard, or directs the contractor to work under the Owner's program instead. Acceptance testing and energization of the installed equipment remain governed by Electrical Acceptance Testing. (11.6)

12 Delivery, Storage, and Handling

12.1Arc-rated clothing, hoods, insulating gloves, and insulated tools shall be stored in clean, dry conditions that protect them from contamination, ultraviolet degradation, and physical damage.
12.2Insulating rubber gloves shall be stored in their protective bags and shall not be folded inside-out or compressed.
12.3Insulating rubber gloves shall be inspected for damage before each use.
12.4PPE that has been exposed to an arc event, contaminated, or damaged shall be removed from service and not returned to use until inspected and, where required, re-tested or replaced.

13 Spare Parts

13.1The Contractor shall maintain spare arc-rated garments, hoods, and insulating gloves sufficient to keep the required PPE categories available while items are out for laundering, testing, or replacement.
13.2Spare arc flash labels and label stock shall be retained so that labels damaged or made illegible in service can be replaced without delaying work.

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Electrical Safety Program." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/electrical-safety-program — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.