1 Scope
1.1This Standard covers structural framing systems assembled from visually graded dimensional sawn lumber for load-bearing walls, floor systems, roof systems, and their structural connections in new construction and renovation of light-frame buildings.
NOTE Light-frame wood construction is a repetitive-member system: many small, closely spaced members (studs, joists, rafters) share load through sheathing and blocking rather than relying on a few large members. (1.1.1)
NOTE The system serves IBC Type III and Type V buildings, including residential, low-rise commercial, and light industrial occupancies, and applies to both platform-frame and balloon-frame assemblies. (1.1.2)
1.1.3Work of this Standard includes stud walls, floor joists, ceiling joists, rafters, headers, beams, blocking, bridging, ledgers, rim boards, sill plates, sill anchorage, hold-down anchorage, and nailed or screwed framing connections.
1.1.4Both the prescriptive conventional light-frame path of IBC Section 2308 / IRC Chapter 6 and the engineered path using AWC NDS allowable stress design or LRFD are within scope; the structural drawings and this Standard together establish which path governs each assembly.
1.1.5Pressure-preservative-treated lumber for sill plates, ledgers, and other members in contact with concrete, masonry, or the ground is included.
NOTE Engineered wood headers and beams (LVL, PSL) used as drop-in substitutes for dimensional headers are addressed here only at the interface; the engineered product itself is specified with its product Standard. (1.1.6)
1.2Boundaries with adjacent Standards.
NOTE Heavy timber and mass timber structural systems (glulam frames, CLT panels, NLT, DLT) are not part of this Standard. (1.2.1)
NOTE Mass timber and other large-section systems behave and are detailed differently from repetitive light framing; see
Mass Timber.
(1.2.2) NOTE Non-structural rough carpentry — blocking, nailers, grounds, wood curbs, rough bucks, sleepers, and furring that carries no structural load — is not part of this Standard; see
Rough Carpentry.
(1.2.4) NOTE Finish trim, millwork, and architectural woodwork are not part of this Standard; see
Finish Carpentry.
(1.2.5) NOTE Glued laminated timber, structural composite lumber, and wood I-joists are specified with the engineered wood product being used, except where used solely as a dimensional-lumber substitute header as noted above. (1.2.6)
NOTE Gypsum sheathing and the fire-resistance rating of wall, floor, and roof assemblies are not part of this Standard; see
Gypsum Board Assemblies.
(1.2.7) 2 Referenced Standards
2.1Materials, design, and installation shall comply with the latest adopted edition of each of the following except where a specific edition is cited.
2.2Where the structural drawings, this Standard, and a referenced document conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
NOTE The adopted building code edition for the project jurisdiction governs over the editions listed below where the jurisdiction has amended or pinned a different edition. (2.2.1)
| Standard |
Title |
| IBC 2024 Chapter 23 |
International Building Code — Wood (Section 2308 conventional light-frame construction) |
| IRC 2024 Chapters 5 and 6 |
International Residential Code — Floors (R502) and Wall Construction (R602) |
| ANSI/AWC NDS-2024 |
National Design Specification for Wood Construction (with March 2025 addendum) |
| AWC NDS Supplement-2024 |
NDS Supplement: Design Values for Wood Construction |
| ANSI/AWC WFCM-2024 |
Wood Frame Construction Manual for One- and Two-Family Dwellings |
| ANSI/AWC SDPWS-2021 |
Special Design Provisions for Wind and Seismic |
| ANSI/AWC FDS-2024 |
Fire Design Specification for Wood Construction |
| PS 20-23 |
American Softwood Lumber Standard |
| ASTM D245-22 |
Establishing Structural Grades and Allowable Properties for Visually Graded Lumber |
| ASTM D1990-19 |
Allowable Properties for Visually Graded Dimension Lumber from In-Grade Tests |
| ASTM D2555-17 |
Establishing Clear Wood Strength Values |
| ASTM D4761-19 |
Mechanical Properties of Lumber and Wood-Based Structural Materials |
| AWPA U1 |
Use Category System: User Specification for Treated Wood |
| AWPA C20 |
Structural Lumber — Fire-Retardant Treatment by Pressure Process (interior type) |
| AWPA C27 |
Plywood — Fire-Retardant Treatment by Pressure Process (exterior type) |
| NFPA 13 |
Standard for the Installation of Sprinkler Systems |
| NFPA 1 |
Fire Code |
3 Submittals
3.1Action Submittals.
3.1.1The Contractor shall submit the following action items for review before fabrication or delivery:
- Product data for each lumber species, grade, and size, including the grade-marking agency and the basis of grade certification under PS 20.
- Product data and treatment certification for all pressure-preservative-treated lumber, stating the preservative, AWPA use category, and retention.
- Product data and treatment certification for all fire-retardant-treated lumber, stating the treatment type and any required strength-adjustment factors.
- Manufacturer data and ICC-ES evaluation reports for proprietary metal framing connectors, hold-downs, and post-installed anchors.
- Shop drawings for engineered lumber headers and beams (LVL, PSL) used in lieu of dimensional members, including reactions delivered to the supporting framing.
☑ Lumber product data and grade certification
☑ Preservative-treatment certification (AWPA use category and retention)
☐ Fire-retardant-treatment certification and strength factors
☐ Metal connector / hold-down product data and ICC-ES reports
☐ Post-installed anchor product data and ICC-ES reports
☐ Engineered header / beam shop drawings and reactions
3.2Informational Submittals.
3.2.1The Contractor shall submit the following informational items:
- Mill certificates or grade stamps documenting species, grade, and moisture-content classification (KD-19, S-DRY, or S-GRN) for each lumber shipment.
- Special-inspection coordination documents where IBC Section 1705.5 special inspection of shear walls or diaphragms is required.
- Fastener and connector schedules correlating the structural drawings' nailing schedule to the products supplied.
☑ Mill certificates / grade stamps with moisture classification
☐ Special-inspection coordination documents
☑ Fastener and connector schedules
3.3Closeout Submittals.
3.3.1The Contractor shall submit the following closeout items:
- Field-correction records for any notched, bored, or cut structural members and the engineer-approved reinforcement applied.
- Special-inspection reports for shear walls, hold-downs, and diaphragms where special inspection was required.
☐ Field-correction and reinforcement records
☑ Special-inspection reports
4 Quality Assurance
4.1Grading and certification.
4.1.1All structural lumber shall conform to PS 20, the American Softwood Lumber Standard, and shall bear the grade stamp of an inspection agency accredited by the American Lumber Standard Committee.
NOTE The grade stamp is the legal record that the member carries the design values used in the structural calculations; an unstamped member has no assigned design value and is unenforceable. (4.1.2)
4.1.3Each structural member shall be grade-stamped with species or species group, grade, moisture classification, the producing mill, and the certifying agency.
4.1.4Lumber on which the grade stamp has been cut away (for example at trimmed ends) shall not be used in a structural location unless re-graded in place by a certified grader, or the cut member relocated so the stamp remains visible.
4.2Qualifications and design responsibility.
4.2.1Engineered framing — members and connections designed outside the IBC Section 2308 prescriptive limits — shall be designed by a licensed Engineer of Record under AWC NDS allowable stress design or LRFD.
4.2.2The prescriptive conventional light-frame path of IBC Section 2308 may be used only within its stated limits; assemblies that exceed those limits shall be engineered.
NOTE The prescriptive path of IBC Section 2308 is capped at three stories above grade plane, a maximum bearing-wall height of 10 ft, and is not permitted in Seismic Design Category E or F without engineering. Commercial projects routinely exceed these caps, which forces full NDS engineering — confirm the path before relying on prescriptive tables. (4.2.3)
4.2.4Where any portion of the structure is designed by full engineering, the prescriptive tables shall not be mixed into the engineered load path without the Engineer of Record's confirmation that load paths remain continuous.
4.3Special inspection.
4.3.1Where the building is in Seismic Design Category C or above, special inspection of high-load diaphragms, shear-wall nailing, and hold-down installation shall be provided in accordance with IBC Section 1705.5.
4.3.2Special inspection of shear-wall and diaphragm fastening shall verify nail size, spacing, edge distance, and penetration against the structural drawings' nailing schedule before the assembly is concealed.
NOTE Omitting required special inspection is a common cause of failed inspections at certificate of occupancy, because shear-wall nailing cannot be verified once sheathing and finishes are closed in. (4.3.3)
5 Environmental and Service Conditions
5.1Moisture and service condition.
5.1.1Lumber enclosed in conditioned or weather-protected construction shall be furnished kiln-dried to a maximum moisture content of 19% (KD-19) at time of installation.
NOTE Green or surfaced-green (S-GRN) lumber installed in enclosed framing shrinks as it dries in service, causing nail pops, drywall cracking, and loosened connections. KD-19 lumber is treated as dry-service, so the wet-service moisture factor CM = 1.0 applies (IBC Section 2303.1.5). (5.1.2)
5.1.3Where members will be wet in service — exposed to weather, in ground contact, or with sustained in-service moisture content above 19% — the wet-service moisture factor CM shall be applied to the NDS design values.
5.1.4Treated lumber shall be re-dried after treatment to the project's required moisture content where it is installed in enclosed construction, to avoid in-service shrinkage of wet treated members.
5.2Preservative-treated locations.
5.2.1Sill plates and sleepers resting on concrete or masonry in direct contact with the ground or exposed to weather shall be pressure-preservative-treated or naturally durable wood.
5.2.2Wood members in direct ground contact, embedded in concrete, or otherwise subject to soil moisture shall be pressure-preservative-treated to the ground-contact use category.
NOTE The boundary between above-ground and ground-contact retention is set by AWPA U1 use categories: UC3B for above-ground exterior, UC4A for general ground contact (including sill plates on slabs above grade), and UC4B for severe or critical ground contact. Specifying the wrong category lets the contractor default to the cheapest retention, which may not be code-compliant for the application. (5.2.3)
5.2.4Where treated lumber is in contact with metal connectors, fasteners and connectors shall be hot-dip galvanized, stainless steel, or otherwise rated by the connector manufacturer for use with the specified preservative.
NOTE Modern waterborne preservatives (ACQ, CA-C, MCA) are more corrosive to steel than legacy CCA; using under-rated fasteners with them causes accelerated connector failure. See
Dampproofing where a moisture break is also detailed at the sill.
(5.2.5) 6 Lumber Materials
6.1Species and grade.
6.1.1Lumber shall be specified by both species (or species group) and grade; neither alone is sufficient.
NOTE Species and grade together fix the design values. Calling for "No. 2 or Better" without a species is meaningless, because No. 2 design values differ dramatically between species groups — Southern Pine No. 2 2x10 has a tabulated Fb of 1500 psi while Spruce-Pine-Fir No. 2 2x10 is 875 psi. Both pieces of information are mandatory. (6.1.2)
6.1.3The species group, grade, and moisture classification for each framing use shall be as scheduled on the structural drawings or as selected below, and shall not be substituted without the Engineer of Record's approval.
● Douglas Fir-Larch
○ Hem-Fir
○ Southern Pine
○ Spruce-Pine-Fir
○ Stud
● No. 2
○ No. 1
○ Construction
● No. 2
○ No. 1
○ Select Structural
● KD-19 (kiln-dried, 19% max)
○ S-DRY (surfaced dry, 19% max)
○ S-GRN (surfaced green)
6.1.4NDS Supplement design values shall be applied with all governing adjustment factors; the tabulated reference value alone is never the allowable design value.
NOTE The NDS tabulated value (for example No. 2 Douglas Fir-Larch 2x10 Fb = 900 psi from NDS Supplement Table 4A) must be adjusted by the applicable factors — load duration CD, wet service CM, temperature Ct, size CF, incising Ci, repetitive member Cr, and others — before it becomes the allowable design value. Using raw table values overstates capacity. Cite NDS Supplement Tables 4A and 4B for the specific value; never invent a design value. (6.1.5)
6.2Sizes.
6.2.1Dimensional lumber shall conform to the nominal and dressed sizes of PS 20; references to nominal size (2x4, 2x6, and similar) denote PS 20 dressed dimensions.
6.2.2Pre-cut studs furnished for standard wall heights (for example 92-5/8 in. for an 8-ft finished wall) shall match the wall height and plate count shown on the drawings.
6.3Preservative treatment.
6.3.1Pressure-preservative treatment shall conform to AWPA U1 for the use category and retention scheduled for each location.
○ UC3B above-ground exterior
● UC4A general ground contact
○ UC4B heavy-duty ground contact
○ Alkaline Copper Quaternary (ACQ)
○ Copper Azole (CA-C)
● Micronized Copper Azole (MCA)
○ Borate (interior, protected)
6.4Fire-retardant treatment.
6.4.1Where the code requires fire-retardant-treated wood in concealed combustible spaces, exterior walls, or other locations in IBC Type III and Type V-A construction, fire-retardant-treated lumber conforming to AWPA C20 (interior type) or AWPA C27 (exterior type) shall be furnished.
NOTE Fire-retardant-treated lumber is a standard off-the-shelf product. The key coordination is that the treatment reduces lumber design values — the treater's published strength-adjustment factors must be applied to the NDS values, and members must not be cut after treatment in a way that exposes untreated wood beyond the treater's allowances. (6.4.2)
● None
○ Interior type (AWPA C20)
○ Exterior type (AWPA C27)
7 Bearing Walls and Studs
7.1Stud walls.
7.1.1Exterior and interior bearing-wall studs shall be sized, spaced, and continuous as scheduled on the structural drawings or as selected in the stud datasheet, and shall not exceed the prescriptive height limit for the selected size and spacing.
NOTE Under the prescriptive path, 2x4 bearing studs are limited to 10 ft at 16 in. o.c. and 2x6 bearing studs to 10 ft at 24 in. o.c. (IBC Section 2308.5). Energy code is now an equal driver of stud size: 2x4 walls often cannot accommodate the continuous or cavity insulation required by IECC, so 2x6 at 16 or 24 in. o.c. has become the common exterior bearing wall — confirm the wall assembly with the energy model before fixing stud size. (7.1.2)
7.1.3Studs shall bear on a continuous bottom plate and be capped by a top plate; exterior and bearing walls shall have a double top plate with laps offset and splices lapped not less than the spacing of the studs, except where a single top plate is engineered and tied across joints.
7.1.4Studs shall be installed with the wide face perpendicular to the wall plane and shall be full-length between plates without splices, except where an engineered splice is detailed.
● 16 in. o.c.
○ 24 in. o.c.
7.1.5Studs notched or bored for piping, conduit, or ducts shall not exceed the depth and location limits of IBC Section 2308.5.9 / IRC R602.6; over-notched or over-bored studs shall be reinforced or replaced.
7.2.1Headers over openings in bearing walls shall be sized for the span and tributary load as scheduled, by the prescriptive header tables (IBC Table 2308.4.1.1 or IRC Table R602.7(1)) within their limits, or by engineering for spans or loads beyond the tables.
NOTE Prescriptive header tables cover clear spans up to roughly 12 ft with No. 2 or better lumber under typical loads; longer spans, point loads, or multi-story tributary loads push the header into engineered LVL or PSL. Where an engineered header is used, coordinate its procurement and reactions with
Rough Carpentry so that the member engineered on the structural drawings is the member actually installed.
(7.2.2) 7.2.3Headers shall bear on jack (trimmer) studs at each end, with the number of jack and king studs as scheduled for the header reaction.
● Dimensional lumber (built-up)
○ LVL (laminated veneer lumber)
○ PSL (parallel strand lumber)
8 Floor Framing
8.1Joists.
8.1.1Floor joists shall be sized, spaced, and spanned as scheduled on the structural drawings or by the prescriptive span tables (IRC Table R502.3.1) within their limits, for the design live load and the selected species and grade.
NOTE The residential floor design live load is 40 psf (IBC Table 1607.1); sleeping rooms and certain occupancies use lower or higher values, so confirm the controlling live load before selecting from a span table. Douglas Fir-Larch No. 2 and Southern Pine No. 2 are the common species; both list E = 1,600,000 psi in the NDS Supplement, but their bending values differ, so the span table must match the actual species. (8.1.2)
8.1.3Joists shall bear not less than 1-1/2 in. on wood or metal and not less than 3 in. on masonry or concrete, except where an engineered hanger or ledger provides bearing.
8.1.4Joists framing into a beam, ledger, or header shall be supported by metal joist hangers selected for the joist size and reaction; toe-nailing alone shall not be used to carry a joist reaction.
● 40 psf residential
○ 50 psf light commercial
○ 60 psf
○ 12 in. o.c.
● 16 in. o.c.
○ 24 in. o.c.
8.2Blocking, bridging, and rim.
8.2.1Solid blocking or approved bridging shall be installed in floor joists at intervals not exceeding 8 ft and at points of bearing, in accordance with IBC Section 2308.4.6 / IRC R502.7.
NOTE Blocking and bridging keep deep, narrow joists from rotating or buckling laterally under load and distribute concentrated loads between adjacent joists. Without it, joists can roll at the bearing and the floor loses its diaphragm continuity. (8.2.2)
8.2.3A continuous rim board or rim joist shall close the ends of the floor framing, transfer wall loads through the floor, and provide the boundary nailing for the floor diaphragm.
8.2.4Joists notched or bored shall comply with the depth, length, and location limits of IBC Section 2308.4.2.1 / IRC R502.8; cuts beyond those limits shall be engineered and reinforced.
9 Roof and Ceiling Framing
9.1Rafters and ceiling joists.
9.1.1Conventional roof framing shall consist of rafters with a ridge board and ceiling joists or rafter ties that resist the outward thrust of the rafters, sized and spaced as scheduled or by the prescriptive rafter tables (IRC Tables R802.5.1) within their limits.
NOTE In a conventional rafter roof, the ceiling joists or rafter ties are the tension members that keep the walls from spreading under roof load; omitting or improperly lapping them lets the ridge sag and the walls bow outward. Pre-engineered wood trusses are an alternative roof system and are designed and supplied separately from this Standard. (9.1.2)
9.1.3The minimum roof design live load shall be 20 psf, except where the ground snow load or other governing load produces a higher demand (IBC Table 1607.1).
NOTE In most jurisdictions the ground snow load governs the roof design over the 20 psf minimum; the structural drawings carry the controlling roof load for the project. (9.1.4)
9.1.5Rafters shall be tied at the ridge and bear on a top plate or beam; where the rafter slope or span exceeds the prescriptive tables, the roof shall be engineered.
○ 20 psf minimum roof live load
● Ground snow load governs
9.2Ledgers.
9.2.1A ledger supporting roof, floor, or deck framing against a wall shall be attached for the gravity reaction and any lateral load, by through-bolting, lag screws, or approved connectors as scheduled, and shall not rely on toe-nailing or on withdrawal of fasteners loaded in tension.
NOTE Deck and roof ledger failures are frequently traced to fasteners loaded in withdrawal or to a ledger attached only to wall sheathing rather than to the structure behind it; the ledger connection is an engineered detail. Ledgers in contact with concrete or masonry are also a preservative-treated location. (9.2.2)
10 Connections and Anchorage
10.1Nailed and screwed connections.
10.1.1Framing connections shall be made with the nail or screw type, size, and spacing of the structural drawings' nailing schedule, which governs over the default schedule of IBC Table 2304.10.1.
NOTE The 80% framing fastener is the 16d common nail (0.162 in. diameter x 3.5 in.). The most common connection RFI in light framing is a mismatch between the shear-wall nailing called on the drawings (for example 8d at 4 in. o.c. at panel edges) and a spec that defaults silently to the standard nailing table — the drawings' schedule must be the controlling document and this Standard must defer to it. (10.1.2)
10.1.3Common, box, and sinker nails are not interchangeable; the nail type named in the schedule shall be supplied, because shank diameter and thus capacity differ between them.
10.1.4Pneumatically driven fasteners shall match the diameter and length of the specified hand-driven nail; clipped-head or undersized collated nails shall not be substituted for full-round-head common nails where the schedule calls for them.
10.1.5Where treated or fire-retardant-treated lumber is fastened, fasteners and connectors shall be corrosion-rated for that treatment as required under the Environmental and Service Conditions section.
10.2Sill anchorage.
10.2.1Sill plates shall be anchored to the foundation with anchor bolts not less than 1/2 in. in diameter embedded not less than 7 in. into concrete or grouted masonry, spaced not more than 6 ft on center, with not less than two bolts per plate piece and a bolt within 12 in. of each plate end (IBC Section 2308.3.1).
NOTE These are the prescriptive minimums; shear-wall and high-wind or high-seismic conditions tighten them — for example 3/4 in. diameter bolts at shear-wall ends. The anchorage shown on the structural drawings governs where it is more stringent. (10.2.2)
10.2.3Anchor bolts shall be set with a plate washer of the size required by the drawings between the nut and the sill plate where the wall resists lateral load.
10.2.4Cast-in-place (wet-set) anchor bolts shall be the default; post-installed anchors shall be used only where shown and shall be a mechanical or adhesive anchor qualified by a current ICC-ES evaluation report for the substrate and loading.
NOTE Wet-set and post-installed anchors are not interchangeable: post-installed anchors require an ICC-ES report and a separate adhesive or mechanical-anchor specification, and adhesive anchors in tension have edge-distance, embedment, and special-inspection requirements that wet-set bolts do not. (10.2.5)
● 1/2 in.
○ 5/8 in.
○ 3/4 in.
1672
Default: 72 in. on center
● Cast-in-place (wet-set)
○ Post-installed (ICC-ES qualified)
10.3Hold-downs and shear-wall anchorage.
10.3.1Hold-down devices and their anchorage shall be installed at shear-wall ends and other locations where the lateral-load-resisting system develops overturning tension, sized by the shear-wall design under AWC SDPWS-2021 and as scheduled on the structural drawings.
NOTE Hold-downs anchor the tension chord of a shear wall to the foundation or to the framing below so the wall does not overturn under wind or seismic load. They are sized member by member by the lateral designer; this Standard requires that the scheduled device, anchor, and installation torque be furnished and installed exactly as shown. (10.3.2)
10.3.3Hold-down anchor bolts, embedment, and edge distance shall be as scheduled; substitution of a different hold-down model or anchor shall require the Engineer of Record's approval, because hold-down capacity, deflection, and required anchor differ between models.
10.3.4The hold-down nailing or bolting to the framing member shall be installed in full, in the holes provided, before the assembly is concealed and inspected.
● Yes, per shear-wall schedule
○ No (gravity-only framing)
11 Wall Sheathing for Lateral Resistance
11.1Structural sheathing.
11.1.1Where walls resist lateral load as shear walls, the structural panel or board sheathing type, thickness, and edge and field nailing shall be as scheduled and shall match the shear-wall design under AWC SDPWS-2021.
NOTE The structural capacity of a shear wall comes almost entirely from its sheathing nailing schedule — edge nail spacing, panel thickness, and whether panel edges are blocked. The sheathing material is coordinated with the wall assembly and water-resistive barrier; see
Gypsum Board Assemblies where gypsum contributes to the assembly rating.
(11.1.2) 11.1.3Shear-wall panel edges shall be blocked where the schedule requires blocked diaphragm action, with all panel edges supported on and nailed to framing or blocking.
11.1.4The edge and field nail spacing installed shall be verified against the shear-wall schedule by special inspection where required, before the sheathing is covered.
● Wood structural panel (sheathing-grade plywood or OSB)
○ Diagonal board sheathing
○ Non-structural (lateral resisted elsewhere)
12 Installation
12.1General.
12.1.1Framing shall be erected plumb, level, and true to line, with members fully bearing and connections made before loads are applied; temporary bracing shall hold the frame stable until permanent sheathing and connections are complete.
12.1.2Framing members shall not be cut, notched, or bored beyond the limits of the governing code section; any cut that exceeds those limits shall be reviewed by the Engineer of Record and reinforced as directed before being concealed.
NOTE The most damaging field decision in wood framing is cutting a structural member to make room for a pipe or duct after the fact. Code limits on notch depth and bored-hole size and location exist because the cut removes load-carrying fiber at the worst location; an over-cut joist or stud must be reinforced or replaced, not concealed. (12.1.3)
12.1.4Multiple-member built-up beams and headers shall be fastened together along their length per the schedule so the plies act together; the plies of a built-up member nailed only at the ends do not share load as designed.
12.1.5Bearing of joists, rafters, and beams shall be solid; shimming with non-structural material to make up bearing length is not permitted.
12.2Treated and fire-retardant lumber handling.
12.2.1Field cuts and bored holes in pressure-preservative-treated lumber shall be field-treated with a compatible preservative in accordance with AWPA M4 to restore protection at the exposed surface.
NOTE A saw cut exposes untreated heartwood; without field treatment the cut becomes the point where decay begins, defeating the original treatment. This is mandatory for ground-contact and exterior members. (12.2.2)
12.2.3Fire-retardant-treated members shall be installed with the treater's published strength-adjustment factors reflected in the design and shall not be ripped or re-sawn in a way that exceeds the treater's cutting allowances.
12.3Diaphragm and shear-wall sequencing.
12.3.1Floor and roof diaphragm sheathing and shear-wall sheathing shall be nailed in full to the scheduled boundary, edge, and field spacing before the framing is loaded or concealed, so the lateral system is complete and inspectable.
13 Delivery, Storage, and Handling
13.1Lumber shall be delivered bundled and grade-stamped, and shall be protected from weather, ground moisture, and standing water throughout storage and erection.
13.1.1Lumber shall be stored off the ground on level supports, stacked to drain, and covered to shed water while allowing air circulation, so that kiln-dried members do not reabsorb moisture before installation.
13.1.2Treated lumber shall be stored separated from untreated lumber and finish materials, with the treatment certification kept with the bundle until installed.
13.1.3Damaged, checked, split, or excessively warped members shall be rejected and shall not be incorporated into the structural frame.
14 Warranty
14.1The Contractor shall warrant that the wood framing is furnished and installed in accordance with this Standard, the structural drawings, and the referenced codes, and is free from defects in materials and workmanship for the project's warranty period.
14.1.1Latent framing defects discovered within the warranty period — including members of incorrect species or grade, missing or undersized fasteners, missing hold-downs or blocking, and untreated members in treated locations — shall be corrected at no cost to the Owner.
15 Spare Parts
15.1Structural framing is a built-in-place system and ordinarily carries no spare-parts requirement; where the drawings call for attic stock, the Contractor shall furnish the quantity scheduled.
15.1.1Where treated or fire-retardant-treated members are difficult to match later, the Contractor should deliver a documented surplus of each treated grade and size to the Owner for future repairs.