SynC · Editorial revision

Dry-Pipe Fire Sprinkler Systems

Revision8
EditedSep 14, 2026
StatusCurrent
Contents

View changes in this revision   Revision history

Current revision. This is editorial revision 8, the current text of this standard. Read it on the standard's page.

Remake for template neutrality (from-scratch field inventory, five-state defaults, parameters and derived fields, schedule deferrals)

1 Scope

NOTE This standard covers the dry-pipe valve, the quick-opening device, the supervisory gas supply and its pressures, water delivery time, pitch and drainage, interior corrosion mitigation, refrigerated-space provisions, and the acceptance tests specific to an automatic dry-pipe sprinkler system. (1.1)
NOTE In a dry-pipe system the piping downstream of the dry-pipe valve holds pressurized air or nitrogen instead of water. When a sprinkler opens, the supervisory gas escapes, the pressure differential that held the valve clapper closed collapses, and water enters the piping and flows to the open sprinkler after the gas ahead of it has been expelled. (1.2)
NOTE This standard is the dry-pipe layer over Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems. The family standard establishes how a sprinkler system is classified, sized, supplied, valved, supported, tested, spared, and warranted; this standard establishes what changes when the piping is dry: the valve that keeps it dry, the gas that supervises it, the delay before water arrives, the water that stays behind, and the tests that prove all of it. (1.3)
1.4 Dry-pipe systems furnished under this standard shall also comply with Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems.
1.5 Where a requirement of this standard and a requirement of Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems address the same subject, the requirement of this standard shall govern.
1.6 Hazard classification, design density and area, water supply verification, sprinkler selection and temperature rating, control valve supervision, hangers and seismic bracing, hydrostatic testing, spare sprinklers, and warranty for systems furnished under this standard shall be as required by Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems.
1.7 Pipe, fittings, and joints for systems furnished under this standard shall be as required by Fire Protection PipingFire Protection Piping and SpecialtiesResolves to the current adopted revision.sync/fire-protection-piping.
1.8 The extent of each dry-pipe system and the location of each dry-pipe valve shall be as indicated on the fire protection plans and riser diagram.
1.9 Dry piping shall be used where the sprinkler piping cannot be maintained at or above 40°F (4°C), and wet piping shall be used elsewhere unless the Contract Documents direct otherwise.
NOTE Freezing exposure can also be met by an antifreeze system within the limits NFPA 13 sets for it, by listed heat-tracing with insulation, or by moving the piping into heated space. A dry system delays water, increases the design area, adds an air supply and a valve that need continual attention, and corrodes from the inside faster than a wet system; the alternatives avoid those costs where their own limits are not exceeded. (1.10)
NOTE The following are outside the scope of this standard: (1.11)
  • Pre-action and deluge systems, which hold dry piping but admit water on a detection signal rather than on the loss of supervisory pressure, and which are covered by Pre Action And Deluge Sprinkler SystemsPre-Action and Deluge Sprinkler SystemsResolves to the current adopted revision.sync/pre-action-and-deluge-sprinkler-systems
  • Antifreeze systems and listed heat-tracing, which protect piping against freezing while keeping it filled with liquid
  • Standpipes and hose connections, which are covered by Standpipe SystemsStandpipe SystemsResolves to the current adopted revision.sync/standpipe-systems
  • Fire pumps and the pressure they add to the supply, which are covered by Fire PumpsFire PumpsResolves to the current adopted revision.sync/fire-pumps
  • The fire department connection, its check valve, and its automatic drain, which are covered by Fire Department ConnectionsFire Department ConnectionsResolves to the current adopted revision.sync/fire-department-connections
  • The fire alarm control unit and the circuits that carry waterflow and supervisory signals, which are covered by Fire Alarm SystemsFire Alarm SystemsResolves to the current adopted revision.sync/fire-alarm-systems
  • A plant compressed air system that supplies more than the dry-pipe systems, which is covered by Compressed Air SystemsCompressed Air SystemsResolves to the current adopted revision.sync/compressed-air-systems
  • Dry systems protecting storage occupancies under the storage chapters of NFPA 13, whose in-rack, density, and delivery provisions are outside this standard

2 Referenced Standards

2.1 Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2 Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard Title
NFPA 13 Standard for the Installation of Sprinkler Systems
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm and Signaling Code
UL 260 Dry Pipe and Deluge Valves for Fire-Protection Service
UL 753 Alarm Accessories for Automatic Water-Supply Control Valves for Fire-Protection Service
UL 1486 Quick Opening Devices for Dry Pipe Valves for Fire-Protection Service
FM Global Data Sheet 2-0 Installation Guidelines for Automatic Sprinklers
FM Global Data Sheet 2-1 Corrosion in Automatic Sprinkler Systems
NOTE Successive editions of NFPA 13 have changed the volume thresholds, the water delivery table, the nitrogen provisions, and the corrosion provisions that govern a dry system, so the edition adopted by the Authority Having Jurisdiction settles which rule applies to a given project. (2.3)
2.4 The Contractor shall confirm the edition of NFPA 13 adopted by the Authority Having Jurisdiction before beginning the working drawings.

3 Submittals

3.1 Action Submittals

3.1.1 The Contractor shall submit the following for the Engineer of Record's review and return, together with the submittals required by Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems, before the dry-pipe valve, the supervisory gas supply, or the dry piping is procured:
  • Product data for the dry-pipe valve and its trim, identifying the listing, the size, the body and trim materials, the priming requirement, and the published trip pressure at each water supply pressure
  • Product data for the quick-opening device, where one is furnished, identifying the listing of the device with the dry-pipe valve it is installed on and the anti-flood provision
  • Product data for the supervisory gas source, identifying the compressor or nitrogen generator, its capacity, the air maintenance device, the dryer, the relief valve, and the electrical requirements
  • The calculated volume of each dry-pipe system
  • The water delivery time calculation for each system that is subject to the delivery time requirement, identifying the calculation method and the assumed supervisory pressure
  • The supervisory gas pressure calculation, stating the maximum water supply pressure at the valve, the published trip pressure, the margin applied, and the resulting normal pressure and low-pressure supervisory setpoint
  • The pitch and drainage plan, showing the direction of fall of every main and branch line, every trapped section, the volume of each trapped section, and the type and location of every auxiliary drain
  • Product data for the corrosion mitigation provided, identifying the pipe interior protection and, where nitrogen is used, the purity the generator produces and the purge provision
  • The refrigerated-space provisions, where dry piping serves a space held at or below 32°F, identifying the gas drying, the ice-plug inspection point, and the penetration seal
Action Submittals Requiredcheckbox
☑ Dry-pipe valve and trim product data
☐ Quick-opening device product data
☑ Supervisory gas source product data
☑ System volume calculation
☐ Water delivery time calculation
☑ Supervisory gas pressure calculation
☑ Pitch and drainage plan
☑ Corrosion mitigation product data
☐ Refrigerated-space provisions
3.1.2 The dry piping shall not be fabricated until the pitch and drainage plan has been reviewed and returned.
NOTE A dry system's routing is not free to change in the field the way a wet system's is. Every change moves the system volume, the delivery time, the trapped sections, and the auxiliary drain count together, so a run relocated around a duct after the plan was reviewed may have created a low point no one will drain. (3.1.3)

3.2 Closeout Submittals

3.2.1 The Contractor shall submit the following before the dry-pipe system is accepted, in addition to the closeout submittals required by Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems:
  • The trip test record for each dry-pipe valve, recording the supervisory pressure at the start, the pressure at which the valve tripped, the time from the opening of the inspector's test valve to the trip, and the time from the opening of the inspector's test valve to water at the test connection
  • The air leakage test record for each system, recording the starting pressure, the pressure after 24 hours, and the ambient temperature at each reading
  • The as-left supervisory gas pressure and the as-left low-pressure supervisory setpoint for each system
  • The nitrogen purity measured at the remote end of each system at the completion of purging, where nitrogen is the supervisory gas
  • An auxiliary drain register listing every auxiliary drain by location, type, and the section it drains
  • Operation and maintenance data covering the dry-pipe valve reset procedure, the supervisory gas supply, the auxiliary drain schedule, and the NFPA 25 test and inspection intervals that apply to a dry system
  • As-built drawings recording the installed pitch and drainage arrangement
Closeout Submittals Requiredcheckbox
☑ Trip test record
☑ Air leakage test record
☑ As-left supervisory pressure and setpoint
☐ Nitrogen purity record
☑ Auxiliary drain register
☑ Operation and maintenance data
☑ As-built drawings
NOTE The auxiliary drain register is the document a future operator drains the system from. A drum drip that is not on the register is not drained before the first freeze, and the pipe above it is the pipe that splits. (3.2.2)

4 Quality Assurance

4.1 The individual who prepares the working drawings and the water delivery time calculation shall have prepared the design of not fewer than three dry-pipe systems that were accepted by an Authority Having Jurisdiction.
4.2 Where the parties disagree whether the designer's experience meets that requirement, the Engineer of Record shall make the initial determination.
4.3 The dry-pipe valve, the quick-opening device, the air maintenance device, and the nitrogen generator shall be listed for fire protection service.
4.4 The quick-opening device shall be listed for use with the dry-pipe valve on which it is installed, and a device and a valve from different manufacturers shall not be combined unless the combination is covered by a listing.
NOTE The device and the valve are tested and listed as a pair because the device works by sensing the rate of pressure drop and venting the intermediate chamber of one particular valve body. On a valve it was not listed with, the device can trip too early, too late, or flood itself. (4.5)
4.6 Where the Owner's property insurer requires it, the components named in this standard shall carry the insurer's approval in addition to the listing, in accordance with Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems.

5 System Volume and Water Delivery Time

5.1 System Volume

5.1.1 The volume of each dry-pipe system shall be calculated from the working drawings and stated in the action submittal.
NOTE System volume is the quantity that sets every other dry-pipe decision. It fixes how much gas must escape before water reaches a sprinkler, how large the supervisory gas supply must be, whether the delivery time must be calculated and tested, and whether a quick-opening device is needed. (5.1.2)
5.1.3 The volume of a single dry-pipe system shall not exceed the volume indicated in the datasheet.
Maximum Volume of a Single Dry-Pipe Systemrange
gal
5007501000150020003000
NOTE NFPA 13 exempts a system of not more than 500 gal, and a system of not more than 750 gal that has a quick-opening device, from the water delivery time requirement, and permits a larger system where its delivery time is demonstrated by calculation and confirmed by test. A project or an insurer may hold the volume below the calculated ceiling to keep the delivery time short or to keep the exemption, and a project protecting one large unheated volume may need the ceiling. (5.1.4)
5.1.5 Where the volume of a dry-pipe system as drawn would exceed the datasheet value, the Contractor shall subdivide the system into additional dry-pipe systems, each with its own dry-pipe valve, and shall report the subdivision to the Engineer of Record before the working drawings are submitted.

5.2 Water Delivery Time

5.2.1 Water shall reach the inspector's test connection at the most remote point of each dry-pipe system within the time indicated in the datasheet, measured from the full opening of the inspector's test valve with the system at its normal supervisory pressure.
Water Delivery Time Limitrange
s
1540455060
Derived — the hazard classification selected for the protected area under the sprinkler family standard and the calculated system volume, applied to the dry system water delivery table of NFPA 13 (by default)
NOTE The NFPA 13 delivery table assigns a shorter time to a higher hazard because the design area is already enlarged to cover the delay, and a fire in a high-hazard occupancy outgrows even the enlarged area if water is late. A system below the exempt volume has no delivery time requirement at all, and the limit indicated here applies only where the volume exceeds the exemption. (5.2.2)
5.2.3 Where the system volume exceeds the exemption, the delivery time shall be demonstrated by a calculation using a method acceptable to the Authority Having Jurisdiction, and the calculation shall assume the supervisory pressure the system will actually be held at.
NOTE A delivery calculation run at a lower supervisory pressure than the system is set to is optimistic, because the valve trips sooner from a lower starting pressure and less gas has to leave the pipe before water arrives. (5.2.4)
5.2.5 The calculated delivery time shall be confirmed by the trip test required under Testing, and the tested time shall govern acceptance.

5.3 Quick-Opening Device

5.3.1 The quick-opening device furnished at each dry-pipe valve shall be as indicated in the datasheet.
Quick-Opening Deviceselect
None
Accelerator
Exhauster
NOTE An accelerator senses the rate of pressure drop when a sprinkler opens and vents the intermediate chamber of the dry-pipe valve, so the clapper releases before the system pressure has fallen to the trip point on its own. An exhauster instead vents the system gas to atmosphere through a large port ahead of the water, shortening the time to expel the gas rather than the time to trip. Accelerators are the device manufacturers now list with their valves; exhausters remain in service on existing systems and are procurable for some valve models. (5.3.2)
5.3.3 Where the calculated delivery time without a quick-opening device exceeds the datasheet limit, a quick-opening device shall be provided or the system shall be subdivided until the limit is met.
5.3.4 Where an accelerator is furnished, it shall include the anti-flood provision the listing requires, so that water entering the system after the trip cannot reach the accelerator internals.
NOTE A quick-opening device shortens the delivery time but does not remove the delay, and the design area increase NFPA 13 applies to a dry system is not reduced because a device is installed. (5.3.5)

6 Dry-Pipe Valve and Trim

6.1 Dry-Pipe Valve

6.1.1 The dry-pipe valve type shall be as indicated in the datasheet.
Dry-Pipe Valve Typeradio
○ Differential dry-pipe valve
○ Low-differential dry-pipe valve
NOTE A differential valve holds its clapper closed with a large air-side area against a small water-side area, so a supervisory pressure of a fraction of the water pressure keeps it seated; a low-differential valve holds with a mechanical latch or a smaller area ratio and is held at a supervisory pressure closer to the water pressure. The differential valve needs less gas and a smaller supply; the low-differential valve trips from a smaller pressure loss and pairs with a nitrogen supply that is already sized to hold the higher pressure. (6.1.2)
6.1.3 The dry-pipe valve size shall be as indicated in the datasheet.
Dry-Pipe Valve Sizerange
in.
22.53468
Per drawings — the fire protection riser diagram (deferred by default)
6.1.4 The dry-pipe valve body material shall be as indicated in the datasheet.
Dry-Pipe Valve Body Materialselect
Cast iron
Ductile iron
Manufacturer's standard (by default)
6.1.5 The dry-pipe valve shall be installed with the manufacturer's listed trim, and the trim shall not be assembled in the field from components that are not part of the listing.
6.1.6 Where the valve listing calls for priming water, the trim shall include the priming water connection, the priming level test valve, and a means to confirm the priming level without opening the valve.
6.1.7 The trim shall include a water-side pressure gauge and a gas-side pressure gauge, each readable from the floor of the valve enclosure.
6.1.8 The trim shall include a drain for the intermediate chamber, arranged so that the chamber can be confirmed dry before the valve is reset.
NOTE An intermediate chamber that is not drained before reset holds the valve off its seat, and the valve either fails to reset or trips the moment the supply is reopened. The drain and its sight connection are what let the technician confirm the chamber state instead of guessing at it. (6.1.9)
6.1.10 The main drain shall discharge where a full-flow trip test can be run without damage to the building.
6.1.11 The fire department connection shall enter the system on the system side of the dry-pipe valve clapper, and the connection, its check valve, and the automatic drain between the check valve and the dry-pipe valve shall be as required by Fire Department ConnectionsFire Department ConnectionsResolves to the current adopted revision.sync/fire-department-connections.
6.1.12 The fire department connection sign shall identify the connection as serving a dry-pipe system.

6.2 Valve Enclosure

6.2.1 The dry-pipe valve, its trim, its supply piping, and the supervisory gas source shall be located in an enclosure that is maintained at not less than the temperature indicated in the datasheet.
Valve Enclosure Minimum Temperaturerange
°F
4045505560
6.2.2 The means of heating the valve enclosure shall be as indicated in the datasheet.
Valve Enclosure Heatingselect
Heated room of the building
Dedicated electric unit heater in the valve enclosure
Hydronic or steam unit heater in the valve enclosure
Listed insulated and heated valve enclosure
NOTE The water side of the dry-pipe valve is full, and the trim carries priming water and drain water, so the valve is a wet component that has to live in heated space even though everything downstream of it is dry. A valve enclosure that shares the building's heating is only as reliable as that heating; a dedicated heater is only as reliable as its circuit; a listed heated enclosure trades both for a cabinet with its own thermostat and its own supervision. (6.2.3)
6.2.4 The valve enclosure shall provide clearance to operate every trim valve, read every gauge, service the supervisory gas source, and remove the valve cover for internal inspection.
6.2.5 The valve enclosure shall be provided with a floor drain or an exterior discharge sized for the main drain flow.

7 Supervisory Gas Supply

7.1 Supervisory Gas Source

7.1.1 The supervisory gas source for each dry-pipe system shall be as indicated in the datasheet.
Supervisory Gas Sourceselect
Dedicated riser-mounted air compressor
Dedicated tank-mounted air compressor
Plant compressed air system through an air maintenance device
Membrane nitrogen generator
Pressure-swing adsorption nitrogen generator
Nitrogen cylinders through a pressure regulator
NOTE The supervisory gas is either air or nitrogen, and the source selected fixes which. Air is the gas a compressor supplies and the gas that oxidizes the pipe interior; nitrogen displaces the oxygen and is supplied by a generator that separates it from compressed air on site or by cylinders that are exchanged. (7.1.2)
NOTE A dedicated compressor runs only when the dry system needs gas, draws from the heated enclosure, and stops when its own pressure switch is satisfied. A plant air system supplies gas at plant pressure, carries whatever oil and moisture the plant's own conditioning leaves in it, and is unavailable whenever the plant compressor is down for maintenance or the plant is shut down. Where the plant air is dried and filtered to the condition the sprinkler system needs and is kept in service through building shutdowns, it removes a compressor from the valve room; where it is not, the dry system inherits the plant's oil, water, and outages. (7.1.3)
NOTE A membrane generator separates nitrogen continuously with no moving parts beyond its feed compressor and suits a system that leaks slowly and needs a steady trickle; a pressure-swing adsorption generator produces higher purity from a smaller feed and cycles between beds. Cylinders supply no purity risk and no electrical load, and run out, so they suit a small system, a temporary installation, or a site where a purity-supervised cylinder bank is exchanged on a schedule. (7.1.4)
7.1.5 Where the supervisory gas source is a plant compressed air system, the connection to the dry-pipe system shall pass through a listed air maintenance device and a check valve, and the plant air shall be dried and filtered to the condition required under this standard before it enters the device.
7.1.6 Where the supervisory gas source serves more than one dry-pipe system, each system shall be connected through its own listed air maintenance device and check valve, so that a trip on one system does not depressurize the others.
NOTE An air maintenance device restricts the rate at which gas enters the system, so that a leak large enough to trip the valve is not masked by a supply large enough to keep up with it. A supply piped directly to the system without the restriction turns every leak into a pressure the valve never sees. (7.1.7)
7.1.8 The supervisory gas supply shall be provided with a listed relief valve, set not higher than the pressure rating of the system components, in accordance with NFPA 13.
7.1.9 The compressor or nitrogen generator shall be supplied from a dedicated branch circuit identified at the panelboard as serving the fire sprinkler supervisory gas supply, and the circuit shall comply with NFPA 70.
7.1.10 Where the supervisory gas source is a nitrogen generator, the generator shall be listed for the purpose, and the feed compressor, filtration, and separation module shall be furnished as the listed assembly.

7.2 Supervisory Gas Pressure

7.2.1 The normal supervisory gas pressure of each dry-pipe system shall be as indicated in the datasheet.
Supervisory Gas Pressurerange
psi
101520253035404550607080
Derived — the trip pressure of the selected dry-pipe valve at Site Water Supply Pressure MaximumSite Water Supply Pressure MaximumParameterEach project supplies its own value.site-water-supply-pressure-maximum, or at the fire pump churn pressure where a pump serves the system, plus the margin of 20 psi or the valve manufacturer's published margin, whichever governs under NFPA 13 (by default)
NOTE The supervisory pressure is bounded on both sides. Below the trip pressure plus its margin, a supply pressure surge or a fire pump start trips the valve with no fire; above what the margin requires, the surplus gas lengthens the delivery time by the volume it occupies at that pressure, and every psi of surplus is a psi the leak has to bleed before the valve responds to an open sprinkler. (7.2.2)
7.2.3 The supervisory pressure shall not be raised above the datasheet value to compensate for leakage.
7.2.4 The low-pressure supervisory switch setpoint of each dry-pipe system shall be as indicated in the datasheet.
Low-Pressure Supervisory Setpointrange
psi
510152025303540506070
Derived — the supervisory gas pressure and the trip pressure of the selected dry-pipe valve, set between them at the margin above the trip pressure the valve manufacturer publishes (by default)
7.2.5 Each dry-pipe system shall be provided with a listed low-pressure supervisory switch that transmits a supervisory signal to the fire alarm system when the supervisory gas pressure falls to the setpoint, in accordance with NFPA 72 and Fire Alarm SystemsFire Alarm SystemsResolves to the current adopted revision.sync/fire-alarm-systems.
7.2.6 The additional supervisory signals provided for each dry-pipe system shall be as indicated in the datasheet.
Additional Supervisory Signalscheckbox
☐ High supervisory gas pressure
☐ Valve enclosure low temperature
☐ Air compressor fault or excessive run time
☐ Nitrogen generator trouble or low purity
NOTE A high-pressure signal reports a failed regulator or a stuck air maintenance device, which raises the delivery time without any other symptom. A run-time signal reports a leak by the compressor working to keep up with it, which is the earliest sign a system gives. (7.2.7)

7.3 Air Supply Capacity and Conditioning

7.3.1 Requirements in this article apply where the supervisory gas is supplied by an air compressor or by the feed compressor of a nitrogen generator.
7.3.2 The air supply shall restore a dry-pipe system from atmospheric pressure to its normal supervisory pressure within the time indicated in the datasheet.
Air Supply Restoration Timerange
minutes
10152030
NOTE NFPA 13 requires the automatic supply to restore normal pressure within 30 minutes. A shorter time returns the system to service sooner after a trip test or a trip, at the cost of a larger compressor and, through the air maintenance device, no faster fill on a system that has a leak. (7.3.3)
7.3.4 The capacity of the air supply shall be as indicated in the datasheet.
Air Supply Capacityrange
cfm
0.511.523457.510152030
Derived — the calculated system volume, the supervisory gas pressure, and the restoration time indicated in the datasheet, applied to the compressor sizing method of NFPA 13 or the manufacturer's published sizing (by default)
7.3.5 The compressor shall draw its intake from the heated valve enclosure or from another heated interior space, unless the supervisory gas drying indicated in the datasheet is provided downstream of the compressor.
NOTE The moisture a compressor takes in leaves the receiver as vapor and condenses in the first cold pipe it reaches. Air drawn from a heated room carries less water per cubic foot than air drawn from a humid summer exterior, and it carries none of the winter condensation that an intake in the cold space itself produces. (7.3.6)
7.3.7 The supervisory gas drying provided shall be as indicated in the datasheet.
Supervisory Gas Dryingselect
None
Refrigerated air dryer
Desiccant air dryer
Membrane air dryer
Derived — the pressure dew point needed to keep condensate from forming in the coldest space the dry piping serves (by default)
7.3.8 Where any part of the dry piping serves a space held at or below 32°F, the supervisory gas shall be dried to a pressure dew point below the lowest temperature of that space.
7.3.9 Where the supervisory gas source is a plant compressed air system, the drying and filtration of the plant air shall be confirmed against the datasheet value, and additional drying shall be provided at the connection where the plant air does not meet it.
7.3.10 The air supply shall be provided with a coalescing filter that removes compressor oil before the gas enters the system.

7.4 Nitrogen Supply

7.4.1 Requirements in this article apply where the supervisory gas is nitrogen.
7.4.2 The nitrogen purity maintained in the system shall be not less than the value indicated in the datasheet, measured at the remote end of the system.
Nitrogen Purity at the Systemrange
%
959899
NOTE The corrosion credit NFPA 13 and FM Global Data Sheet 2-1 give a nitrogen-supervised system rests on the oxygen concentration being held low enough that the pipe interior does not corrode at a rate that matters, and 98 percent nitrogen is the purity those documents describe. A higher purity costs generator capacity and purge time and buys a smaller further reduction in oxygen. (7.4.3)
7.4.4 The purge provision by which the initial air charge is displaced shall be as indicated in the datasheet.
Nitrogen Purge Provisionselect
Listed automatic purge vent at the remote end of each system
Manual purge valve at the remote end of each system
Purge through the inspector's test connection
NOTE A system filled with nitrogen from a generator still holds the air it was tested with, and the nitrogen reaches the datasheet purity only as that air is vented at the far end while the generator makes up the loss. An automatic vent runs the purge unattended over the days it takes and closes on purity or on a trip; a manual valve does the same work on someone's schedule; the test connection does it only while a technician stands at it. (7.4.5)
7.4.6 The system shall be purged after the air leakage test and after every subsequent trip or drain-down until the purity at the remote end reaches the datasheet value, and the purity shall be recorded.
7.4.7 Where nitrogen is the supervisory gas, the low-pressure supervisory switch, the relief valve, the air maintenance device, and the gauges shall be as required for air under this standard.

8 Interior Corrosion Mitigation

NOTE A dry system corrodes from the inside faster than a wet system because its interior is wetted and dried repeatedly, with water left standing at every low point and oxygen supplied continuously by the gas above it. The wet-and-dry line at each puddle is where oxygen pitting concentrates, and the same standing water is where microbiologically influenced corrosion establishes. (8.1)
8.2 The interior corrosion protection of the dry piping shall be as indicated in the datasheet.
Dry Piping Interior Corrosion Protectionselect
Black steel, uncoated interior
Galvanized steel
Internally coated steel
Stainless steel
NOTE Galvanizing protects the interior by sacrificial zinc, which holds until the zinc is consumed and then leaves bare steel; where the zinc is damaged at threads or where water stands, the exposed steel pits faster than it would in an ungalvanized pipe, because the surrounding zinc drives the attack to the bare spot. Black steel supervised with nitrogen has no oxygen to feed general corrosion or pitting and is the combination FM Global Data Sheet 2-1 describes for a new dry system. Black steel supervised with air corrodes at the rate the standing water and the oxygen supply allow, which is the condition that produced the service history the other options answer. An internal coating or stainless steel removes the steel from contact with the water at a material cost that a large system or a corrosive supply may justify. (8.3)
8.4 The pipe finish and material selected for the dry piping under Fire Protection PipingFire Protection Piping and SpecialtiesResolves to the current adopted revision.sync/fire-protection-piping shall be consistent with the interior corrosion protection indicated in the datasheet.
8.5 Where galvanized pipe is selected, fittings and couplings on the dry piping shall be galvanized, and field-cut threads and welds shall be restored with a cold-galvanizing compound before the joint is made up.
NOTE A black fitting on a galvanized pipe puts bare steel at the threaded joint, which is the location where water stands last and drains least, so the one unprotected component sits at the one place the protection was most needed. (8.6)
8.7 Pipe used on the dry piping shall carry a listing for dry-pipe service where the pipe is of a wall thickness lighter than Schedule 40 or is of a nonmetallic material.
NOTE Pipe listed for wet service only is listed on the assumption that its interior stays wet and its exterior stays warm. Light-wall steel corrodes through sooner in a wet-and-dry interior, and a nonmetallic pipe that is not listed for dry service has not been tested for the drying, the cold, or the pressure surge of a trip. (8.8)

9 Pitch and Drainage

9.1 Pitch

9.1.1 Dry piping shall be pitched to drain to the dry-pipe valve or to an auxiliary drain, with branch lines pitched not less than the value indicated in the datasheet.
Minimum Branch Line Pitchrange
in. per 10 ft
0.511.52
9.1.2 Mains shall be pitched not less than the value indicated in the datasheet.
Minimum Main Pitchrange
in. per 10 ft
0.250.50.751
NOTE The datasheet defaults are the NFPA 13 minimums for a dry system. A steeper pitch drains faster and leaves less water behind after a trip, at the cost of headroom lost across a long run and more hanger elevations to set. (9.1.3)
9.1.4 Mains serving a space held at or below 32°F shall be pitched not less than 1/2 in. per 10 ft regardless of the datasheet value.
9.1.5 The pitch of every main and branch line shall be verified with a level as the piping is hung and before the ceiling below it is closed.
NOTE Pipe that reads level on the plan and sags between hangers holds water in each sag, and the sag is invisible once the ceiling is up. Verifying pitch at every section while it is still open is the only time the correction is inexpensive. (9.1.6)

9.2 Auxiliary Drains

9.2.1 An auxiliary drain shall be provided at every section of dry piping that cannot drain to the dry-pipe valve by gravity.
9.2.2 The locations of auxiliary drains shall be as indicated on the pitch and drainage plan.
9.2.3 The auxiliary drain for a trapped section holding more than 5 gal shall be as indicated in the datasheet.
Auxiliary Drain for Trapped Sections Over 5 galradio
● Two-valve drum drip
○ Listed automatic auxiliary drain
NOTE A drum drip holds the water that collects in its condensate nipple between an upper valve and a lower valve, and is emptied by closing the upper valve, opening the lower, closing the lower, and reopening the upper, so that the system is never open to atmosphere. An automatic drain does the same on a float without an operator, and adds a device with its own listing, its own leak path, and its own maintenance. (9.2.4)
9.2.5 A two-valve drum drip shall consist of two 1 in. valves and a 2 in. by 12 in. condensate nipple, or the equivalent arrangement NFPA 13 permits.
9.2.6 The auxiliary drain for a trapped section holding not more than 5 gal shall be a valve of not less than 1/2 in. with a plug or a nipple and cap, in accordance with NFPA 13.
9.2.7 Auxiliary drains shall be located so that they can be operated from the floor or from a portable ladder without removal of permanent construction, and access panels shall be provided at auxiliary drains above finished ceilings.
9.2.8 Each auxiliary drain shall be identified with a permanent sign stating that it is a sprinkler auxiliary drain and the section it drains, and the sign at the dry-pipe valve shall list the number and locations of every auxiliary drain on the system.
NOTE Auxiliary drains located in unheated space hold water in the condensate nipple and freeze if they are not drained, so the drain that protects the piping is itself the component that most needs the seasonal drain-down NFPA 25 requires. (9.2.9)

9.3 Inspector's Test Connection

9.3.1 Each dry-pipe system shall be provided with an inspector's test connection at the most remote point of the system, with a valve and an orifice equal to the smallest sprinkler orifice on the system, in accordance with NFPA 13.
9.3.2 The test connection shall discharge where the flow can be observed and where water discharged in freezing weather will not damage the building or create a hazard.
9.3.3 The test connection valve on a dry system shall be arranged so that the piping between the valve and the discharge drains after the test and does not hold water in unheated space.

10 Refrigerated Space Provisions

10.1 Requirements in this article apply where dry piping serves a space held at or below 32°F.
NOTE A freezer is the dry system's hardest service. The gas condenses on contact with the pipe wall, the condensate freezes where it lands, ice grows inward from the wall at the point the pipe enters the cold space, and a trip fills the piping with water that has minutes before it becomes ice. (10.2)
10.3 The dry piping shall enter the refrigerated space from above and shall be arranged so that water drains out of the space and back toward the dry-pipe valve.
10.4 An inspection point shall be provided in the supply pipe at its entry into the refrigerated space, arranged as a removable flanged or grooved spool or as a listed ice-plug detection provision, so that the interior can be examined for an ice plug without cutting the pipe.
NOTE The ice plug forms where the warm supply pipe meets the cold air, and it closes the pipe from the wall inward with no change in supervisory pressure and no signal to any device. The only way to find it is to look. (10.5)
10.6 The penetration of the insulated envelope by the dry piping shall be sealed against vapor migration into the insulation, and the seal shall be compatible with the envelope insulation and the pipe finish.
10.7 After a trip or a test in a refrigerated space, the piping shall be drained and dried, and the space shall be returned to service only after the auxiliary drains and the piping interior have been confirmed free of ice.

11 Sprinklers on Dry Piping

11.1 Sprinklers on dry piping shall be upright sprinklers, listed dry pendent sprinklers, listed dry sidewall sprinklers, or listed horizontal sidewall sprinklers, except that a pendent sprinkler may be installed where both the sprinkler and the branch line serving it are in heated space, in accordance with NFPA 13.
NOTE A standard pendent sprinkler on dry piping hangs below the branch line with its inlet at the low point, so the water left after a trip collects in the sprinkler body and freezes there. An upright sprinkler drains back into the branch line, and a dry pendent carries its seal up at the branch line with an empty barrel below it. (11.2)
11.3 The sprinkler type, orifice, temperature rating, and finish for each area shall be as selected under Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems.
11.4 The barrel length of each dry pendent and dry sidewall sprinkler shall be as indicated on the sprinkler schedule.
11.5 The barrel length of a dry sprinkler shall place its inlet seal in heated space, in accordance with the sprinkler listing and the insulated boundary through which the barrel passes.

12 Waterflow Alarm

12.1 The waterflow alarm for each dry-pipe system shall be initiated by a listed alarm pressure switch connected to the alarm outlet of the dry-pipe valve, and the switch shall transmit a waterflow signal to the fire alarm system in accordance with NFPA 72 and Fire Alarm SystemsFire Alarm SystemsResolves to the current adopted revision.sync/fire-alarm-systems.
12.2 Vane-type waterflow switches shall not be installed in dry piping.
NOTE The pressure switch on the alarm outlet sees full supply pressure the moment the clapper opens, so the alarm on a dry system is transmitted before water has reached the sprinkler rather than after. A vane in dry piping is struck by the slug of gas and water that a trip drives through the pipe, which NFPA 13 prohibits because the vane and the alarm both fail under it. (12.3)
12.4 Where a water motor alarm is selected under the alarm policy of Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems, the alarm line from the dry-pipe valve to the gong shall be arranged to drain and shall not hold water in unheated space.

13 Installation

13.1 Piping shall be installed to the pitch, drainage, and auxiliary drain arrangement of the reviewed pitch and drainage plan, and a deviation that creates a trapped section shall be reported to the Engineer of Record before the section is hung.
13.2 Open ends of dry piping shall be capped whenever work stops, and the piping shall be kept free of cutting debris, thread chips, and construction material until it is closed.
NOTE The trim of a dry-pipe valve, the quick-opening device, and the air maintenance device pass gas and water through small orifices that a chip of pipe scale can close, and the first trip after construction is when the debris that entered during construction arrives at those orifices. (13.3)
13.4 After the hydrostatic test required under Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems, the dry piping shall be drained at the main drain and at every auxiliary drain before the system is placed under supervisory gas, and each auxiliary drain shall be operated and confirmed clear as part of that drain-down.
13.5 The dry-pipe valve shall be installed with its trim oriented as the listing requires and with the gauges, the priming connection, and the intermediate chamber drain reachable from the floor of the valve enclosure.
13.6 A sign shall be provided at the dry-pipe valve stating the calculated system volume, the normal supervisory gas pressure, the low-pressure supervisory setpoint, the supervisory gas, the calculated and the tested water delivery time, and the number and locations of the auxiliary drains, in addition to the signs required by Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems.

14 Testing

14.1 Cold-Weather Testing Sequence

14.1.1 Whether an interim air test may substitute for the hydrostatic test while freezing weather prevents it shall be as indicated in the datasheet.
Interim Cold-Weather Air Testradio
○ Permitted, with the hydrostatic test completed before acceptance
○ Not permitted
NOTE NFPA 13 permits an interim air test at 40 psi for 24 hours where freezing weather prevents a hydrostatic test, with the hydrostatic test to follow when the weather permits. Accepting the interim test keeps the construction schedule through the winter; refusing it keeps the sequence simple at the cost of holding the system until it can be filled. (14.1.2)
14.1.3 Where the interim test is permitted, the hydrostatic test required under Wet Pipe Fire Sprinkler SystemsWet-Pipe Fire Sprinkler SystemsResolves to the current adopted revision.sync/wet-pipe-fire-sprinkler-systems shall be completed before the system is accepted, and the acceptance shall not be conditioned on the interim result alone.

14.2 Air Leakage Test

14.2.1 In addition to the hydrostatic test, each dry-pipe system shall be tested with air or nitrogen at 40 psi for 24 hours, and the pressure loss over the 24 hours shall not exceed 1.5 psi, in accordance with NFPA 13.
14.2.2 The pressure and the ambient temperature at the piping shall be recorded at the start and at the end of the 24 hours, and a pressure change consistent with the temperature change shall not be counted as leakage.
NOTE A dry system leaks air through joints that held water. Water does not pass a thread imperfection that air passes freely, and the hydrostatic test proves the joint against the wrong fluid. The 24-hour air test is the one that finds the joints the compressor would otherwise have spent its life keeping up with. (14.2.3)
14.2.4 Leaks shall be located with a leak-detection solution or an ultrasonic detector, and the joint shall be remade rather than sealed from the outside.
14.2.5 A system that fails the air leakage test shall be retested in full after the repair, and the cost of the repair and of every retest shall be borne by the Contractor.

14.3 Trip Test

14.3.1 Each dry-pipe valve shall be trip tested at acceptance by opening the inspector's test valve fully with the control valve fully open, the system at its normal supervisory pressure, and the quick-opening device in service where one is furnished, in accordance with NFPA 13.
14.3.2 The supervisory pressure at the start, the pressure at which the valve tripped, the time to the trip, and the time from the opening of the test valve to water at the test connection shall be recorded.
14.3.3 Where the system is subject to a water delivery time requirement, the time to water at the test connection shall not exceed the datasheet limit.
14.3.4 Where the tested delivery time exceeds the limit, the Contractor shall correct the cause and repeat the test, and the cost of the correction and the retest shall be borne by the Contractor.
NOTE A tested delivery time longer than the calculated one usually points to one of a few causes: a supervisory pressure set higher than the calculation assumed, an orifice in the trim or the accelerator partly closed by debris, trapped sections holding gas the calculation assumed was pipe, or an air supply that could not be isolated during the test. (14.3.5)
14.3.6 The trip test shall be witnessed by the Authority Having Jurisdiction where the Authority requires it, and the Contractor shall schedule the test with the Authority not less than five working days before it is run.
14.3.7 After the trip test the system shall be drained at the main drain and at every auxiliary drain, the intermediate chamber shall be drained and confirmed dry, the valve shall be reset in accordance with the manufacturer's instructions, and the system shall be restored to its normal supervisory pressure and, where nitrogen is the supervisory gas, purged to the datasheet purity.

14.4 Alarm and Supervisory Device Tests

14.4.1 The alarm pressure switch shall be tested during the trip test by confirming that the fire alarm system received the waterflow signal, and the time from the trip to the signal shall be recorded.
14.4.2 The low-pressure supervisory switch shall be tested by bleeding gas from the system at the inspector's test connection until the switch operates, and the pressure at which it operated shall be recorded and compared with the datasheet setpoint.
14.4.3 Each additional supervisory signal indicated in the datasheet shall be tested by producing its condition, and the receipt of each signal at the fire alarm system shall be recorded.
14.4.4 The air supply shall be tested by depressurizing the system to atmosphere and timing the restoration to normal supervisory pressure, and the time shall not exceed the datasheet restoration time.

15 Spare Parts

15.1 The Contractor shall deliver the spare parts indicated in the datasheet to the Owner before the system is accepted, and shall obtain a signed receipt for them.
Dry-Pipe Spare Parts to Be Furnishedcheckbox
☐ Dry-pipe valve clapper facing and seat seal kit
☐ Quick-opening device service kit
☐ Air compressor intake filter element
☐ Nitrogen generator filter elements for one service interval
☐ One two-valve drum drip assembly
15.2 Spare parts shall be the same make and model as the installed items, delivered in their original packaging, and labeled with the system they serve.